Buffer storage tank
Domestic water storage tank
28
Primary controller/intermediate circuit, without heat
exchanger
29
Primary controller/intermediate circuit, 1 heat ex
changer
Tab.26 Check no. heating circuit (prog.-no. 6217)
Heating circuit 3
Heating circuit 2
Heating circuit 1
0
No heating circuit
00 No heating circuit
00 No heating circuit
1
DHW circulation via boiler circuit
pump
01 DHW circulation via boiler circuit
pump
01 DHW circulation via boiler circuit
pump
2
Heating circuit pump
02 Heating circuit pump
02 Heating circuit pump
3
Heating circuit pump, mixer
03 Heating circuit pump, mixer
03 Heating circuit pump, mixer
Software version (6220)
Display of the actual software version.
Info 1 OEM(6230), Info 2 OEM (6231), Info 3 OEM (6258), Info
4 OEM (6259) and Parameter set number OEM (6236)
These parameters are EEPROM storage locations that may contain
information from the OEM.
9.2.18 LPB system
Device address (6600) andSegment address (6601)
The two-part LPB address of the controller consists of the 2-digit segment
number and the 2-digit device number.
Bus power supply function (6604)
Off: The controller does not provide the bus power supply.
Automatically: The bus power supply is switched on and off by the
controller in accordance with the power demand of the bus system.
Bus power supply state (6605)
Off: The bus system power supply by the controller is currently inactive.
On: The bus system power supply by the controller is currently active.
Display system messages (6610)
This setting allows system messages which are transmitted via LPB to be
suppressed on connected operating elements.
System message to alarm relay (6611)
No: Alarm output K10 Is not triggered when a system fault is reported.
Yes: Alarm output K10 Is triggered when a system fault is reported.
Alarm delay (6612)
The transmission of the alarm to the BM module can be delayed in the
basic device by an adjustable time. This allows the prevention of
unnecessary messages to a service location caused by malfunctions
which only occur briefly (e.g. temperature monitor queried, communication
errors). However, it must be noted that malfunctions which occur briefly
and quickly re-occur are also filtered out by this.
Action changeover functions (6620)
If the setting Central is activated under prog. no. 6221 and 6223
respectively, the action for this setting can be set. The following settings
are possible:
Segment: The changeover is done for all controllers in the same
segment.
System: The changeover is done for all controllers in the entire system
(that is in all segments). The controller must be located in segment 0!
9 Settings
7703046 - 01 - 23072018
Paramount five 30 – 115
123