background image

 

Pub. No. OM-A-10E — April 2004

 

3

 

GENERAL INFORMATION

 

The Pneumatech Drying System is designed to remove 
moisture from compressed air.

When properly installed, the unit requires little 
maintenance or adjustment.

A list of service parts is provided on the attached parts list.

This manual contains important safety information. Read 
THOROUGHLY and follow the Safety Instructions provided 
in this manual and posted on the unit. Keep this manual 
near the unit and in a safe place. Replace this manual if it 
becomes torn or dirty and cannot be properly used.

Please read the Installation & Operation section of this 
manual before attempting to operate the unit.

Please read the Maintenance and Troubleshooting 
sections of this manual before beginning any maintenance 
or service work on this unit.

 

RECEIVING – INSPECTION

 

Inspect equipment. Any concealed shipping 
damage must be reported to the carrier 
immediately. Damage claims should be filed by 
the consignee with the carrier.

 

All the equipment shipped F.O.B. Kenosha, WI becomes 
the property of the purchaser. In all cases of damage, 
visible or suspected, contact your local distributor or 
Pneumatech before attempting to install equipment.

 

SERVICE INQUIRIES:

 

 Provide Model No., Serial No., 

Operating Pressure, Inlet Temperature, Nature of Problem. 
See Dryer Specification Tag located on the control panel.

 

SAFETY INSTRUCTIONS

 

When using air compressors and compressed air 
accessories, basic safety rules and precautions must 
always be followed, including the following:

1.

 

READ ALL INSTRUCTIONS FULLY.

 

2.

 

WIRING & BREAKERS

 

Wiring, breakers and other electrical equipment 
must conform to local and national electrical codes. 
Do not operate this unit with damaged wiring or 
after the unit or air handling parts have been 
dropped or damaged in any manner. Notify 
authorized service facility for examination, repair 
or other adjustments.

3.

 

USE SUITABLE PARTS & ACCESSORIES

 

Do not use air pressurized accessories or parts in the 
air system not suitable for the maximum air pressure 
used. Be sure maximum pressure specified by the 
accessory manufacturer is well above the working 
pressure of your compressor.

4.

 

RELEASE AIR PRESSURE SLOWLY

 

Fast moving air will stir up dust and debris, which 
may be harmful. Release air pressure slowly when 
depressurizing your system to avoid bodily injury.

 

DO NOT install, operate, maintain, adjust
or service this unit without thoroughly
reading this manual.

 

Comply with the National Electrical Code,
Federal, State and Local Codes when
installing or operating this unit.

Содержание EE Series

Страница 1: ...Printed in U S A Publication No OM A 10E April 2004 Owner s Manual HEAT REACTIVATED DRYERS PE SERIES EE SERIES PB SERIES ...

Страница 2: ... Doing this will extend the warranty to 24 months from date of shipment from Company s factory See back page for actual Warranty details DATE OF PURCHASE MODEL SERIAL NO Record above information from nameplate Retain this information for future reference Replacement Price 25 00 ...

Страница 3: ...on Operation 7 General 7 Start Up Procedure 7 Adjustments Settings 8 DMP Microprocessor Control with Cycle Sight 8 Sequence of Operation 10 Shutdown Procedure 11 PB Series Heat Reactivated Blower Purge Air Dryer Installation Operation 13 General 13 Start Up Procedure 13 Adjustments Settings 14 Sequence of Operation 14 Dry Air Sweep 15 Shutdown Procedure 15 Maintenance 17 PE EE Series Heat Reactiva...

Страница 4: ...Programming 19 Open Sensor Condition 19 Setpoint Limit Indication 19 Over Range and Under Range Indication 19 Peak Valley Indication 19 Options Listing with Explanation 21 Audible Alarm 21 Failure to Shift Alarm 21 Heater Failure Alarm 21 High Humidity Alarm 21 Moisture Indicator 21 Over Hi Temperature Alarm 21 Panel Lights 21 PLC Controller 21 Dewpoint Demand Control DPD 22 Pulse Purge Regenerati...

Страница 5: ...o install equipment SERVICE INQUIRIES Provide Model No Serial No Operating Pressure Inlet Temperature Nature of Problem See Dryer Specification Tag located on the control panel SAFETY INSTRUCTIONS When using air compressors and compressed air accessories basic safety rules and precautions must always be followed including the following 1 READ ALL INSTRUCTIONS FULLY 2 WIRING BREAKERS Wiring breaker...

Страница 6: ... be taken Refer to OSHA 29 CFR 1910 134 DISCLAIMER OF WARRANTY If this unit is used to produce breathing air the special equipment and precautions expressed in OSHA 29 CFR 1910 134 for specifications of the necessary equipment and special precautions to make Breathing Air MUST BE used or any warranties are VOID and manufacturer disclaims any liability whatsoever for loss personal injury or damage ...

