This document provides instructions for mounting and wiring the Detector Bases 

PAD100-IB, PAD100-RB and PAD100-SB.  The following detectors are compatible 

with Detector Bases PAD100-IB, PAD100-RB and PAD100-SB.

  PAD200-PD & PAD100-PD: 

Photoelectric Smoke Detector

  PAD200-PHD & PAD100-PHD:   Photoelectric Smoke / Heat Detector

  PAD200-PCD:   

Photoelectric Smoke / CO Detector 

  PAD200-PCHD:    

Photoelectric Smoke / CO Detector/ Heat Detector

  PAD100-HD: 

 

Heat Detector

  PAD100-CD: 

 

Carbon Monoxide Detector

2a. Field Wiring Diagram(s) for PAD100-IB

Typical field wiring diagrams for the Signaling Line Circuit (SLC) (FIGURE 1).            

The SLC supports NFPA wiring Class B, A and X.

Typical NFPA Class B SLC (S+, S-) Wiring using the PAD100-IB base (FIGURE 1).  In 

Class A (FIGURE 2) arrangement two separate conducts would return from the last 

detector base to a listed compatible Fire Alarm Control Panel (FACP).  In 

Class X, it is required to use PAD100-IB (Addressable Isolator Bases (FIGURE 3). 

2b. Field Wiring Diagram(s) for PAD100-RB

Typical field wiring diagrams for the Signaling Line Circuit (SLC) (FIGURE 4).  The SLC 

supports NFPA wiring Class B, A and X.

Typical NFPA Class B SLC (S+, S-) Wiring using the PAD100-RB base (FIGURE 4).  

In Class A arrangement two separate conductors return from the last detector base 

to a listed compatible Fire Alarm Control Panel (FACP).  In Class X, it is required to 

use PAD100-IB (Addressable Isolator Bases).  The typical field diagram is in Field  

Wiring Diagram(s) for PAD100-IB section of this manual.  

2c. Field Wiring Diagram(s) for PAD100-SB

Typical field wiring diagrams for the Signaling Line Circuit (SLC) (FIGURE 5).  The SLC 

supports NFPA wiring Class B, A and X.

Typical NFPA Class B SLC (S+, S-) Wiring using the PAD100-SB base (FIGURE 5). 

 In Class A arrangement two separate conductors would return from the last 

detector base to a listed compatible Fire Alarm Control Panel (FACP).  In Class X, it is 

required to use PAD100-IB (Addressable Isolator Bases).  The typical field diagram is 

in Field Wiring Diagram(s) for PAD100-IB section of this manual.  

3. Wiring Instruction

  To ensure proper installation of the detector head to the base, wires shall be 

 

dressed properly at the time of installation

  When using PAD100 Bases, observe the correct polarity of SLC wiring.

NOTICE:

 

 

THE WIRING TO BE USED SHALL BE IN ACCORDANCE WITH THE 

 

PROVISIONS OF ARTICLE 300.3(B) OF THE NATIONAL ELECTRICAL CODE, 

 

NFPA 70, AS WELL AS ARTICLE 210.

  THIS EQUIPMENT SHOULD BE INSTALLED IN ACCORDANCE WITH THE 

 

NATIONAL FIRE PROTECTION ASSOCIATION STANDARD 72.

CAUTION!

 Break wire runs to provide supervision for connections made to each 

wire pair.

Detector Base Mounting

PAD100-IB, PAD100-RB and PAD100-SB should be mounted directly on the 

electrical box.  The PAD100-IB, PAD100-RB and PAD100-SB mounting holes are 

configured for a single gang, 4” octagon or 4” square box.  Use a box for each base 

and run the power circuit to all base locations.

Detector Bases: 

PAD100-IB, PAD100-RB and PAD100-SB
Detectors:

PAD100-PD, PAD100-PHD, PAD200-PD, PAD200-PHD, 

PAD200-PCD, PAD200-PCHD, PAD100-HD and PAD100-CD

To FACP

Loop (SLC)

