Automatic: In automatic mode, the room temperature is controlled in
accordance with the time program that is selected.
Reduced: In reduced operation mode the room temperature is kept
constantly to the set Reduced setpoint(e.g. prog. no. 712).
Comfort: In comfort mode the room temperature is kept constantly to the
set Comfort setpoint(e.g. prog. no. 710). Eco functions are not activated.
Comfort setpoint (710, 1010, 1310)
Setting of the comfort setpoint in the heating phases. Without room sensor
or with the room influence switched off (prog.no. 750, 1050, 1350), this
value is used for calculation of the flow temperature, to theoretically reach
the set room temperature.
Reduced setpoint (712, 1012, 1312)
Setting of the desired room temperature during the reduced heating
phase. Without room sensor or with the room influence switched off
(prog.no. 750, 1050, 1350), this value is used for calculation of the flow
temperature, to theoretically reach the set room temperature.
Frost protection setpoint (714, 1014, 1314)
Setting of the required room temperature during frost protection mode.
Without room sensor or with the Room influence(prog.no. 750, 1050,
1350), this value is used for calculation of the flow temperature, to
theoretically reach the set room The heating circuit remains turned off until
the flow temperature drops so far that the room temperature falls below
the frost protection temperature.
Heating curve slope (720, 1020, 1320)
Using the heating curve, the flow temperature setpoint is formed that is
used to regulate the heating circuit, subject to the outside temperature.
The gradient indicates how much the flow temperature changes by with
changing outside temperature.
Fig.20
Heating curve diagram
4
3,5
3
2,74
2,5
2,24
2
1,74
1,5
1,24
1
0,76
0,5
0,24
20
10
0
-10
-20
-30
°C
30
40
50
60
70
80
90
100
°C
AT
VT
RA-sRE036B
AT Outdoor temperature
VT Flow temperature
9 Settings
88
Paramount five 30 – 115
7703046 - 01 - 23072018