CA-6500

ClAss A ExpAndEr InsTAllATIOn

Potter  Electric  Signal  Company,  LLC  •  St.  Louis,  MO  •  800-325-3936  •  Canada:  888-882-1833

 

•  www.pottersignal.com

General description

The CA-6500 Class A expander allows notification circuits, PLINK circuits and the SLC circuit to be wired for Class A operation when 

used with the PFC-6500 series addressable fire control panels. Class A operation for notification, PLINK and SLC circuit can be selected 

independently in the PFC-6000 series configuration tool.

Installation

The CA-6500 is installed directly in the PFC-6800 series enclosure using the supplied cable assembly and hardware.

Power the system down

1. 

Slide the CA-6500 Class A expander into the opening on the bottom of the PFC-6800 chassis. The tabs on the back of the CA-6500 Class A 

2. 

expander must slide into the slots located in the PFC-6800 chassis. 
Secure the CA-6500 CLass A expander using two #6-32x3/8” screws.

3. 

Plug the 2 x 9 cable assembly (P/N 5210515) into the CA-6500 and PFC-6800.

4. 

Figure 1: Examples of Installing and Wiring a Class A Expander Card

Features

Standby Current 

 

        60 mA

Alarm Current 

              100 mA

Ambient Operating Temperature  32°F-120°F (0°C-49°C) 10%-93%   

 

@ 30°C (86°F) non-condensing humidity

Maximum CA-6500 Expanders     1

Size (WxHxD) 

 

        10-1/4” x 1-1/8” x 5-1/8”

Compatible Panel 

 

        PFC-6800

Product Includes 5 year warranty.

Figure 2: CA-6500 Installation Showing the CA-6500 Ribbon Connection

#6-32 x 1/4 

screws

CA-6500  

Class A Expander

Slides in guides under main board

CA-6500 Ribbon Cable 

CA-6500 Ribbon Cable 

DETAIL B 

SCALE 1 : 1

7165-0328: 0198