Operating Procedures
01.4IB.50026A
10. Transfer key KB to key lock K1 (Figure 15).
Rotate key KB. The ground and test device
control circuit is now enabled. The KB key is
now captive and the KCF key is released.
Figure 15 Transfer Key KB to Key Lock K1
11. Verify that the Control Selector Switch on
the front of the ground and test device is in
the “Off” (center) position (Figure 16).
Figure 16 Selector Switch in Off Position
12. Connect the umbilical cord of the remote
control box to the ground and test device
(Figure 17). Ensure the cord is locked into
the connected position by turning the plug
clockwise.
Figure 17 Connecting Control Box to Device
13. Move to control selector switch from “OFF”
position to “Close” position (Figure 18).
Figure 18 Selector Switch in Closed Position
14. From a safe distance, connect the ground
and test device remote control box to a
120VAC, 15 ampere power supply.
15. Depress the “Close” push button switch
on the control box (Figure 19) to close the
ground and test device ground making
switch.