S MA RT SC AN
®
Power Loss Alarm
It is possible to fit a power loss alarm to the system, to alert the user if power is cut. Because the alarm is
installed to detect a loss of power, it must be installed on a separate spur of the same circuit as the
Automist system.
Many options for such an alarm are available and Plumis recommends the purchase of an inexpensive
alarm from Amazon, using the following link:
B) Installing the Automist Smartscan Head
•
Route the high pressure hose and a Plumis-specification Smartscan Head Cable between the pump
and the chosen spray head location. Smartscan head Cable is ALPHA WIRE 2466L SL005 Multipair
Screened Cable or equivalent
3
, consisting of two twisted pairs, a conductive shield and an
insulating sleeve.
•
Connect the ¼” BSP high pressure hose to the spray head assembly
•
Pass the Smartscan Head Cable through the cable lock at the back of the spray head assembly.
3 Farnell Order Code 1712538
IMPORTANT: Always hold
the pivot base whilst
tightening the high
pressure hose
Pivot base