Страница 7: ...and larger use two sizes of desiccant For all heat reactivated models fill the tower with the 1 4 diameter Activated Alumina first followed by 1 8 Activated Alumina The large desiccant 1 4 size is used to disperse the inlet air flow 7 Close the fill ports and put the dryer in service Refer to the Start Up Procedure listed in this manual MOLECULAR SIEVE OPTION LOW DEWPOINT Dryers with optional Mole...

Страница 8: ...GAUGE REMOVES 66 MOISTURE AIR COOLED AFTERCOOLER 2 P RECEIVER T C PREFILTER REGENERATIVE AIR DRYER PARTICULATE AFTERFILTER 4 5 TO PLANT USE 37 F RECEIVER REFRIGERATED COALESCING AFTERFILTER DRAIN R OPTIONAL 3 VALVE SYSTEM BYPASS P 6 P CONTROL OPTIONAL AUTO DRAIN 1 SEE PNEUMATECH BULLETIN PWC 1 2 SEE PNEUMATECH BULLETIN A 3 3 SEE PNEUMATECH BULLETIN A 16 4 SEE PNEUMATECH BULLETIN A 8 5 SEE PNEUMATE...

Страница 9: ...esistance The element phase to ground should exceed the resistance value by 20 megohms If this value is not indicated energize the heater at low voltage to drive the moisture from the element insulation Remove the cover to vent the moisture from the heater terminal enclosure 11 STEAM CONNECTIONS For units with optional steam heat exchanger the steam connections are supplied as flanges for both inl...

Страница 10: ...ation is based on an 8 hour NEMA Cycle with one half of the total time being for adsorption of moisture from the process gas and one half for desiccant regeneration Specifics of the timing sequence are detailed in Figure 2 the Sequence of Operation Diagram SDG 1 on Page 11 If power is interrupted the DMP controller electronically stores the point in the timing cycle at which power was removed When...

Страница 11: ...at which a temperature is measured there is a high temperature setpoint If the temperature for a given area rises above its setpoint the heater LOAD 5 will be disabled The heater will be re energized when the temperature drops to the setpoint less the specified hysteresis a To set the high temperature setpoints move the slide switch on the back of the module to the TEMP SET position b The high tem...

Страница 12: ...only Any liquids or slugs of water tend to decrease the efficiency of the desiccant and retard the regeneration process to provide the designed dewpoint With the power switch in the ON position at time equal to 0 0 hrs the left tower air inlet valve is open to allow the air to pass through the left tower The right tower inlet valve is closed The saturated compressed air gas passes through the desi...

Страница 13: ...lose the dryer outlet isolation valve b Turn the dryer ON OFF switch to the OFF position c Close the dryer inlet isolation valve on the dryer bypass piping At this time the dryer is isolated and can be depressurized for servicing 2 If the compressed air system has not been piped with a bypass then the following should be completed a Turn the power switch to the OFF position b The tower switching v...

Страница 14: ...VALVE 12 TEMPERATURE GAUGE 14 ELECTRIC HEATER 15 HEATER CHAMBER 16 HEATER CONTROL THERMOSTAT 17 OVER TEMPERATURE THERMOSTAT 18 PURGE ISOLATION VALVE OPTIONAL 19 PURGE ORIFICE ASSEMBLY 20 PURGE ADJUSTMENT PRESSURE GAUGE 22 PILOT AIR SHUT OFF VALVE 23 PILOT AIR FILTER 24 MOISTURE INDICATOR OPTIONAL 25 4 WAY LEFT TOWER SWITCHING SOLENOID 27 4 WAY LEFT TOWER PURGE SOLENOID 29 4 WAY PURGE ISOLATION SOL...

Страница 15: ...lement phase to ground should exceed the resistance value by 20 megohms If this value is not indicated energize the heater at low voltage to drive the moisture from the element insulation Remove the cover to vent the moisture from the heater terminal enclosure 11 STEAM CONNECTIONS For units with optional steam heat exchanger the steam connections are supplied as flanges for both inlet and condensa...

Страница 16: ...wer switch in the ON position at time equal to 0 0 hrs the left tower air inlet valve is open to allow the air to pass through the left tower The right tower inlet valve is closed The saturated compressed air gas passes through the desiccant in the left tower where the desiccant adsorbs the moisture and the dry air at a pressure dewpoint of 40 F or less exits through the left outlet check valve an...

