Caution
Risk of damage to the device!
The condensate hose must be laid with even gradient to the fun
nel. Avoid horizontal pipe routing.
Fill the condensate discharge in the Paramount four with water be
fore commissioning. For this, fill 0.25 l water in the flue outlet be
fore assembly of the flue gas pipe.
6.1.4 Sealing and filling of the system
1. Fill the heating system via the return flow of the Paramount four (see
note below)!
2. Check tightness (see note below for max. operating pressure).
For more information, see
Dimensions and connections, page 18
6.2 Gas connection
6.2.1 Gas connection
The gas-side connection may only be carried out by an approved installer.
For the gas-side installation and setting, the factory setting data of the
equipment and optional label should be compared with the local supply
conditions.
An approved thermally activated disconnector valve must be installed up
stream of the Paramount four.
If old gas pipes still exist in the region, the installation of a gas filter is rec
ommended.
Residues in pipes and pipe joints should be removed.
6.2.2 Venting the gas line
The gas line must be vented before initial commissioning.
For this, open the measuring nozzle for the connecting pressure and vent,
taking the safety precautions into account. Check for tightness of the con
nection after venting.
Danger
Danger to life by gas!
The entire gas inlet pipe, particularly the joints, must be checked
for leakages before commissioning.
6.3 Air supply/flue gas connections
6.3.1 Flue gas connection
For the operation of the Paramount four as a gas condensing boiler, the
flue gas pipe should be designed with the flue gas temperature under
120°C (flue gas pipe type B).
Note
The enclosed assembly instructions for the flue gas system have
to be observed.
6 Installation
36
Paramount four 30 – 115 kW
7658013 - 02 - 15092016