IntelliCheck

Advanced Leak Rate Monitor

Installation, Operation, and 

Instruction Manual

Содержание 1119664

Страница 1: ...Manual 5403773 A 11 20 St Louis MO 800 325 3936 www pottersignal com IntelliCheck Advanced Leak Rate Monitor Installation Operation and Instruction Manual ...

Страница 2: ...s warranty Replacement parts provided under the terms of the warranty are warranted for the remainder of the Warranty Period of the product upon which installed to the same extent as if such parts were original components DISCLAIMER THE FOREGOING WARRANTY IS EXCLUSIVE AND IT IS EXPRESSLYAGREED THAT EXCEPT AS TO TITLE THE COMPANY MAKES NO OTHER WARRANTIES EXPRESSED OR IMPLIED OR STATUTORY INCLUDING...

Страница 3: ...upplying Power to the IntelliCheck 10 Suggested Install Diagrams 11 Wiring Diagram 12 LRM Transducer Installation 12 LRM Current Transformer Installation 12 Optional LRM Solenoid Kit Installation 12 IntelliCheck Startup 13 Setting Sprinkler System Pressure Limits 14 IntelliCheck Leak Detection System 14 Leak Rate Test Operation 15 Setting Sprinkler System Size 15 IntelliView Dashboard Connectivity...

Страница 4: ...each unit must be read thoroughly and completely understood before installation and operation of the Potter IntelliCheck Leak Rate Monitor Unpacking After unpacking unit carefully inspect all parts and equipment for any damage that may have occurred during transit Make sure to tighten fittings bolts etc before putting unit into service Do not operate if damage occurred during shipping handling or ...

Страница 5: ...ons or property Specific procedure must be developed for maintenance of the equipment Do not attempt to disassemble the IntelliCheck Equipment damage may occur and cause the system to function incorrectly Operation of the IntelliCheck above the rated design specifications may be hazardous All wiring should be performed by a licensed electrician and conform to NEC and all applicable local standards...

Страница 6: ... LRM Controller The LRM Controller monitors many aspects of a single dry sprinkler system to ensure the system and air supply are performing optimally The LRM Controller can monitor pressure compressor runtime ambient temp leak rate and can run NFPA 13 and NFPA 25 leak rate tests Also by monitoring these conditions the controller can indicate the development of sprinkler system leaks user interact...

Страница 7: ...IntelliCheck Exterior View Fig 1 1 LRM Display 2 LRM Housing 3 Knockouts for 1 2 Conduit Connection Qty 8 4 FNPT Pipe Connections 5 LRM Pressure Transducer 6 LRM Current Transformer 7 LRM Solenoid Kit optional kit 1 2 3 5 4 6 7 ...

Страница 8: ...8 LRM 5403773 REV A 11 20 IntelliCheck Interior View Fig 2 1 LRM Controller 2 Dip Switches 3 Mounting keyhole slots 4 Ethernet Port 3 3 2 1 4 ...

Страница 9: ...test EXCESSIVE AVERAGE LEAK RATE The amber EXCESSIVE AVERAGE LEAK RATE LED indicates the Leak Rate Monitor continuously exceeded thee allowable leak rate of 36 psi 24 hrs for existing systems NFPA 25 allows a leak rate of 1 5 psi 2 hrs MAINTENANCE The amber MAINTENANCE LED indicates the set compressor runtime hours has been reached TROUBLE The red TROUBLE LED indicates the Leak Rate Monitor has a ...

Страница 10: ...ccording to Fig 4 below 2 The device will recognize the setting change upon power up and will be ready for the set application Note If the dipswitch setting needs to be changed after the device has been powered on Remove the DC Power terminal block change the dipswitch setting per Fig 4 and then reconnect the DC Power terminal block Installation of the IntelliCheck Supplying Power to the IntelliCh...

Страница 11: ...CE DEVICE SOLENOID CHECK VALVE PRESSURE TRANSDUCER LRM TO RISER SUPERVI GAS SU LRM SUPERVISORY GAS SUPPLY TANK AIR MAINTENANCE DEVICE SOLENOID LRM SUPERVISORY GAS SUPPLY PRESSURE TRANSDUCER LRM TO RISER Suggested Install With Tank Fig 6 Suggested Tankless Install Fig 7 ...

Страница 12: ... the compressor 4 Run the cable of the current transformer back to the LRM and through a supplied strain relief fitting and a knockout on the LRM Housing 5 Insert the two 2 wires of the current transformer into the bottom 2 terminals by depressing orange tab inserting wire and releasing tab of the middle right 6 terminal block labeled CT per Fig 8 wiring diagram on page 12 6 Place a supplied clip ...

Страница 13: ...plete hardware tests of BMS Relay and Solenoid Valve if applicable a Press ENTER on the LRM Display keypad b Select Settings using the keypad Press ENTER c Enter passcode 0000 d Select Hardware Test e Select BMS Relay if applicable f Press ENTER to initiate test g Confirm BMS signal was received h Select Solenoid Valve if applicable i Press ENTER to initiate test j Confirm the LED on the solenoid ...

Страница 14: ...LRM s system pressure will need to correlate with the gauge on the sprinkler system The low pressure set point needs to be set 1 psi above the valve manufacturer s actuator trip point or valve trip point determined by water supply pressure and valve ratio Consult the valve manufacturer s data sheet to determine this pressure The LRM low and high pressure set points will not necessarily correlate t...

Страница 15: ...rage leak rate test The Reg LR Test is a 1 hr test 2 NFPA 25 Test to run the NFPA 25 test to see if your system has an average leak rate less than 3 psi 2 hrs The NFPA 25 Test is a 2 hr test The NFPA 25 test can scheduled for a specific date time 1 After selecting NFPA 25 Test select Adjust Schedule 2 Input Recurrence in years 3 Press the right arrow on the LRM Display keypad 4 Set the date on whi...

Страница 16: ...h live status updates of your IntelliCheck The IntelliCheck needs to be wired using a Cat 5 Ethernet cable The Ethernet port is located on the top left of the LRM Controller When the unit is connected to the internet and powered on data will be accessible at www potterintelliview com Refer to Fig 2 for location of CAT 5 jack and MAC ID Serial Number labels Register your IntelliCheck at www potteri...

Страница 17: ...lfunction of the AMD 2 Malfunction of riser mount pressure switch Trouble Alert 9 Compressor Maintenance Unacknowledged Time Exceeded Trouble Alert 8 Temperature Limits Exceeded Trouble Alert 10 Average Leak Rate Limit Exceeded Trouble Alert 11 Short Circuit Detected Issue Maintenance Delay Timer has exceeded setpoint 250 hrs standard Probable Cause 1 Max number of maintenance reminder silenced ti...

Страница 18: ...18 LRM 5403773 REV A 11 20 LRM Housing Dimensional Drawing A C D E F DATE D C E F VENDOR CERTIFICATION 2 86in 72 54mm 1 2 FNPT 1 2 FNPT CHECK VALVE Fig 9 Fig 10 Fig 11 Fig 12 Fig 13 ...

Страница 19: ...19 LRM 5403773 REV A 11 20 1 Main Menu Menu Trees ...

Страница 20: ...20 LRM 5403773 REV A 11 20 2 System Status Menu 3 View History Menu 4 Maintenance Menu ...

Страница 21: ...21 LRM 5403773 REV A 11 20 5 System Settings Menu 6 Network Settings Menu ...

Страница 22: ...22 LRM 5403773 REV A 11 20 7 Leak Rate Settings Menu 8 Compressor Settings Menu ...