Page 22 of 89
(PVI-6000-OUTD-xx-AU Rev:1.0)
3.3.
Selecting the place of installation
Place of installation should be selected based on the following considerations:
Height from ground level should be such to ensure that display and status LEDs
are easy to read.
Select a well ventilated place sheltered from direct sun radiation. Choose a
place that allows unobstructed air flow around the unit.
Allow sufficient room around the unit to enable easy installation and removal
from the mounting surface.
A door is provided on unit front to allow for hardware maintenance; the USB
port for software connection is on right side wall of the inverter (protected by a
cover). Ensure free access to the right side, otherwise you will have to remove
the unit from its mounting surface.
The following figure shows the recommended minimum clearances around the
inverter:
Fig.5 Place of installation - Minimum clearances around AURORA
150mm
(6”)
150mm (6”)
200mm (8”)
50mm
(2”)