PS120 SERIES

SUPERVISORY PRESSURE SWITCH

Installation 

The  Potter  PS120  Series  Supervisory  Pressure  Actuated  Switches  are 

designed primarily to detect an increase and/or decrease from normal system 

pressure in automatic fire sprinkler systems.  Typical applications are: Wet 

pipe systems with excess pressure, pressure tanks, air supplies, and water 

supplies. The PS120 switch is factory set for 120 PSI (8,3 BAR) normal 

system pressure.  The switch marked with the word LOW is set to operate at 

a pressure decrease of 10 PSI (0,7 BAR) at 110 PSI (7,6 BAR). The switch 

marked with the word HIGH is set to operate at a pressure increase of 10 

PSI (0,7 BAR) at 130 PSI (9 BAR). See section heading 

Adjustments and 

Testing

 if other than factory set point is required.

1.  Connect the PS120 to the system side of any shutoff or check valve. 

 

2.  Apply Teflon tape to the threaded male connection on the device.          

    (Do not use pipe dope) 

 

 

 

 

 

3.  Device should be mounted in the upright position.   

    

       

    (Threaded connection down)   

 

 

 

 

4.  Tighten the device using a wrench on the flats on the device.

Wiring Instructions 

1.  Remove the tamper resistant screw with the special key provided. 

2.  Carefully place a screwdriver on the edge of the knockout and sharply                   

     apply a force sufficient to dislodge the knockout plug.  See Fig. 9 

3.  Run wires through an approved conduit connector and affix the 

     connector to the device.  A NEMA-4 rated conduit fitting is required 

     for outdoor use.

Potter Electric Signal Company

 • St. Louis, MO • Customer Service: 866-572-3005 • Tech Support: 866-956-0988 •

 Canada 888-882-1833

 

 www.pottersignal.com

Service Use:

 

Automatic Sprinkler 

NFPA-13

 

One or two family dwelling 

NFPA-13D

 

Residential Occupancy up to four stories 

NFPA-13R

 

National Fire Alarm Code 

NFPA-72

UL,  cUL,  and  CSFM  Listed,  FM  and  LPC  Approved,  NYMEA 

Accepted, CE Marked
Dimensions: 

3.78" (9.6cm)W x 3.20" (8.1cm)D x 4.22" (10.7cm)H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

                            

 

 

 

 

 

 

 

 

 

 

Enclosure:    

Cover- Die-cast with textured red powdercoat finish, single                    

                       cover screw and rain lip.     

 

 

 

 

      Base- Die-cast                                                   

Pressure Connection: 

Nylon 1/2" NPT male

Cover  incorporates  tamper  resistant  fastener  that  requires  a 

special key for removal.  One key is supplied with each device.  

For optional cover tamper switch kit, order Stock No. 0090200.  

See bulletin #5401200 PSCTSK.

Switch Contacts: 

 SPDT (Form C)  

                               10.1 Amps at 125/250VAC, 2.0 Amps at 30VDC

                               One SPDT in PS120-1, Two SPDT in PS120-2

Environmental Specifications:  

 

 

 

 

 

 

NEMA 4/IP66 Rated Enclosure - indoor or outdoor when used   

 

with NEMA 4 conduit fittings.

 

Temperature range: -40°F to 140°F (-40°C to 60°C)   

Pressure Range:  

25-175 PSI (1,7 - 12,1 BAR)

Differential:  

Typical 2 lbs. at 25 PSI (0,14 at 1,7 BAR)             

         

       8 lbs at 175 PSI (55 at 12,1 BAR) 

Maximum System Pressure:  

300 PSI (20,68 BAR)

Factory Adjustment: 

PS120-1 operates on decrease at 110 PSI (7,6 BAR)

PS120-2 operates in increase at 130 PSI (9 BAR) and 

on decrease at 110 PSI (7,6 BAR)

Conduit Entrance:

Two knockouts provided for 1/2" conduit. Individual 

switch compartments and ground screw suitable for 

dissimilar voltages

Tamper:

4.  Connect the wires to the appropriate terminal connections for the 

     service intended. See Figures 2,4,5,6, and 8.  See Fig. 7 for two switch 

     one conduit wiring.

Adjustment And Testing 

The operation of the pressure supervisory switch should be tested upon 

completion of installation and periodically thereafter in accordance with 

the applicable NFPA codes and standards and/or the authority having 

jurisdiction (manufacturer recommends quarterly or more frequently). 

Note

: Testing the PS120 may activate other system connected devices.   

The use of a Potter BVL (see product bulletin 8900067 for details) is 

recommended to facilitate setting and testing of the PS120 pressure switch. 

When a BVL (bleeder valve) is used, the pressure to the switch can be 

isolated and bled from the exhaust port on the BVL without effecting the 

supervisory pressure of the entire system.  See Fig. 3 

The operation point of the PS120 Pressure Switch can be adjusted to any 

point between 25 and 175 PSI (1,7 - 12,1 BAR) by turning the adjustment 

knob(s) clockwise to raise the actuation point and counter clockwise to 

lower the actuation point.  In the case of the PS120-2, both switches operate 

independent of each other.  Each switch may be independently adjusted to 

actuate at any point acrosss the switch adjustment range.  Initial adjustment 

can be made with a visual reference from the top of the adjustment knob 

across to the printed scale on the switch bracket.  Final adjustments should 

be verified with a pressure gauge. 

 

Ordering Information 

 

 

 

Model 

 

Description 

 

 

Stock No.

PS120-1 

Pressure switch with one set                           1341203 

 

SPDT contacts 

PS120-2 

Pressure switch with two sets                         1341204

 

SPDT contacts 

 

 

Hex Key                                                          5250062

 

Cover Tamper Switch Kit                               0090200

BVL 

Bleeder valve                                                  1000018