Output Values
Description
Value
PVI – 6000-OUTD
Nominal output power
6000 W
Grid voltage, maximum range
200 to 270 Vac
Grid voltage, nominal
230 Vac
Grid voltage, operating range as per
AS4777
from 89% to 115% of nominal voltage
(from 205 to 264Vac for
V
nom
=230Vac)
Grid frequency, maximum range
45 to 55 Hz
Grid frequency, nominal
50 Hz
Grid frequency, operating range as per
AS4777
47.1 to 52.9 Hz
Nominal output current
26 Arms
Max. output current
30 Arms
Output over current protection
40 Arms
8.3.
Grid protection characteristics
Anti islanding protection
Complies with: