Automist Smartscan Hydra
®
DIOM Manual - version 3.01.0
Plumis Ltd Copyright © 2020. All Rights Reserved.
Page 100 of 116
S MA RT SC AN
®
Finishing Up
Disconnect the needle adapter from the PCB by pinching the legs in and pulling upwards. The controller
requires a power cycle to start running the newly programmed software. To do this disconnect the
Power/Data connector in the bottom right of the board, then reconnect. You will now hear the Controller
start-up chime, and the Hydra heads will return to the parked position. Close the lid of the controller. Screw
in the top and bottom lid fastening screws. There is no need to commission the system after a software
update unless commissioning is required (see page 75).
Cleaning
The Automist Smartscan Hydra wall-mounted head must be wiped clean with a damp cloth. Do not attempt
to clean with any other chemical cleaners or abrasives
To clean your alarm, remove it from the mounting base. N.B. This will trigger a tamper error on the
controller. You can clean the interior of the alarm by using compressed air or a vacuum cleaner hose and
blowing or vacuuming through the openings around the perimeter of the detector. The outside of the
detector can be wiped with a damp cloth.
After cleaning reinstall and test your alarm by using. If cleaning does not restore the alarm to normal
operation the alarm must be replaced.
It is recommended that the homeowner test the alarm in ALARM TEST MODE (see page 86) once a week!
This mode allows you to test the alarms causing the paired heads to begin scanning.
Repair
CAUTION!
Do not attempt to repair the Automist Smartscan Hydra head, controller, or pump unit. Doing so
will invalidate your warranty.
Automist Smartscan Hydra must be serviced or replaced if any part of the system, including any heat
alarms, has been exposed to fire conditions.
Troubleshooting
Problem
Probable Cause
Recommended Action
Pressure does
not consistently
reach correct
range (too low)
during
commissioning
procedure
Leakage between
pump and Automist
Smartscan Hydra head
Check for leakage on the high-pressure water path, for
example the quick-fit connector, tee connections or
sprayhead may not be secured, or its O-ring may not have
been fitted.
Re-run commissioning.