With the setting --°C, the value calculated via the heating curve is used as
the flow setpoint.
Swi-on ratio room stat (744, 1044, 1344)
The boiler tries to adapt the flow temperature so that the switch-on ratio
set under this parameter is achieved by the ambient thermostats
Delay heat request (746, 1046, 1346)
The boiler heat request is forwarded to the burner delayed by the time set
here. In this way a slowly opening mixer can already start up before the
burner goes into operation.
Important
If the option Absolute is selected under prog.no. 1630, the value 0
must be set under this prog.no. For special functions (e.g.
chimney-sweep function) the delay does not have an effect (see
prog.no. 2470).
For more information, see
Charging priority (1630), page 95
Delay heat req special op (2470), page 102
Room influence (750, 1050, 1350)
The flow temperature is calculated by means of the heating curve subject
to outside temperature. This type of control assumes that the heating
curve is set correctly, since room temperature is not taken into
consideration with this setting.
Important
However, if there is a room unit (e.g. RGP) is connected and the
setting "room influence" is set between 1 and 99%, the deviation
of the room temperature compared to the set point is recorded
and taken into consideration in the temperature control. In this
way any external heat can be taken into account enabling a
constant room temperature to be achieved. The influence of the
deviation can be set in percentage. The more representative the
lead room is (correct room temperature, correct installation
location etc.), the higher the value can be set, giving the room
temperature even greater relevance.
Caution
Should there be radiator valves in the lead room (where the room
sensor is installed), they must be opened fully.
Setting for weather compensation with room influence: 1% - 99%
Setting for pure weather compensation: ---%
Setting for pure room compensation: 100%
Room temp limitation (760, 1060, 1360)
TRx Room temperature actual value
TRw Room temperature setpoint
SDR Room switching difference
P Pump
t Time
1 On
0 Off
The heating circuit pump is switched on or off subject to room temperature
in line with the switching differential set here. The switch-off point of the
pump is set as the difference to the set room setpoint. The pump switch-
on point is 0.25 °C below the room setpoint. This function is only possible
with a room device (e.g. RGP) and active room influence.
Important
A room sensor must be connected. This function only applies to
pumped heating circuits.
Fig.22
Room temp limitation
RA-0000068
1
0
9 Settings
90
Paramount five 30 – 115
7703046 - 01 - 23072018
Содержание Paramount five 115
Страница 55: ...For more information see Technical data page 15 7 Commissioning 7703046 01 23072018 Paramount five 30 115 55 ...
Страница 138: ...For more information see Status page 132 State page 132 9 Settings 138 Paramount five 30 115 7703046 01 23072018 ...
Страница 150: ...Gas pressure not stable 11 Troubleshooting 150 Paramount five 30 115 7703046 01 23072018 ...