2.6.
Chlorine dosing
2.6.1.
Manual injection
Menu
Functions
Possible
settings
Setting
by default
Instructions
Dosing
Manual injection
•
Primes the pump and fills the
semi-rigid pipes
•
Injects chlorine
•
Means of checking that the
pump is working properly
From 1 to 59, in
1 min
increments
10 min
•
To start injecting:
Confirm the selected
setting.
(The pump is
running, and the timer
countdown is displayed in
real time).
•
To pause,
and to restart injection:
Press
OK
.
•
To stop injection:
Press
.
2.6.2.
Activating/disabling chlorine dosing
Menu
Possible settings
Default setting
Dosing
Mode XXX
•
ON
(to activate)
•
OFF
(to disable)
ON
2.6.3.
Setting the chlorine setpoint
Menu
Possible settings
Default setting
Dosing
CL setpoint X.X
From 0.5 to 8 ppm, in increments of 0.1 ppm
1.5 ppm
2.6.4.
Calibrating the free chlorine rate measurement
Menu
Possible settings
Default setting
Dosing
Cl calibration
From 0.1 to 5 ppm, in increments of 0.1 ppm
Current measurement
2.6.5.
Memorising the last refill/change of electrolyte gel
→
The electrolyte gel relates to the amperometric probe (see the manual provided with the probe).
Menu
Sub-menu
Principle
Confirmation
Dosing
Cl gel
Cl gel
Gel added
Date of last refill/change
=
Date of last confirmation
Press twice on
OK
:
the message ‘
Gel Addition Successful
’
will appear.