PRINTED IN USA

 PAgE 1 OF 4

MFg. #5401205 - REV H

01/12

vsr-sG

vane type waterflow

alarM swItCH wItH retarD 

anD Glue-In unIon

for CpvC pIpe

Do not over-tighten the union nut, hand tighten only. Use of a wrench 

may damage the union nut.

Do not trim the paddle. Failure to follow these instructions may prevent the 

switch from operating and will void the warranty. 

General Information

The Model VSR-SG is a vane type waterflow switch for use on wet 

sprinkler systems using CPVC plastic fittings (manufactured by Tyco, 

Nibco, Victaulic, Ipex, and Spears Manufacturing Company) that use 1”, 

1 ¼”,  1 ½”, or 2” pipe sizes. It is equipped with a union to accommodate 

installation in confined spaces. 
The VSR-SG  contains  two  single  pole,  double  throw,  snap  action 

switches and an adjustable, instantly recycling pneumatic retard.  The 

switches  are  actuated  when  a  flow  of  10  GPM  (38  LPM)  or  more 

occurs downstream of the switch.  The flow condition must exist for a 

period of time necessary to overcome the selected retard period.

ul,  Cul  and  CsfM  listed, Ce Marked
service pressure: 

Up to 175 PSI (12,07 BAR)

flow sensitivity range for signal: 

4-10 GPM (15-38 LPM) - UL

Maximum surge:        

18 FPS (5.5 m/s)

Contact  ratings:

   Two sets of SPDT (Form C)

 

10.0 Amps at 125/250VAC

 

2.0 Amps at 30VDC  Resistive 

 

10 mAmps min. at 24VDC

Conduit entrances:

   Two openings provided for 1/2" conduit.  

 

Individual switch compartments suitable 

    

for dissimilar voltages.

Environmental Specifications:

     

 

•  NEMA 4/IP54 Rated Enclosure suitable for indoor or  

outdoor use with factory installed gasket and die-cast housing 

when used with appropriate conduit fitting.

 

•  Temperature Range:  40°F - 120°F, (4.5°C - 49°C) - UL

 

service use:

 

British Standard    

 

 

B59251   

      

Automatic Sprinkler 

 

 

NFPA-13  

One or two family dwelling   

 

NFPA-13D 

 

Residential occupancy up to four stories 

NFPA-13R 

National Fire Alarm Code 

 

 

NFPA-72 

  

Installation must be performed by qualified personnel and in    

    

   accordance with all national and local codes and ordinances. 

•  Shock hazard. Disconnect power source before servicing. Serious        

   injury or death could result.

•  Risk of explosion. Not for use in hazardous locations. Serious  

 

   injury or death could result.

Specifications subject to change without notice.

stock number:

 1144460

optional

:  Cover Tamper Switch Kit, stock no. 0090148

replaceable Components:

 Retard/Switch Assembly, stock no. 1029030

enclosure

 

The VSR-Sg  switches  and  retard  switch  are  enclosed  in  a  general 

purpose, die-cast  housing.  The cover is held in place with two tamper 

resistant  screws  which  require  a  special  key  for  removal.   A  field 

installable cover tamper switch is available as an option which may 

be used to indicate unauthorized removal of the cover.  See bulletin 

number 5401103 for installation instructions of this switch.

Waterflow switches that are monitoring wet pipe sprinkler systems shall 

not be used as the sole initiating switch to discharge AFFF, deluge, 

or chemical suppression systems.  Waterflow switches used for this 

application  may  result  in  unintended  discharges  caused  by  surges, 

trapped air, or short retard times.

Potter Electric Signal Company, LLC • St. Louis, MO • Cust Service: 866-572-3005 • Tech Support: 866-956-0988 /Canada 888-882-1833

 

 www.pottersignal.com

Installation  (

see Fig. 1, 3, and 5)

These switches may be mounted on horizontal or vertical pipe.  On 

horizontal pipe they shall be installed on the top side of the pipe where 

they will be accessible.  The switch should not be installed within 6" 

(15 cm) of a fitting which changes the direction of the waterflow or 

within 24" (60 cm) of a valve or drain. The unit has a 1" male fitting 

for gluing into a CPVC plastic tee. 

note

:

 Do not leave cover off for an extended period of time.

Loosen the union nut and separate the 1" male fitting from the VSR-SG. 

Glue the 1" male fitting into the TEE following the TEE manufacturer's 

instructions for preparation and gluing of CPVC piping systems. (Note: 

The 1" male fitting must bottom out on the stop of the TEE for proper 

operation of the VSR-SG. See Fig. 1.) Wait 2 to 4 hours to allow the 

glue to dry before attaching the VSR-SG to the 1" male fitting. Select 

the proper paddle for the pipe size and type of 

TEE

 used. See Fig. 3 

for instructions on how to change paddle. 

verify that the o-ring is 

properly positioned in its groove

. Hand tighten the nut on the union 

after orienting the switch in the appropriate direction to detect waterflow 

as shown in Fig. 5 & Fig. 7.

The vane must not rub the inside of the TEE or bind in any way. The 

stem should move freely when operated by hand.

Содержание VSR-SG

Страница 1: ...fications subject to change without notice Stock Number 1144460 Optional Cover Tamper Switch Kit stock no 0090148 Replaceable Components Retard Switch Assembly stock no 1029030 Enclosure The VSR SG switches and retard switch are enclosed in a general purpose die cast housing The cover is held in place with two tamper resistant screws which require a special key for removal A field installable cove...

Страница 2: ...duce a minimum flow of 10 GPM to activate the switch The discharge orifice shall be equal to the smallest sprinkler used in the system Fig 2 Important 11 paddles are furnished with each unit to accommodate the various sizes and manufacturers of TEES The paddles have raised lettering that show the pipe size and the TEE manufacturer they are to be used with The proper paddle must be used The paddle ...

Страница 3: ...lowing water activates switch in one direction only DWG 1205 15 DWG 1190 1 5 56 in 141 2 mm PIPE PLASTIC PADDLE 2 00 in 50 8 mm 3 91 in 99 33 mm 3 50 in 89 0 mm An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connections The wire must be severed thereby providing supervision of the connection in the event that the wire become dislodge...

Страница 4: ... wires from the waterflow switch 3 Remove the 2 mounting screws holding retard switch assembly to the base 4 Do not remove the 2 retard housing screws Remove the retard assembly by lifting it straight up over the tripstem 5 Install the new retard assembly Make sure the locating pins on the retard switch assembly fit into the locating pin bosses on the base 6 Re install the 2 original mounting scre...

Отзывы: