![Plymovent CONTROLPRO Скачать руководство пользователя страница 4](http://html.mh-extra.com/html/plymovent/controlpro/controlpro_installation-manual_1569222004.webp)
0000112606/010720/A ControlPro
3
Other options:
- Other type of frequency
inverter (third party)
fan start/stop with optional
alarm feedback only; optional
connection to internal fan
pressure sensor
- Star-delta switch
fan start/stop with optional
alarm feedback only
- Other type of motor
starter
e.g. Direct online (DOL)
4
1.3.2
SHIELD fire safety solutions
5
To enhance fire safety of the entire filter/extraction system,
you can connect the following components to the Panel:
- ShieldControl | Fire detection panel
-
Sliding valves | Pneumatic shut-off sliding valves in the
extraction duct that close automatically in case of fire
- 3/2 solenoid valve | Release valve
1.4
Options and accessories
The following products can be obtained as an option and/or
accessory:
- Panel
HMI cable 60 m/197 ft (instead of standard length
15 or 30 m)
- LightTower
- PT-1000 or PT-2500 | External pressure sensor
- Dustbin level indication
6
(switch or sensor)
1.5
Technical specifications
1.5.1
ControlPro/Panel
Dimensions
Weight
11 kg (24 lbs.)
Material of housing
sheet metal
Protection class
IP 65
Input voltage
100-240 VAC, 50-60Hz
Internal operating
voltage
24 VDC
Power consumption
max. 60 W
Inputs
8x digital input (10 mA wetting current)
3x analogue input (4-20 mA)
Outputs
2x relay output (max. 30 VDC, 2,5 A)
2x output “low-side switch” (24 VDC, 2,5 A)
1x output “low-side switch” (24 VDC, 250
mA)
4x output “low-side switch” (24 VDC, 30 mA)
1x analogue output (4-20 mA)
Internal connectors
2x CAN + power (ControlPro/HMI & Control/
SlaveBoard)
1x RS-485 (Modbus) to frequency inverter
(19200,8N1)
1x USB 2.0 (host only, USB A receptacle)
1x ethernet (for service purposes)
1x RS-232 (for service purposes)
Internal pressure
sensors
2x integrated pressure sensor
Working range: 0-4000 Pa (0-16 in. WG)
4. Full integration of communication between the HMI and the Plymovent VFD/
Panel (frequency inverter) through an RS-485 cable. Including main switch to
de-energize the entire filter system, thus complying with CE safety
requirements.
5. Only in combination with the MDB; not suitable for the SCS.
SHIELD is a safety system that consists of components for fire prevention,
detection and suppression.
6. Future development
Guidelines &
standards
EMC 2014/30 EU
LVD 2014/35 EU
EN 61000-6-2
IEC 60204-1
EN 61000-6-4
IEC 61131-2
IEC 61439-1
Approvals &
certificates
CE
cULus (UL 508A)
1.5.2 ControlPro/HMI
Dimensions
255 x 165 x 125 mm (10.0 x 6.5 x 4.9 in.)
Weight
900 g (2 lbs.)
Material of housing
-
flammability
standard
PC/ABS
- UL94 V-0
Operating voltage
24 VDC (+/- 15%)
Power consumption
-
display off: nom. 4 W
- display on: max. 5 W
External connectors
- CAN + power (connection to Panel)
[M12-5p shielded connector]
- USB 2.0 (host only)
[USB A receptacle, with dust cap]
- ethernet 10/100 Mbit/s
[RJ45, shielded, with dust cap]
Display:
- size
- 7”
- type
- resistive touch screen
- brightness
- 300 cd/m²
- colour
- 262K
- resolution
- 800 x 480 pixels
Guidelines &
standards
EMC 2014/30 EU
LVD 2014/35 EU
EN 61000-6-2
IEC 60204-1
EN 61000-6-4
Approvals &
certificates
CE
1.5.3
Control/SlaveBoard
Operating voltage
24 VDC (+/- 15%)
Current
max. 2,5 A
Internal connectors
2x CAN + power (max. 24 VDC, 2,5A)
Guidelines &
standards
EMC 2014/30 EU
LVD 2014/35 EU
EN 61000-6-2
IEC 60204-1
EN 61000-6-4
Approvals &
certificates
CE
1.6
Ambient conditions
1.6.1
ControlPro/Panel
Pressure sensors:
Ambient temperature:
internal
external
- min.
- nom.
- max.
0°C (32°F)
+20°C (68°F)
+50°C (122°F)
-20°C (-4°F)
+20°C (68°F)
+50°C (158°F)
Max. relative humidity
80%
Suitable for outdoor use
yes
1.6.2 ControlPro/HMI
Ambient temperature:
- min.
- nom.
- max.
0°C (32°F)
+20°C (68°F)
+50°C (122°F)
Max. relative humidity
80%
Suitable for outdoor use
no