POWER ELECTRONICS
SD300
DESCRIPTION OF PROGRAMMING PARAMETERS
173
Group 6: Outputs
→
OU
Screen Description
Default
value
Range
Function
Set on
RUN
OU.1
Analog output
1 mode
selection
Frequen
cy
0 to 15
The analog output 1 is programmable
according to the following table:
OPT. DESCR. FUNCTION
0
Frequency
Proportional signal to the
motor speed. For the
maximum
frequency
defined
in
M2.20,
analogue value will be
10V/20mA.
1
O/pCurr
Proportional signal to the
motor current. 10V/20mA
are generated when the
drive rated current is at
200%.
2
O/pVolt
Proportional signal to the
motor voltage. For the
voltage value defined in
bA.15, analogue value will
be 10V/20mA.
3
DCLink
V
Proportional signal to the
bus DC voltage. The
analogue
output
is
10V/20mA when the DC
voltage is 410Vdc for
220Vac
drives
and
820Vdc
for
400Vac
drives.
4
Torque
Proportional signal to the
generated torque.
Outputs 10V/20mA at
250% of motor rated
torque.
5
O /
pPower
Proportional signal to the
output power. 10V/20mA
are generated operating
200% of the nominal
power.
Note
: Continues on the next page.
YES
Содержание SD 300 Series
Страница 1: ...SD300 GETTING STARTED MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE ...
Страница 2: ......
Страница 3: ...Variable Speed Drive Getting Started Manual Edition February 2019 SD30IM01GI Rev G ...
Страница 159: ...POWER ELECTRONICS SD300 DESCRIPTION OF PROGRAMMING PARAMETERS 157 Power off delay ...
Страница 174: ...SD300 POWER ELECTRONICS 172 DESCRIPTION OF PROGRAMMING PARAMETERS TI configuration ...
Страница 352: ......
Страница 353: ......
Страница 354: ...24H TECHNICAL ASSISTANCE 365 DAYS A YEAR FIND YOUR NEAREST DELEGATION POWER ELECTRONICS COM CONTACT ...