Страница 17: ...ould be turned off at the end of the 4 hour regenerating cycle and with both towers at line pressure If servicing is required advance the time sequence so the purge valves close and both towers pressurize At this time the dryer can be turned off 1 If the compressed air system has been piped with a bypass around the dryer then the following should be completed a Open the bypass valve to allow proce...

Страница 18: ...L 2 AIR INLET VALVE 4 PURGE FLOW CHECK VALVE 8 9 DESICCANT SCREEN 11 PRESSURE GAUGE 12 TEMPERATURE GAUGE 13 DESICCANT THERMOSTAT 14 ELECTRIC HEATER 16 HEATER CONTROL THERMOSTAT 17 18 COOLING FLOW REPRESSURIZING VALVE 19 PURGE ORIFICE ASSEMBLY 20 PURGE ADJUSTMENT PRESSURE GAUGE 22 PILOT AIR SHUT OFF VALVE 26 27 FLEX CONNECTOR 29 THROTTLING VALVE 30 BACK FLOW PREVENTION CHECK VALVE 31 4 WAY LEFT TOW...

Страница 19: ...essary 3 Blow down relief valves 4 Check outlet dewpoint conditions Twelve Months 1 Close the inlet and outlet valves on the dryer or bypass the dryer and completely depressurize the dryer system Open the desiccant fill port and check visually If desiccant is contaminated with oil or broken replace the desiccant 2 Check for leaking check valves per Table 1 symptoms C D in Troubleshooting Guide Rep...

Страница 20: ...e filter Replace if necessary Three Months 1 Every three 3 months check for any leaks in the inlet and or check valves indicated by air coming through the exhaust mufflers when the blower is off 2 Check the prefilter and afterfilter elements for excessive clogging or possible damage Replace as necessary 3 Blow down relief valves 4 Check outlet dewpoint conditions Twelve Months 1 Close the inlet an...

Страница 21: ...nge of the hygrometer OVER RANGE AND UNDER RANGE INDICATION For Ceramic Sensor Probes 1 When the hygrometer detects the maximum value of the Measurement range 68 F flashes on the display 2 When the hygrometer detects the minimum value of the Measurement range 148 F flashes on the display For Aluminum Oxide Sensor Probes Dryers built prior to Year 2000 1 When the hygrometer detects the maximum valu...

Страница 22: ...20 Pub No OM A 10E April 2004 FIGURE 6 DEWPOINT DISPLAY CONTROL WIRING ...

Страница 23: ...robe every two years Probe Replacement Turn the normal demand selector switch to the normal position This will disable the contacts for Dewpoint Demand Isolate and depressurize the probe chamber Replace the probe Pressurize the probe chamber and turn the power back on MOISTURE INDICATOR The moisture indicator consists of a small clear polycarbonate filter filled with a color change silica gel It i...

Страница 24: ...ble A small amount of sample air approximately 2 10 SCFH should expel out the chamber needle valve PULSE PURGE REGENERATION PPR WITH DEWPOINT DEMAND DPD PE EE Series only Pulse Purge Regeneration systems use the same NEMA cycle of 8 hours as PE EE Series dryers except during the regeneration cycle instead of continuously flowing 7 of the purge air and blowing it out into the atmosphere the purge a...

Страница 25: ... pressure on regenerating tower 4 Heater burnout 5 Contactor faulty 6 No power 7 Insufficient heating period 1 Reset thermostat or replace if necessary 2 See A1 3 See C1 4 Check heater replace if necessary 5 Replace heater contactor 6 Check for continuity 7 Contact factory C High back pressure on regenerat ing tower NOTE The tower should be at 0 PSIG during regeneration cycle Any back pressure wil...

Страница 26: ...r if necessary 2 Replace timer 3 Clean or replace pilot filter element 4 Repair or replace pilot air cylinder G High pressure drop in dryer 1 Desiccant retainer screens plugged 2 Excess flow 3 High purge flow 4 Purge valve stays open 5 Repressurizing valve stays open 1 Replace desiccant retainer screens 2 Check inlet flow conditions 3 Check and reset purge pressure 4 Check repressurizing solenoid ...

Страница 27: ... regenerating tower does not pressurize fully desiccant attrition takes place at the time of tower switch over 1 See K L 2 Excess flow due to greater demand in process or addition of extra compressors 2 Check outlet flow N Dewpoint Spike NOTE Blower purge dryers may spike during normal operation due to blower cooling 1 Excessive residual heat in newly regenerated tower 1 Lower heater thermostat se...

Страница 28: ...tive dryers and valves on Intermediate Controls for defects in material or workmanship covering Components only provided a Customer notified the Company of any claim of defect in material or workmanship within sixty 60 months from date of shipment from the Company s factory b Customer holds the Product or Component for inspection by the Company s representative c Customer returns the Component s o...

Отзывы: