background image

NOTICE:

w

DO NOT USE LOOPED WIRE UNDER TERMINALS.  BREAK WIRE RUN TO 

PROVIDE SUPERVISION OF CONNECTION.

w

VOLTAGE SUPPLIED TO SIGNAL WHEN THE PANEL IS LATCHED.

w

NFPA 72 REQUIRES THAT AN AUDIBLE SIGNAL APPLIANCE THAT EMITS A 

CONTINUOUS SIGNAL WHILE ENERGIZED HAVE A TEMPORAL PATTERN 

IMPOSED ON IT IF THE ALARM SIGNAL IS INTENDED TO EVACUATE THE 

BUILDING.

w

TO SYNCHRONIZE THE MHT-1224, USE THE AVSM CONTROL MODULE.

4. Install the MHT-1224 unit to the mounted rough-in box.

5. Secure the unit to the box using the two mounting screws (supplied).

CAUTION:

When installing, route field wiring away from sharp projections, corners, and

internal components.

6. The MHT-1224 is a temporal 3 or continuous tone unit.  The device is factory set 

in temporal 3 mode.  To enable continuous tone, break jumper on back of unit as 

shown in DIAGRAM 2.  

NOTICE:

ONCE JUMPER HAS BEEN BROKEN, THE OPTION TO REVERT FROM 

CONTINUOUS TO TEMPORAL 3 TONE IS NOT POSSIBLE.  DO NOT BREAK JUMPER

IF TEMPORAL 3 TONE IS NEEDED.

This appliance will not operate without electrical power.  As fires 

frequently cause power interruptions, we suggest you discuss further 

safeguards with your local fire protection specialist.

VI. ELECTRICAL SPECIFICATIONS

IV. CHECKOUT AND TROUBLESHOOTING

1. Supply power to the system control panel.  The auxiliary alarms in the system should 

not alarm.

2. If alarm is heard:

a. Check all smoke and fire detection units in the system to make sure that they have 

not been activated.

b. Check all wiring connections to make sure detection circuits are not reversed or 

shorted together.  

3. To test the auxiliary alarms circuit, trip the alarm circuit at the main control panel or 

activate one of the fire detection units in the system.  All auxiliary alarms should be 

activated.

4. Always perform an operational test on this product on a regular basis after installation.  

Potter Electric suggests that this regularly scheduled testing be performed at least twice 

a year, or more often as may be dictated by the local authorities having jurisdiction.

NOTICE

: THESE TESTING AND TROUBLESHOOTING INSTRUCTIONS ARE 

GENERALIZED.  PLEASE REFER TO THE SYSTEM CONTROL PANEL OPERATING

INSTRUCTIONS FOR PROPER OPERATION OF THE PANEL AND FIRE DETECTION

SYSTEM.

NOTICE: 

w

DC VOLTAGE RANGE LIMITS: 8-17.5V AND 16-33V.  FWR VOLTAGE RANGE LIMITS:  

8-17.5V AND 16-33V.  THIS PRODUCT WAS ONLY TESTED TO THE STATED 

VOLTAGE RANGE(S); DO NOT APPLY 80% AND 110% OF THIS RANGE FOR 

SYSTEM OPERATION.

w

THE THREE PULSE TEMPORAL PATTERN IS TO BE USED FOR EVACUATION USE 

ONLY.

w

THE SOUND OUTPUT FOR THE TEMPORAL 3 TONE IS RATED LOWER SINCE THE 

TIME THE HORN IS OFF IS AVERAGED INTO THE SOUND OUTPUT RATING.  

WHILE THE HORN IS PRODUCING A TONE IN THE TEMPORAL 3 MODE ITS 

SOUND PRESSURE IS THE SAME AS THE  CONTINUOUS MODE.  UNITS HAVE 

BEEN TESTED TO 0°C, 49°C AND 93% HUMIDITY. 

I. INTRODUCTION

The Potter Electric MHT-1224 is a high-quality, remote, audible signaling appliance rated a

minimum of 75-85dBA at 10 feet.  This appliance is ideal for applications where a 

dependable alarm signal is required in hotels, dormitories, apartments, and other 

installations.  

II. LOCATION

The appliance is intended for use in fire protective signaling systems and is to be installed

in accordance with the applicable requirements of NFPA 72 and the local authorities having

jurisdiction.  The MHT-1224 is intended for indoor installation only.  This appliance is 

not

listed for outdoor applications.

