background image

Terminal Layout:

Mounting Instructions:

1.  Loosen screws, but not all the way out, from junction box.

2.  Align keyholes on the base with screw heads. 

3.  Slide screw to the slot on the mounting plate.

4.  Tighten screw to secure base.

5.  Snap trim ring on the base (PAD300-6DB).

PAD300-4DB

    PAD300-6DB

Contents

A.

 Introduction

D.

 Wiring

B.

 Specifications

E.

 Locking Feature

C.

 Mounting

F.

 Warranty

PAD300-4DB

Installation Temp Range

32ºF to 150ºF

Operating Humidity Range

0% - 93% (Non-condensing)

Dimension

Φ3.93 in

Weight 

1.34 oz

Height

0.76 in

Acceptable Wire Gauge

22 to 12 AWG

Mounting Options

3-1/2” octagon, 4” square with 

plaster ring, 50mm c/c, 60mm 

c/c and 70mm c/c boxes

The PAD300-4DB and the PAD300-6DB are mounting bases 

designed to work specially with the PAD300 series detectors. 

Compatible detectors include PAD300-PD, PAD300-

HD,PAD300-PHD and PAD300-DD.
The PAD300-4DB has a four (4) inches diameter and the 

PAD300-6DB has a six (6) inches diameter. Both products 

provide multiple mounting options to accommodate different 

UL listed junction boxes.
The PAD300-4DB and the PAD300-6DB have a locking feature 

to allow tamper-proofing to prevent unwanted removal. 
Refer to the company website for the latest revision of this 

manual.

B.  Specifications

A.  Introduction

C. Mounting

PAD300-6DB

Installation Temp Range

32oF to 150oF

Operating Humidity Range

 0% - 93% (Non-condensing)

Dimension

Φ 6.3 in

Weight 

3.03 oz

Height

0.76 in

Acceptable Wire Gauge

22 to 12 AWG

Mounting Options

3-1/2” octagon, 3-1/2” square, 

double gang, 4" octagon, 4” 

square, 50mm c/c, 60mm c/c 

and 70mm c/c boxes

PAD300-4DB

S1: SLC+

S2: SLC-

Record loop address on 

label.

PAD300-6DB

1609 Park 370 Pl, Hazelwood, MO 63042

www.pottersignal.com

S2

S1