 PAGE 1 OF 4

VSR

VANE TYPE WATERFLOW

ALARM SWITCH WITH RETARD

MFG. #5401146 - REV M

11/15

UL,  CUL  and  CSFM  Listed,  FM   Approved, LPCB Approved, For 

CE Marked (EN12259-5) / VdS Approved  model use VSR-EU   

Service Pressure:         

450 PSI (31 BAR) - UL 

 

          

Flow Sensitivity Range for Signal:                                  

 

  

     4-10 GPM (15-38 LPM) - UL 

               

Maximum Surge:        

18 FPS (5.5 m/s)

Contact  Ratings:

   Two sets of SPDT (Form C)

 

10.0 Amps at 125/250VAC

 

2.0 Amps at 30VDC  Resistive 

 

10 mAmps min. at 24VDC

Conduit Entrances:

   Two knockouts provided for 1/2" conduit.  

 

Individual switch compartments suitable 

    

for dissimilar voltages.

Environmental Specifications:

    

 

•  NEMA 4/IP54 Rated Enclosure suitable for indoor or  

outdoor use with factory installed gasket and die-cast housing 

when used with appropriate conduit fitting.

 

•  Temperature Range:  40°F - 120°F, (4.5°C - 49°C) - UL

 

•  Non-corrosive sleeve factory installed  in saddle.

Service Use:

     

 

 

 

 

 

      

Automatic Sprinkler 

 

 

NFPA-13  

One or two family dwelling   

 

NFPA-13D 

 

Residential occupancy up to four stories 

NFPA-13R 

National Fire Alarm Code 

 

 

NFPA-72 

  

Installation must be performed by qualified personnel and in    

    

   accordance with all national and local codes and ordinances. 

•  Shock hazard. Disconnect power source before servicing. Serious        

   injury or death could result.

•  Risk of explosion. Not for use in hazardous locations. Serious  

 

   injury or death could result.

Ordering Information

Nominal Pipe Size

Model

Part Number

2"

DN50

VSR-2

1144402

2 1/2"

DN65

VSR-2 1/2

1144425

3"

DN80

VSR-3

1144403

3 1/2"

-

VSR-3 1/2

1144435

4"

DN100

VSR-4

1144404

5"

-

VSR-5

1144405

6"

DN150

VSR-6

1144406

8"

DN200

VSR-8

1144408

Specifications subject to change without notice.

Optional

:  Cover Tamper Switch Kit, stock no. 0090148

Replaceable Components:

 Retard/Switch Assembly, stock no. 1029030

Waterflow switches that are monitoring wet pipe sprinkler systems shall 

not be used as the sole initiating device to discharge AFFF, deluge, 

or chemical suppression systems.  Waterflow switches used for this 

application  may  result  in  unintended  discharges  caused  by  surges, 

trapped air, or short retard times.

Potter  Electric  Signal  Company,  LLC  •  St.  Louis,  MO  •  Phone:  866-956-1211/Canada  888-882-1833

 

 www.pottersignal.com

General Information

The Model VSR is a vane type waterflow switch for use on wet sprinkler 

systems. It is UL Listed for use on a steel pipe; schedules 5 through 40, 

sizes 2" - 6" and is UL Listed and FM Approved for use on steel pipe; 

schedules 10 through 40, sizes 2" thru 8" (50 mm thru 200 mm). LPC 

approved sizes are 2" thru 8" (50 mm thru 200 mm).  See Ordering 

Information chart.

The VSR may also be used as a sectional waterflow detector on large 

systems. The VSR contains two single pole, double throw, snap action 

switches and an adjustable, instantly recycling pneumatic retard.  The 

switches are actuated when a flow of 10 GPM (38 LPM) or more occurs 

downstream of the device.  The flow condition must exist for a period 

of time necessary to overcome the selected retard period.

Enclosure

 

The VSR switches and retard device are enclosed in a general purpose, 

die-cast  housing.  The cover is held in place with two tamper resistant 

screws which require a special key for removal.  A field installable 

cover tamper switch is available as an option which may be used 

to indicate unauthorized removal of the cover.  See bulletin number 

5401103 for installation instructions of this switch.

Important: 

This  document  contains  important  information  on  the  installation  and  operation  of  the VSR  waterflow  switches.  Please  read  all 

instructions carefully before beginning installation.  A copy of this document is required by NFPA 72 to be maintained on site.

Содержание VSR-2

Страница 1: ...d Switch Assembly stock no 1029030 Waterflowswitchesthataremonitoringwetpipesprinklersystemsshall not be used as the sole initiating device to discharge AFFF deluge or chemical suppression systems Waterflow switches used for this application may result in unintended discharges caused by surges trapped air or short retard times Potter Electric Signal Company LLC St Louis MO Phone 866 956 1211 Canad...

Страница 2: ...nt false alarms Flowing water activates device in one direction only DO NOT LEAVE COVER OFF FOR AN EXTENDED PERIOD OF TIME TIGHTEN NUTS ALTERNATELY MOUNT ON PIPE SO ARROW ON SADDLE POINTS IN DIRECTION OF WATERFLOW ROLL PADDLE IN OPPOSITE DIRECTION OF WATERFLOW DIRECTION OF WATERFLOW Hole must be drilled perpendicular to the pipe and vertically centered Refer to the Compatible Pipe Installation Req...

Страница 3: ...nsions DWG 1146 14 3 50 in 89 0 mm 2 34 in 59 4 mm PIPE DIA 5 25 in 133 4 mm 5 56 in 141 2 mm 2 00 in 50 8 mm U BOLT NUT U BOLT WASHER PIPE SADDLE PIPE PLASTIC PADDLE U BOLT NOMINAL PIPE DIA 1 75 in 44 5 MM FOR DN 50 DN 65 2 2 5 in NOMINAL PIPE DIA 2 125 in 54 0 MM FOR DN 80 DN 200 3 8 in DWG 1146 15 GREEN GROUND SCREWS Fig 7 An uninsulated section of a single conductor should not be looped around...

Страница 4: ...e waterflow switch 4 Remove the 2 mounting screws holding retard switch assembly to the base Do not remove the 2 retard housing screws 5 Remove the retard assembly by lifting it straight up over the tripstem 6 Install the new retard assembly Make sure the locating pins on the retard switch assembly fit into the locating pin bosses on the base 7 Re install the 2 original mounting screws 8 Reconnect...

Страница 5: ...Mouser Electronics Authorized Distributor Click to View Pricing Inventory Delivery Lifecycle Information AMSECO VSR 4 ...

Отзывы: