PFC-6006

Conventional Fire Panel

8830038 - REV E

   •  

 

4/19

 page 1 OF 2

Potter Electric Signal Company, LLC

      •   

 St. Louis, MO

      •   

 Phone: 800-325-3936

      •   

 www.pottersignal.com

Features

• 

6 programmable Initiating Device Circuits

• 

Class A or Class B Waterflow Initiating Circuit

• 

2 Wire Smoke Detector Compatibility

• 

1.0 Amp Power Supply

• 

1 Notification Circuit rated at 0.5 Amps Regulated

• 

Strobe Synchronization for potter/aMSeCO, gentex, System 

Sensor and Cooper/Wheelock

• 

0.5 Amp Auxiliary Power, Programmable as Constant or 
Resettable

• 

2 x 16 LCD display with system LEDs for clear system status

• 

Keypad for system features

• 

P-Link for Remote Annunciator Connections

• 

Capacity to charge and house 18AH batteries

• 

Onboard Dual Line Digital Alarm Communicator

• 

Built-in Ethernet Connection with listed IP Communicator

• 

Ability to E-mail system status, reports and system configuration

• 

Service Reminder E-mails

General Description

The PFC-6006 is a listed small conventional fire system ideally suited 

to monitor a small fire system such as a  fire sprinkler system. The first 

input is selectable as a Class A or Class B water flow input and the other 

five zones are selectable from a menu of options including two-wire 

smoke detection. The panel has a 1.0 amp power supply that powers 

the panel, charges the batteries and supplies 0.5 amps to a notification 

appliance circuit and 0.5 amps of auxiliary power. The auxiliary power 

is programmable as constant or resettable. 

The control panel is in a metal cabinet with a key lock and lexan window 

for viewing the system status. The printed circuit assembly is mounted 

for quick removal and installation to allow the cabinet to be installed with 

minimal effort. The cabinet houses up to two 12VDC, 18 AH batteries. 
The display is a thirty-two (32) character LCD with system status LEDs. 

The system status is clearly displayed and the panel includes a history 

buffer for past events. The key pad allows navigation into the system 

menu,  limited  programming  and  system  control.  The  condition  and 

events on the panel are clearly displayed to allow the user and installer 

to determine the system status.
The panel has a dual telephone line digital alarm communicator transmitter 

(DACT) built on-board. One or both telephone lines may be enabled 

to allow communication to a remote monitoring station. In addition, an 

updated panel configuration may be sent to the panel through the telephone 

lines. The panel has line in and line out to allow the panel to be installed 

ahead of other telephone equipment on the premises. 

The panel will support up to four (4) of the RA-6075 remote annunciators 

on the P-Link bus. These annunciators include a metal enclosure with a 

key lock and provide full functionality of the system.
The panel is pre-programmed from the factory for monitoring a typical 

wet or dry fire sprinkler system. The programming may be changed using 

the Potter Fire Panel Programmer (available free from www.pottersignal.

com) and a standard Ethernet cable. The default program is as follows:
Input 1 - Waterflow

Input 2 - Smoke Detection (two-wire)

Input 3 - Manual Pull Station

Input 4 - Non-Latching Supervisory

Input 5 - Valve Tamper

Input 6 - Valve Tamper

7165-0328:0204

S735

NYC Fire Dept. 

Certificate of 

approval 

6282

Size (H x W x D)

18-1/2" x 14-1/4" x 4-3/4"

enclosure

Eighteen  (18)  gauge  sheet  steel  with  hinged, 

removable locked door

aC Mains

1.0 amp @ 120 VAC 60 Hz

Battery

105 mA Standby

160 ma alarm

Temperature

32° to 120°F, humidity 93% non-condensing

Standards/

approvals

UL-864

NFPA-70, 72

Technical Specifications