3.2.3
Technical data
Tab.4
Technical data
Model
Para‐
mount
30
Para‐
mount
40
Para‐
mount
50
Para‐
mount
60
Para‐
mount
80
Para‐
mount
95
Para‐
mount
115
Product ID no.
CE-0085BL0514
IP rating
IPx4D
Gas category
II
2H3+
Appliance category
B
23
, B
23P
, B
33
, C
13X
, C
33X
, C
43X
, C
53
, C
53X
, C
63X
, C
83
, C
93X
Software version
V 4.6
Nominal input range
Natural gas
E, LL
Heating
mode
kW
5,6 -
30,0
9,0 -
38,0
10,0 -
50,0
14,0 -
58,0
21,0 -
77,0
20,0 -
95,0
25,0 -
115,0
Effective rated output
range
Natural gas
E, LL
80/60°C
kW
5,4 -
29,2
8,7 -
37,0
9,7 -
48,7
13,6 -
56,4
20,3 -
74,9
19,4 -
92,5
24,3 -
111,7
50/30°C
kW
6,0 -
31,2
9,7 -
39,6
10,8 -
52,1
15,1 -
60,4
22,6 -
80,2
21,4 -
98,6
26,7 -
119,3
Standard operating efficiency
75/60°C
106
pH value condensate
–
4 - 5
4 - 5
4-5
4-5
4-5
4 - 5
4 - 5
Volume condensate
40/30°C
l/h 0,83 -
3,00
1,19 -
2,84
1,60 -
4,68
1,78 -
4,71
2,53 -
6,46
2,75 -
8,42
3,85 -
9,61
NO
X
concentration, weighted in accordance with
EN 15502
mg/k
Wh
23
23
23
21
23
25
30
NO
X
class in accordance with EN 15502
-
6
6
6
6
6
6
6
Data for design of the chimney to DIN EN 13384 (room air-depending operation)
Flue gas temperature
Part load/full
load
80/60°C
°C 53/66
56/75
58/69
59/71
59/73
59/73
60/77
Part load/full
load
50/30°C
°C 33/46
35/53
33/50
34/54
35/54
32/51
33/57
Flue gas mass flow
rate
Natural gas
E, LL
80/60°C
g/s
2,8 -
14,8
4,4 -
18,7
4,9 -
24,6
6,9 -
28,5
10,3 -
37,9
9,8 -
46,7
12,3 -
56,6
With natural gas
50/30°C
g/s
2,5 -
14,1
4,1 -
18,0
4,5 -
23,5
6,4 -
27,4
9,7 -
36,4
9,1 -
44,8
11,3 -
54,4
Flue gas mass flow
rate
Propane
80/60°C
g/s
2,6 -
14,1
4,2 -
17,8
5,6 -
23,5
6.6 -
27.2
9,8 -
36,1
14,1 -
44,6
16,4 -
53,9
for LPG
50/30°C
g/s
2,4 -
13,4
3,9-
17,1
5,2 -
22,4
6,1 -
26,1
9,2 -
34,6
13,3 -
42,6
15,4 -
51,7
CO2 content natural
gas
Natural gas
E, LL
%
Paramount 30 - Paramount 60: 8,3 - 8,8
Paramount 80 - 115: 8,5 - 9,0
CO2 content LPG
Propane
%
10,3 - 10,8
Draft requirement
mbar
0
Max. delivery pressure at flue gas
outlet
mbar
1,1
1,1
1,1
1,1
1,1
1,5
1,8
Flue gas/air supply
duct
mm
110 / 160
Flue gas value group to DVGW G636
–
G6
Heating water
Adjustment range heating water temperature
°C 20 - 85 20 - 85 20 - 85 20 - 85 20 - 85 20 - 85
20 - 85
Max. flow temperature
°C
85
Operating pressure
min.
bar
1,0
1,0
1,0
1,0
1,0
1,0
1,0
MPa
0,1
0,1
0,1
0,1
0,1
0,1
0,1
max.
bar
3.0
3,0
6,0
6,0
6,0
6,0
6,0
MPa
0,3
0,3
0,6
0,6
0,6
0,6
0,6
Gas-connected loads
Supply pressure for natural gas
mbar
G20: min. 17 - max. 25
3 Technical specifications
7703046 - 01 - 23072018
Paramount five 30 – 115
15
Содержание Paramount five 115
Страница 55: ...For more information see Technical data page 15 7 Commissioning 7703046 01 23072018 Paramount five 30 115 55 ...
Страница 138: ...For more information see Status page 132 State page 132 9 Settings 138 Paramount five 30 115 7703046 01 23072018 ...
Страница 150: ...Gas pressure not stable 11 Troubleshooting 150 Paramount five 30 115 7703046 01 23072018 ...