background image

FEP-A, FEP-B, FEP-G, FEP-R SERIES 

ANSI/UL & CAN/ULC COMPLIANT

SEP-A, SEP-B, SEP-G, SEP-R SERIES 

ANSI/UL & CAN/ULC COMPLIANT

WALL MOUNT EXPANDER PLATE FOR USE WITH FASPKR, SPKSTR-24WLP,

SPKSTR-24-AL AND CSPKSTR COLORED LENS SERIES 

MODELS

FEP-A  . . . . . . .WALL MOUNT EXPANDER PLATE WITH SELECTABLE CANDELA STROBE, AMBER LENS, ALERT TEXT , WHITE FACEPLATE

FEP-B  . . . . . . .WALL MOUNT EXPANDER PLATE WITH FIXED 15/75 CANDELA STROBE, BLUE LENS, ALERT TEXT , WHITE FACEPLATE

FEP-G  . . . . . . .WALL MOUNT EXPANDER PLATE WITH FIXED 15/75 CANDELA STROBE, GREEN LENS, ALERT TEXT , WHITE FACEPLATE

FEP-R  . . . . . . .WALL MOUNT EXPANDER PLATE WITH FIXED 15/75 CANDELA STROBE, RED LENS, ALERT TEXT , WHITE FACEPLATE

SEP-A  . . . . . . .WALL MOUNT SURFACE MOUNT EXPANDER PLATE WITH SELECTABLE CANDELA STROBE, AMBER LENS, ALERT TEXT , WHITE FACEPLATE

SEP-B  . . . . . . .WALL MOUNT SURFACE MOUNT EXPANDER PLATE WITH FIXED 15/75 CANDELA STROBE, BLUE LENS, ALERT TEXT , WHITE FACEPLATE

SEP-G  . . . . . . .WALL MOUNT SURFACE MOUNT EXPANDER PLATE WITH FIXED 15/75 CANDELA STROBE, GREEN LENS, ALERT TEXT , WHITE FACEPLATE

SEP-R  . . . . . . .WALL MOUNT SURFACE MOUNT EXPANDER PLATE WITH FIXED 15/75 CANDELA STROBE, RED LENS, ALERT TEXT , WHITE FACEPLATE

I.     INTRODUCTION

The Potter Electric FEP-A, FEP-B, FEP-G, FEP-R, SEP-A, SEP-B, SEP-G, SEP-R is an expander plate device with a high quality colored lens strobe for use with the Potter

Electric FASPKR, SPKSTR-24WLP, SPKSTR-24-AL and CSPKSTR Wall Mount Colored Lens Series to have the ability to mount multiple strobes on a single electrical box for

use on a voice evacuation system.  The high intensity strobe utilizes a Xenon flash tube that generates a high-intensity flash visible from all listed angles.  

The FEP-A and SEP-A are provided with a turn dial which provides candela selection at the installation site; see chart below.  The FEP-B, FEP-G, FEP-R, SEP-B, SEP-G and

SEP-R are fixed candela units, available in 15/75 candela intensity only. The FEP/SEP strobe is designed to be used on a 24VDC system and features ALERT text on the lens.

The FEP-A, FEP-B, FEP-G, FEP-R, SEP-A, SEP-B, SEP-G and SEP-R strobe is listed in compliance with ANSI/UL 1638, Visual Signaling Appliances - Private Mode 

Emergency and General Signaling for use with Emergency Communication Systems and Private Mode Systems.  Additionally, models FEP-A and SEP-A comply with the light

output dispersion requirements of ANSI/UL 1971 for wall mount applications.

Not to be used as a visual public mode alarm notification appliance. 

II.   LOCATION

This appliance is intended for use in Fire Alarm Systems and Emergency Communication Systems and is to be installed in accordance with this manual, the recommendation of

the local authorities having jurisdiction, and other NFPA documents that provide standards on notification appliances for protective signaling systems.  The FEP-A, FEP-B, 

FEP-G, FEP-R, SEP-A, SEP-B, SEP-G, SEP-R is intended for indoor installations only; this appliance is 

NOT

listed for 

outdoor

or drip proof applications.  

550-0592

Page 1

FEP-A AND SEP-A (AMBER COLOR LENS) PRODUCT INFORMATION

Model

Color Lens

FEP-A and SEP-A

AMBER

NOTICE:

DC VOLTAGE RANGE LIMITS: 16-33V.  FWR VOLTAGE

RANGE LIMITS: 16-33V.  THIS PRODUCT WAS ONLY TESTED TO

THE STATED VOLTAGE RANGE(S); DO NOT APPLY 80% AND

110% OF THIS RANGE FOR SYSTEM OPERATION.

AMBER Lens Strobe Current Ratings

Use with FEP-A and SEP-A 

Candela

Regulated 24VDC Max.

Operating Current (mA)

Regulated 24VFWR Max.

Operating Current (mA)

15

78

113

30

96

135

60

137

186

75

180

245

110

224

313

AMBER Lens Strobe Candela Ratings

Use with FEP-A and SEP-A 

Candela

ANSI/UL 1638

On-Axis Candela Rating

ANSI/UL 1971 

Measured Candela Rating,

Wall Mount

15

15

15

30

30

30

60

60

60

75

75

75

110

110

110

NOTICE:

PER NFPA 72, COLORED STROBES ARE TO BE LISTED TO ANSI/UL 1638.