First Base

- SLC2 +

Last Base

- SLC 

+

- SLC2 +

- SLC 

+

- SLC2 +

- SLC 

+

FACP

IB

ISOLATOR BASE

ADDRESSABLE BASE / MODULE

SHORT CIRCUIT

THE AREA TO BE ISOLATED BY 

DETECTING THE SHORT CIRCUIT

IB

IB

SLC

OUT

FIGURE 2: Wiring (Class A) Using PAD100-IB

FACP

IB

ISOLATOR BASE

SHORT CIRCUIT

THE AREA TO BE ISOLATED BY 

DETECTING THE SHORT CIRCUIT

THE IB NEXT TO A FACP SHALL BE INSTALLED

WITHIN 20 FEET FROM THE TERMINAL OF THE FACP

SLC

OUT

IB

IB

IB

SLC

IN

FIGURE 3: Wiring (Class X) Using PAD100-IB

FACP

IB

ISOLATOR BASE

THE IB NEXT TO A FACP SHALL BE INSTALLED

WITHIN 20 FEET FROM THE TERMINAL OF THE FACP

SHORT CIRCUIT

THE AREA TO BE ISOLATED BY 

DETECTING THE SHORT CIRCUIT

IB

IB

IB

SLC

OUT

SLC

IN

 SLC -

To FACP

Loop (SLC)

First Base

NC

S +

S -

S +

S -

SLC +

 SLC -

SLC +

Last Base

C NO

NC C NO

Accessory

Alarm 

Contacts

Normally

Open

Closed

Normally

Closed

FIGURE 4: Wiring (Class B) Using PAD100-RB

 SLC -

To FACP

Loop (SLC)

First Base

- PWR +

S +

S -

S +

S -

24+

24-

SLC +

 SLC -

- PWR +

SLC +

Last Base

FIGURE 5: Wiring (Class B) Using PAD100-SB

Manual Number: 550-0671

550-0671-000

550-0671-000

FIGURE 1: Wiring (Class B) Using PAD100-IB

Содержание PAD100-IB

Страница 1: ...agram is in Field Wiring Diagram s for PAD100 IB section of this manual 3 Wiring Instruction To ensure proper installation of the detector head to the base wires shall be dressed properly at the time of installation When using PAD100 Bases observe the correct polarity of SLC wiring NOTICE THE WIRING TO BE USED SHALL BE IN ACCORDANCE WITH THE PROVISIONS OF ARTICLE 300 3 B OF THE NATIONAL ELECTRICAL...

Страница 2: ...IC TESTING BY THE FACP BE SURE TO RE ENGAGE THESE SYSTEMS WHEN ALL TESTING IS COMPLETE Walk Test The FACP must be placed into Walk Test Mode and follow the steps below Use the appropriate steps outlined below for the detector that is to be tested CAUTION FAILURE TO ALARM DURING A TEST INDICATES A DEFECTIVE DETECTOR REPLACE DETECTOR IMMEDIATELY a PAD100 PD PAD200 PD PAD200 PCD PAD200 PCHD PAD100 PH...

Страница 3: ...t on the detector FIGURE 10 and push the plastic tab while simultaneously turning the detector head counter clockwise 2 The locking feature can be disabled To disable the locking feature break off the locking tab before installation FIGURE 11 8 Detector Base Options FIGURE 10 Locking Feature Insert small screwdriver into slot to remove detector from base FIGURE 11 Disable Locking Feature Break off...

Страница 4: ...n Section 4 No Item PAD100 HD PAD100 CD 1 Working Voltage Range 24 VDC 2 Standby Current 300 µA 3 Alarm Indicator 1 LED 4 Alarm Indictor Current 1 4 mA 5 Alarm Set Point Range 135O to 174O F 57O to 79O C 175O to 185O F 80O to 85O C 135O to 160O F 57O to 71O C Fixed 70 150 400 PPM 6 Installation Temperature Range 32O to 100O F 0O to 38O C 32O to 150O F 0O to 66O C 32O to 100O F 0O to 38O C 32O to 1...

Страница 5: ...100 HD PAD200 PCD PAD200 PCHD and PAD100 CD detectors and modules Setting the Address All PAD protocol detectors and modules require an address prior to connection to the panel s SLC loop Each PAD device s address i e detector and or module is set by changing the dip switches located on the device PAD device addresses are comprised of a seven 7 position dip switch used to program each device with ...

Страница 6: ... ELECTRIC SIGNAL COMPANY LLC DISCLAIMS ALL STATUTORY AND IMPLIED WARRANTIES INCLUDING WITHOUT LIMITATION WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE AND WARRANTIES AGAINST HIDDEN OR LATENT DEFECTS TO THE EXTENT PERMITTED BY LAW TO THE EXTENT SUCH WARRANTIES CANNOT BE DISCLAIMED AND TO THE EXTENT PERMITTED BY APPLICABLE LAW SUCH IMPLIED WARRANTIES SHALL APPLY ONLY FOR THE WAR...

Отзывы: