Appendix A
01.4IB.48040C
MODBUS and EIP Memory Map (cont.)
Range: 30038 to 30039
Category
Register
Name
Read/
Write
Register
Type
Description
Default
Range, Format
UOM
Register # Modbus
Offset #
EIP Offset
*2
Interpretations
G-HSM-9M G-HSM-9SM G-HSM-18K
EIP
Instances
HMI Settings
Degree CF
R
Input
Degree C or F Flag (1=C, 2=F)
1
1-2
N/A
30038
37
N/A
(1=C, 2=F)
N/A
N/A
x
N/A
Sound Mute
Beep and Alarm Mute Flag
(0=Sound, 1=Muted)
0
0-1
30039
38
(0=Sound, 1=Muted)
x
Range: 30040 to 30067
Category
Register
Name
Read/
Write
Register
Type
Description
Default
Range, Format
UOM
Register # Modbus
Offset #
EIP Offset
*2
Interpretations
G-HSM-9M G-HSM-9SM G-HSM-18K
EIP
Instances
Temperature
Alarm Registers
Alert Lvl
R
Input
Alert Level for Operator
0
0-2
N/A
30040
39
0
(0=OK, 1=Warning,
2=Alarm)
x
x
x
A
lar
m I
nstanc
e 104 (siz
e: 56 b
yt
es)
Alert Code 1
HSM Alert Code Slot 1
0
0x0000-0x0312
30041
40
1
Example Alarm
0x0310
First byte of the word:
(0x03) indicates type
of error
0x00...no error
0x01...temperature
warning
0x02...temperature
alarm...Priority
highest
0x03...sensor module
error...priority lowest
Second byte of
the word: (0x10)
indicates the channel
0x10...channel 16
Alert Code 2
HSM Alert Code Slot 2
0
30042
41
2
Alert Code 3
HSM Alert Code Slot 3
0
30043
42
3
Alert Code 4
HSM Alert Code Slot 4
0
30044
43
4
Alert Code 5
HSM Alert Code Slot 5
0
30045
44
5
Alert Code 6
HSM Alert Code Slot 6
0
30046
45
6
Alert Code 7
HSM Alert Code Slot 7
0
30047
46
7
Alert Code 8
HSM Alert Code Slot 8
0
30048
47
8
Alert Code 9
HSM Alert Code Slot 9
0
30049
48
9
Alert Code 10
HSM Alert Code Slot 10
0
30050
49
10
primaryWarningSetpointC
The Primary Warning
Temperature Threshold in C
90
-50 - 200
°C
30051
50
11
N/A
primaryAlarmSetpointC
The Primary Alarm
Temperature Threshold in C
105
-50 - 200
°C
30052
51
12
primaryWarningSetpointF
The Primary Warning
Temperature Threshold in F
194
-58 - 392
°F
30053
52
13
primaryAlarmSetpointF
The Primary Alarm
Temperature Threshold in F
221
-58 - 392
°F
30054
53
14
warningFlagHi
High Word of Warning Flags
(Ch 17 & Ch 18)
N/A
0x0000-0x0003
N/A
30055
54
15
Bitwise representation
the channel warning and
alarm status:
Example: register
30057=0x1492=0001 0100
1001 0010:
D1(Ch 2=1), D4(Ch 5=1),
D7(Ch 8=1), D10(Ch 11=1),
D12(Ch 13=1) temperature
alarm on
Ch 2,5,8,11,13
warningFlagLo
Low Word of Warning Flags
(Ch 1 to Ch 16)
N/A
0x0000-0xFFFF
30056
55
16
alarmFlagHi
High Word of Alarm Flags
(Ch 17 & Ch 18)
N/A
0x0000-0x0003
30057
56
17
alarmFlagLo
Low Word of Alarm Flags
(Ch 1 to Ch 16)
N/A
0x0000-0xFFFF
30058
57
18
relayEnableFlagHi
Indicates if the channel will
control relay on channel alarm
or not (Ch 17 AND Ch 18)
N/A
0x0000-0x0003
30059
58
19
N/A
relayEnableFlagLo
Indicates if the channel will
control relay on channel alarm
or not (Ch 1 TO Ch 16)
N/A
0x0000-0xFFFF
30060
59
20
secondarySetpointSelectFlagHi
Indicates if the channel uses
the primary or secondary
setpoint (Ch 17 AND Ch 18)
N/A
0x0000-0x0003
30061
60
21
secondarySetpointSelectFlagLo
Indicates if the channel uses
the primary or secondary
setpoint (Ch 1 TO Ch 16)
N/A
0x0000-0xFFFF
30062
61
22
secondaryWarningSetpointC
The Secondary Warning
Temperature Threshold in C
90
-50 - 200
°C
30063
62
23
secondaryAlarmSetpointC
The Secondary Alarm
Temperature Threshold in C
105
-50 - 200
°C
30064
63
24
secondaryWarningSetpointF
The Secondary Warning
Temperature Threshold in F
194
-58 - 392
°F
30065
64
25
secondaryAlarmSetpointF
The Secondary Alarm
Temperature Threshold in F
221
-58 - 392
°F
30066
65
26
relayStatus
The current status of the Relay
N/A
0-1
On/Off
30067
66
27
Содержание BriteSpot BSG3
Страница 1: ...Instruction Bulletin 01 4IB 48040C BriteSpot BSG3 Powered by Safety ...
Страница 4: ...Powered by Safety BriteSpot BSG3 01 4IB 48040C This page is intentionally left blank ...
Страница 10: ...Powered by Safety BriteSpot BSG3 01 4IB 48040C This page is intentionally left blank ...
Страница 37: ...Powered by Safety 27 Usage 01 4IB 48040C Figure 34 LCD Menu and Navigation ...