Automist Smartscan Hydra
®
DIOM Manual - version 3.01.0
Plumis Ltd Copyright © 2020. All Rights Reserved.
Page 64 of 116
S MA RT SC AN
®
Plumis Wireless Smoke Heat Alarm (DT01) Installation and Battery replacement
Once a suitable location is found, mount the alarm as follows:
1.
Refer to the diagram below and install the mounting base on the ceiling or on the wall (if permitted
for the application) using the screw location as required. Use the two screws and anchors
provided. Manoeuvre the base so the screws are at the elbow of the screw slots and secure.
2.
Fit the alarm inside the base aligning it over the base as shown (alarm alignment notch must be
slightly offset from mounting base tamper release tab), then turn the detector in a clockwise
direction until it clicks into place.
Figure 57: Mounting the detector
During initial power-up the LED blinks alternately red, yellow then green. It takes about 8 seconds for the
detector to stabilize.
After power-up has completed and the alarm is functioning normally, the green LED blinks once every 12
seconds.
To replace the batteries:
1.
Remove the alarm from its mounting base by twisting the alarm counter clockwise. Remove and
dispose of the batteries according to your local regulations.
2.
To ensure proper power-down sequence, wait a minimum of 20 seconds before installing new
batteries.
3.
Install 3 new AAA batteries (ideally Duracell or Energizer) in the battery compartment. Follow the
polarity diagram inside the compartment. If the batteries are incorrectly inserted, please remove
gently with a non-conductive tool, and correctly reinsert
4.
Reinstall the alarm onto the mounting base by turning the detector clockwise until the mating
marks align.
5.
After the power-up sequence the green LED must blink about once every 12 seconds to indicate
normal operation. If the batteries are not installed correctly, the alarm will not operate, and the
batteries may be damaged. If the detector does not power-up, check the batteries are correctly
installed and/or for fully charged batteries. Please refer to the Apollo flash codes for more details.