Tab.46 Temps / mode CH1 – Temps / mode CH2 – Temps / mode CH3 menu
Parameter number
Parameter
Description
Factory setting
Heating
circuit 1
Heating
circuit 2
Heating cir
cuit 3
700
1000
1300
Operating
mode
The control unit is installed on the boiler:
Off : heating is deactivated.
Timed : the heating is dependent on the timer pro
gram.
Reduced : heating is in permanent reduced mode.
On : heating is in permanent reduced mode.
The control unit is installed as a room temperature
control system:
Off : the boiler starts up when the room tempera
ture falls below the frost protection set point.
Timed : the heating is dependent on the timer pro
gram.
Reduced : the room temperature set point is the
reduced set point (Parameters 712, 1010, 1310)
On : the room temperature set point is the comfort
set point (Parameters 710, 1010, 1310)
On
710
1010
1310
Comfort
setpoint
20 °C
712
1012
1310
Reduced
temp setpoint
16 °C
10.1.4 List of installer parameters
Tab.47 Structure of the installer menu
Menu
Sub-menu
Installer
Operator section
Temps / mode CH1
Temps / mode CH2
Temps / mode CH3
Temps / mode hot water
Boiler Settings
Solar
Configuration
Error
Service/special operation
State
Diagnostics heat generation
Burner control
Tab.48 Operator section menu
Parameter
number
Parameter
Description
Factory set
ting
24
Lighting
Off
Temporarily
Permanently
Temporarily
29
Units
°C, bar
°F, PSI
°C, bar
10 Settings
86
7702639 - v03 - 10072018