SDRIVE 700
POWER ELECTRONICS
60
DESCRIPTION OF PROGRAMMING PARAMETERS
10.8.
10.8.1.
Subgroup 8.1 – S8.1: Output Relays
Parameter
Name /
Description
Range
Default
value
Function
Set on
RUN
1 SEL RELAY 1=02
G8.1.1
/
Selection of
Relay 1 control
source
00 – 31
02
It configures the operation of each output relay according to the
options shown in the following table:
OPT
DESCRIPTION
FUNCTION
00
ALWAYS OFF
Output is not active.
01 ALWAYS
ON When the drive is powered the
output relay is activated.
02 NO
FAULTS
There is no fault in the drive. When
a fault occurs, the relay will be
activated.
03
GENERAL
FAULT
Drive fault or low input voltage will
activate the relay.
04 START
Relay is active when the drive has
received the start command.
05 RUN
The relay will be energized after the
drive is started (the speed is
increasing).i.e. G8.1.1 = 05 and
G8.1.5 = 06. Start command is on,
relay 1 is on and immediately relay
2 is on. Stop command is activated,
then relay 1 is automatically off BUT
relay 2 will be on until drive was
completely stopped.
06 READY
Drive is ready for start (no fault and
no warning).
07
ZERO SPEED
Drive is running at zero speed.
08 SET
SPEED Speed has reached the value set as
reference.
09
SP
DIRECTION
The relay is activated when the
speed direction is negative.
10
RESERVE
Reserved for future use.
11
SP REF
DIRECT
The relay is activated when the
speed refer. direction is negative.
12
RESERVE
Reserved for future use.
13
SP LIMIT
Speed limit has been reached.
14 CURR
LIMIT Motor current limit has been
reached.
15 VOLT
LIMIT DC Bus voltage limit has been
reached.
16
TORQ LIMIT
Torque limit has been reached.
17
COMPARATOR1
When the comparator 1 output is
active, relay is activated.
18
COMPARATOR2
When the comparator 2 is output
active, relay is activated.
19
COMPARATOR3
When the comparator 3 output is
active, relay is activated.
20
ACC / DEC 2
Relay is activated if the alternative
ramps are used.
21
REFERENCE 2
Relay is activated if reference 2 has
been selected.
22 STOP
2
Relay is activated if stop mode 2 is
used.
23
SP LIMIT 2
Relay is activated if the alternative
speed limits have been selected.
24 DC
BRAKE Relay is activated if DC brake is
active.
25
RESERVE
Reserved for future use.
26
RESERVE
Reserved for future use.
27
RESERVE
Reserved for future use.
Note:
See following page.