FAULT MESSAGES. DESCRIPTIONS AND ACTIONS
11.
FAULT MESSAGES. DESCRIPTIONS AND
ACTIONS
When a fault occurs the SD700 will stop the motor and show the generated fault on the display. You can
display this fault in the programming line (lower line) while motor current and the speed values at the
moment of the fault are displayed in the upper line.
It is possible to navigate through the additional display lines to access other status parameters without
resetting the fault. These additional status parameters offer further information about the moment at which
the fault occurred. Additionally, the FAULT led will blink and the fault message will be displayed until the
fault is remedied and the drive is reset.
Figure 11.1 Fault displaying - Programming Line
11.1.
Description of Faults List
DISPLAY
DESCRIPTION
F0 NO FAULT
Drive is operative. There is no fault.
F1 I LIM FLT
Output current has reached a dangerous level. Its value is above 220% of the drive rated current. Protection is
activated instantaneously.
F2 V LIM FLT
DC Bus voltage has reached a dangerous level >850Vdc. Hardware Protection. Drive will turn off the output to
the motor.
F3 PDINT FLT
DC Bus voltage and the output current of the equipment have reached dangerous levels.
F4 U+DESAT
F5 U - DESAT
F6 V + DESAT
F7 V - DESAT
F8 W + DESAT
F9 W - DESAT
Internal protection within the appropriate IGBT semiconductor has acted.
F10 NEG IGBT
Automatic internal protection of several of the IGBT semiconductors has acted.
F11 VIN LOSS
Power supply loss of any input phase for a time higher than 20ms has occurred.
F12 IMB V IN
Input voltage imbalance greater than ±10% of average input power supply of SD700 for a time higher than
100ms.
F13 HI V IN
Average supply voltage has exceeded the value set in ‘G11.6 HIGH VOLT’ for greater than the time set in 'G11.7
HIGH V TO'.
F14 LW V IN
Average supply voltage is lower than the value set in ‘G11.4 LOW VOLT’ for greater than the time set in ‘G11.5
LOW V TO’.
F15 CURL Vdc
Unstable bus voltage. There is a DC Bus voltage ripple higher than 100Vdc for more than 1.1sec.
F16 HI Vdc
DC Bus voltage has exceeded critical operating level (>850Vdc). Software Protection.
F17 LW Vdc
DC Bus voltage is lower than critical operating level (<350Vdc).