ANSI/UL 1971 IS NOT APPLICABLE TO COLORED LENS DEVICES USED IN 

EMERGENCY COMMUNICATION INSTALLATIONS.  HOWEVER, THESE READINGS

WERE OBTAINED USING THE LIGHT OUTPUT DISPERSION MEASUREMENT 

REQUIREMENTS UNDER ANSI/UL 1971.

FOR FEP-A & SEP-A PRODUCT ONLY

ADJUST INTENSITY BY INSERTING SMALL FLAT

BLADE TO TURN DIAL.  DISPLAYED NUMBER

WILL INDICATE SELECTED CANDELA.

ADDITIONAL CAN/ULC LISTED PRODUCT INFORMATION IS FOUND ON PAGE 4

firealarmresources.com

Содержание FEP-A Series

Страница 1: ...P G FEP R SEP A SEP B SEP G and SEP R strobe is listed in compliance with ANSI UL 1638 Visual Signaling Appliances Private Mode Emergency and General Signaling for use with Emergency Communication Systems and Private Mode Systems Additionally models FEP A and SEP A comply with the light output dispersion requirements of ANSI UL 1971 for wall mount applications Not to be used as a visual public mod...

Страница 2: ...D OR PULSING SIGNALING CIRCUITS HOWEVER USE OF THE POTTER ELECTRIC AVSM CONTROL MODULE IS PERMITTED TO SYNCHRONIZE THE STROBE w REFERENCE AVSM CONTROL MODULE MANUAL 550 0598 DATED 2 1 13 FOR SYNCHRONIZATION MODULE WIRING DIAGRAMS AVSM MANUAL CAN BE OBTAINED BY CALLING POTTER ELECTRIC SIGNAL COMPANY AT 1 800 325 3936 W I R E C O N D U C T I V I T Y 18 AWG 60 16 AWG 95 14 AWG 153 12 AWG 244 FEP B SE...

Страница 3: ...ATION WALL MOUNT SEP SURFACE MOUNT PLATE TO 4 SQUARE x 2 1 8 DEEP METALLIC BACK BOX WALL MOUNT SEP SURFACE MOUNT PLATE INSTALLED SEP PLATE WITH SPEAKER STROBE NOTICE FOR SURFACE MOUNT APPLICATION MATERIAL MUST BE REMOVED FROM SIDE OR TOP AREAS TO ACCOMMODATE SPECIFIC CONDUIT AND FITTINGS THE SEP CAN ACCOMMODATE 1 2 AND 3 4 CONDUIT WITH APPROPRIATE CUTOUTS SPEAKER OR SPEAKER STROBE SOLD SEPARATELY ...

Страница 4: ...VE AND IN LIEU OF ALL OTHER WARRANTIES REMEDIES AND CONDITIONS WHETHER ORAL WRITTEN STATUTORY EXPRESS OR IMPLIED POTTER ELECTRICAL SIGNAL COMPANY LLC DISCLAIMS ALL STATUTORY AND IMPLIED WARRANTIES INCLUDING WITHOUT LIMITATION WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE AND WARRANTIES AGAINST HIDDEN OR LATENT DEFECTS TO THE EXTENT PERMITTED BY LAW TO THE EXTENT SUCH WARRANTIE...

Страница 5: ... R sont homologués conformément à la normeANSI UL1638 Appareils de signalisation visuelle Urgences privées et signalisation générale pour utilisation avec les systèmes de communication d urgence privée De plus les modèles FEP Aet SEP Asont conformes aux exigences de dispersion lumineuse de la norme ANSI UL1971 pour les appareils installés au mur Ne pas utiliser avec un appareil de signalisation d ...

Страница 6: ...UTILISER LE MODULE DE COMMANDE AVSM DE POTTER ELECTRIC POUR SYNCHRONISER LE STROBOSCOPE w SE REPORTER AU MANUEL DU MODULE DE COMMANDE AVSM 550 0598 DATÉ DU 1ER FÉVRIER 2013 POUR DES SCHÉMAS DE CÂBLAGE DU MODULE DE SYNCHRONISATION IL EST POSSIBLE DE SE PROCURER LE MANUEL AVSM EN APPELANT POTTER ELECTRIC AU 1 800 325 3936 C O N D U C T I V I T É D E S F I L S 18 AWG 60 16 AWG 95 14 AWG 153 12 AWG 24...

Страница 7: ...LAQUE DE MONTAGE DU SEP PLAQUESEPINSTALLÉEAVECLEHAUT PARLEURSTROBOSCOPE AVIS POUR UNE INSTALLATION EN SURFACE IL FAUT ENLEVER DES MATÉRIAUX SUR LE CÔTÉ ET SUR LE DESSUS POUR FACILITER LE PASSAGE DES CONDUITS ET DES RACCORDS LE MODÈLE SEP PEUT ACCUEILLIR DES CONDUITS DE 1 2 ET 3 4 PO EN RETIRANT LES ALVÉOLES DÉFONÇABLES APPROPRIÉES HAUT PARLEUR OU HAUT PARLEUR STROBOSCOPE VENDU SÉPARÉMENT AVIS w AL...

Страница 8: ... exigent les lois applicables Cette garantie est nulle et sans effet lorsque les dommages ou la défectuosité sont attribuables à un accident un usage abusif un abus une utilisation anormale une installation fautive un contact avec un liquide un incendie un séisme ou toute autre cause externe à l utilisation de l appareil en dehors des directives établies par Potter Electric Signal Company LLC à l ...