III. INSTALLATION AND WIRING

Unit Dimensions: 

2.84” Wide X 4.48” High X 0.5” Deep

MOUNTING BOXES

Handy Box:

4" x 2-1/8" (approx.)

Switch Box:

3" x 2" (approx.) with conduit knockouts

Masonry Box:        

3-3/4" x 2"(approx.) with ½" and ¾"  concentric knockouts 

Non-Metallic Switch Box: 3-3/4" x 2-5/16" (approx.)

NOTICE

: A MOUNTING BOX MUST BE INSTALLED FOR EACH REMOTE 

SIGNALING APPLIANCE.

WIRE CONNECTIONS

1. The MHT-1224 has two terminals for power-in and power-out supply circuits.

2. Make the wire connections as follows: Positive to the (+) terminal and negative to 

the (-) terminal.

3. Run a minimum 18-gauge insulated conductor from the signaling appliance in the 

system.  Use ANSI/UL Listed Class 1 wire.

Use screwdriver to 

break jumper for 

continuous tone.  

DO NOT BREAK

JUMPER IF 

TEMPORAL 3 

TONE IS NEEDED.

DIAGRAM 1

DIAGRAM 2

MHT-1224 SERIES

ANSI/UL & CAN/ULC COMPLIANT

ADDITIONAL CAN/ULC LISTED PRODUCT INFORMATION IS FOUND ON PAGE 2

12/24VDC REMOTE AUDIBLE 

SIGNALING APPLIANCE

MHT-1224 HORN DECIBEL RATINGS: REVERBERANT ROOM 

Horn Mode

Minimum SPL @ 

10Ft. Per 

ANSI/UL464 @ 24VDC

Minimum SPL @ 

10Ft. Per 

ANSI/UL464 @ 12VDC

Temporal 3 Tone

81 dBA

78 dBA

Continuous Tone

86 dBA

83 dBA

HORN RATINGS OVER INPUT 

VOLTAGE RANGE OF 16-33V

HORN RATINGS OVER INPUT 

VOLTAGE RANGE OF 8-17.5V

Regulated 

24VDC Max.

Operating (mA)

Regulated 

24VFWR Max.

Operating (mA)

Regulated 

12VDC Max.

Operating (mA)

Regulated 

12VFWR Max.

Operating (mA)

Temporal 3

18

20

13

17

Continuous

21.1

20.7

7

10

firealarmresources.com

Содержание MHT-1224 Series

Страница 1: ...CT WAS ONLY TESTED TO THE STATED VOLTAGE RANGE S DO NOT APPLY 80 AND 110 OF THIS RANGE FOR SYSTEM OPERATION w THE THREE PULSE TEMPORAL PATTERN IS TO BE USED FOR EVACUATION USE ONLY w THE SOUND OUTPUT FOR THE TEMPORAL 3 TONE IS RATED LOWER SINCE THE TIME THE HORN IS OFF IS AVERAGED INTO THE SOUND OUTPUT RATING WHILE THE HORN IS PRODUCING A TONE IN THE TEMPORAL 3 MODE ITS SOUND PRESSURE IS THE SAME ...

Страница 2: ...ny LLC postage prepaid to Potter Electrical Signal Company LLC 1609 Park 370 Hazelwood MO 63042 You must prove to the satisfaction of Potter Electrical Signal Company LLC the date of purchase of your appliance You must also enclose a return address Warranty service may only be performed by Potter Electrical Signal Company LLC personnel at Potter Electrical Signal Company LLC s facilities in Hazelw...

Страница 3: ...NT Dimensions de l appareil 2 84 po de largeur x 4 48 po de hauteur x 0 5 po de profondeur BOÎTES DE MONTAGE Boîte pratique 4 po x 2 1 8 po environ Boîte d interrupteur 3 po x 2 po environ avec alvéoles défonçables pour conduit Boîte pour maçonnerie 3 3 4 po x 2 po environ avec alvéoles défonçables concentriques de 1 2 po et 3 4 po Boîte d interrupteur non métallique 3 3 4 po x 2 5 16 po environ A...

Страница 4: ...tre uniquement exécuté par le personnel de Potter Electrical Signal Company LLC dans les installations de Potter Electrical Signal Company LLC s de Hazelwood au Missouri Il faut aussi emballer soigneusement l appareil pour réduire au minimum les risques de dommage pendant le transport Si nous recevons un appareil endommagé en cours de transport nous vous en aviserons et il vous reviendra d obtenir...

Отзывы: