background image

Powered by Safety

®

IB-51807  

PV System 38® Remote Racking Device  

Mechanical Connection

Содержание PV 38 IB-51807

Страница 1: ...Powered by Safety IB 51807 PV System 38 Remote Racking Device Mechanical Connection ...

Страница 2: ... System 38 Remote Racking Device Mechanical Connection Contact Information Powell Electrical Systems Inc www powellind com info powellind com Service Division PO Box 12818 Houston Texas 77217 2818 Tel 713 944 6900 Fax 713 948 4569 ...

Страница 3: ...ted in ANSI Z535 4 2002 4 13 4 13 3 as a signal word but used in this manual is IMPORTANT This is defined as IMPORTANT indicates a section of the manual covering a non hazardous situation but one where Powell feels proper attention is warranted IMPORTANT IMPORTANT Qualified Person For the purposes of this manual a qualified person as stated in NFPA 70 is one familiar with the construction and oper...

Страница 4: ...ipment Description 5 A General 5 B Motor Control Box 5 C Electric Racking Device 5 Ch 4 Installation Operation 8 A Receiving 8 B Handling 8 C Operation 8 D Inserting the Circuit Breaker into Switchgear Compartment 12 1 Racking Mechanism 12 2 Inserting the Circuit Breaker Into the Compartment 12 E Removing the Circuit Breaker from the Switchgear Compartment 14 Powered by Safety i IB 51807 Contents ...

Страница 5: ...king Device 10 Figure 5 Remote Racking Device Installed 10 Figure 6 Connecting the Motor to the Control Box 11 Figure 7 Activate Remote Racking Device 11 Figure 8 Circuit Breaker in Test Disconnect Position 11 Figure 9 Circuit Breaker in Connected Position 11 Powered by Safety ii IB 51807 PV System 38 Remote Racking Device Mechanical Connection Figures ...

Страница 6: ...ponents or wiring of this equipment the power supply must be disconnected Failure to follow this warning may result in injury or death IMPORTANT IMPORTANT The information in this instruction bulletin is not intended to explain all details or variations of the Powell equipment nor to provide for every possible contingency or hazard to be met in connection with installation testing operation and mai...

Страница 7: ...ment described in Ch 1 General Information A Scope The illustrations in this document are provided as general information to aid in showing component locations only All illustrations are shown using deenergized equipment Be sure to follow the appropriate safety precaution while handling any of the equipment Failure to do so may result in serious injury or death WARNING WARNING To the extent requir...

Страница 8: ... conductors or circuit parts apply ground connecting devices rated for the available fault duty B Safety Guidelines Each user has the responsibility to instruct and supervise all personnel associated with usage installation operation and maintenance of this equipment on all safety procedures Furthermore each user has the responsibility of establishing a safety program for each type of equipment en...

Страница 9: ...e located in various places in and on the switchgear and on the circuit breaker Always observe these warnings and caution labels Do NOT remove or deface any of these warning caution labels IMPORTANT IMPORTANT IB 51807 PV System 38 Remote Racking Device Mechanical Connection ...

Страница 10: ...rd enables the user to move to a remote location from the circuit breaker during the racking in or racking out procedures The motor control box power supply cord Figure 1 f plugs into a 110VAC outlet C Electric Racking Device The electric racking device uses a hanger bracket Figure 1 b to connect to the bottom flange of the upper compartment The drive socket Figure 1 c engages the racking shaft th...

Страница 11: ...ystem 38 Remote Racking Device Mechanical Connection Figure 1 PV System 38 Remote Racking Device b c d e g f h a a Adjusting Screws b Hanger Bracket c Drive Socket d Motor Adjustment Knob e Power Cord Receptacle f Power Cord g Control Box Cord h Control Box ...

Страница 12: ... Safety 7 Equipment Description IB 51807 Figure 2 Close up of Control Box a b c e f d a Electrical Cord b In Indicator Light c Out Indicator Light d Power Switch e In Out Selector Switch f Push Button g Handle g ...

Страница 13: ...he equipment CAUTION CAUTION Do NOT handle or carry the racking device by the power cords Damage to the power connections may cause an electrical short The power cords should be inspected for any signs of damage before each use CAUTION CAUTION C Operation Do NOT work on an energized circuit breaker Follow circuit breaker safety guidelines and operating instruction provided in the specific circuit ...

Страница 14: ...Powered by Safety 9 Installation Operation Figure 3 Opening Racking Access Window IB 51807 ...

Страница 15: ...Powered by Safety 10 Installation Operation Figure 4 Installing Remote Racking Device Figure 5 Remote Racking Device Installed IB 51807 PV System 38 Remote Racking Device Mechanical Connection ...

Страница 16: ... Installation Operation Figure 6 Connecting the Motor to the Control Box Figure 7 Activate Remote Racking Device Figure 8 Circuit Breaker in Test Disconnect Position Figure 9 Circuit Breaker in Connected Position IB 51807 ...

Страница 17: ...ans of moving the circuit breaker from the TEST to CONNECT position a means of mechanically tripping the breaker with the door closed and the required safety interlocks The mechanism is located directly above the circuit breaker engaging the circuit breaker in the center and moving it between the TEST and CONNECT positions smoothly A visual indication of the circuit breaker position is given on th...

Страница 18: ...let Figure 6 Lock the plug by turning it clockwise i Ensure the control box power switch is in the OFF position j Connect the device to a 120VAC power source k Move the power switch to the ON position l Move the selector switch on the push button to the IN position Note The housing on the push button is a switch and can be rotated to either the IN or OUT positions m Physically move the motor contr...

Страница 19: ...rn the red knob on the back of the electric racking device until the socket engages the racking shaft Close and latch the upper compartment door and latch it to capture the hanger bracket 3 Insert the cylindrical plug into the remote racking device outlet Figure 6 Lock the plug by turning it clockwise 4 Ensure the control box power switch is in the OFF position 5 Connect the device to a 120VAC pow...

Страница 20: ...Service Division Houston PO Box 12818 Houston TX 77217 Tel 713 944 6900 Fax 713 948 4569 www powellind com info powellind com 2006 Powell Industries Inc All rights reserved Mechanical Connection IB 51807 PV System 38 Remote Racking Device April 2010 ...

Отзывы: