the controller operates only with a standard room thermostat. 

Return protection 

A set of parameters available after connecting return sensor, responsible for return protection of the 
boiler  with  hydraulic  installation  with  four-way  valve  equipped  with  mixer  servomotor.  It  is  not 
recommended  to  turn  on  return  protection  function  as  it  may  cause  often  supply  pauses  in  mixer 
circuit. Instead of that it is recommended to use higher preset boiler temperatures  (70-

75°C) which 

will  cause,  in  installation  with  four-way  valve  (with  servomotor)  automatic  return  temperature 
increase. 

Minimum boiler 
temperature 

Minimum  preset  boiler  temperature  that  user  can  set  in  the  user  menu  and  minimum  that    the 
controller can set automatically, e.g. from night decreases, floor control etc. 

Maximum boiler 
temperature 

Maximum  preset  boiler  temperature  that  user  can  set  in  user  menu  and  maximum  that  can  be 
automatically set by the controller, e.g. from night decreases, floor control etc. 

Auxiliary boiler 

Description in section 12.14 

A,B,C FL parameter 

Applicable  to  FuzzyLogic  mode.  They  affect  speed  at  which  boiler  temperature  reaches  preset 
value  and  stability  of  sustaining  this  temperature.  It  is  not  recommended  to  change  these 
parameters  if  the  control  speed  and  stability  of  sustaining  value    of  preset  temperature  is  at  the 
desired level. 

Boiler cooling 
temperature 

Temperature  of  preventive  boiler  cooling.  Above  this  temperature  the  controller  switches  on  the 
HUW  pump  and  opens  mixer  circuits  to  cool  down  the  boiler.  The  controller  will  switch  off  HUW 
pump  if  the  water  temperature  exceeds  maximum  value.  The  controller  will  not  open  the  mixer 
circuit when 

Mixer support = Floor on.

 

Boiler thermostat 
function 

Available options: 

 

Turn  off  boiler

 

–  after  activation  of  boiler  thermostat  the  burner  is  off,  only  boiler  pump 

operates. 

 

Turn off pump 

– boiler pump will be off when boiler thermostat activates. Burner still operates. 

 

Turn off burner and pump

 

– after boiler thermostat activates the burner and pump of the boiler 

will be turned off. 

14.3

 

CH and HUW 

Parameter 

Description 

CH pump activation 
temperature 

Parameter  determines  temperature  at  which  the  CH  pump  of  the  boiler  will  switch  on.  It  prevents 
retting  of  the  boiler  due  to  cooling  it  with  cold  water  returning  from  the  installation.  Attention: 
switching  only  pump  off  does  not  guarantee  boiler  protection  against  retting  and,  as  a  result, 
corrosion.  Additional  automatics  should  be  used,  e.g.  four-way  valve  or  thermostatic  three-way 
valve. 

CH pump standstill 
during HUW loading 

Available after connecting HUW sensor. Extended HUW container loading with HUW priority on may 
result  in  excessive  CH  installation  cooling,  since  with  such  settings  CH  pump  is  off.  CH  pump 
standstill  parameter  during  HUW  loading  prevents  it  by  enabling  periodical  CH  pump  activation 
during  loading  of  HUW  container.  CH  pump  will  activate  after  that  time  for  constant  programmed 
time of 30 sec. 

Minimum HUW 
temperature 

Available after connecting HUW sensor. It is a parameter with which user can be limited to set too 
low preset HUW temperature. 

Maximum HUW 
temperature 

Available after connecting HUW sensor. The parameter determines till what maximum temperature 
HUW container will be heated during discharging of excess heat from the boiler during alarms. It is a 
very important parameter, since setting its value too high might result in risk of scalding users with 
utility  water.  Too  low  value  of  this  parameter  might  result  in  that  during  boiler  overheat  it  will  be 
impossible  to  discharge excess  of  the  heat  to  HUW container. When  designing  HUW installation  a 
risk  of 

damaging  the  controller  must be considered.  Due  to  controller’s malfunction  water  in HUW 

container  might  be  heated  up  to  dangerous  temperature,  causing  scalding  of  users.  Additional 
protection in a form of thermostatic valves should be used. 

Increasing boiler 
temp. from HUW and 
mixer 

The parameter determines by how many degrees the preset boiler temperature is increased to load 
the  HUW  container,  buffer  and  mixer  circuit.  Increasing  the  temperature  is  done  only  when 
necessary. When preset boiler temperature is at sufficient level the controller will not change it due 
to necessity of loading HUW container, buffer or mixer circuit.  

Extending HUW 
pump operation time 

Available after connecting HUW sensor. After HUW container is loaded and HUW pump is off there 
can  be  a danger  of  boiler  overheat.  It happens  when  the preset  HUW temperature  is set to  higher 
than preset boiler temperature. This problem especially concerns HUW pump operation in SUMMER 
mode, where CH pump is off. To cool down the boiler, HUW pump operation can be extended by the 
time of 

Extending HUW pump operation time

Circulation pump 
standstill time 

Parameters are available after connecting additional module C. Standstill time between the periods 
of  circulating  pump  operation  is  defined  by  the  value  of  the 

Circulating  pump  standstill  time 

parameter  (recommended  setting  15-40  min.).  Circulating  pump  operates  cyclically  for 

Circulating 

pump operation time 

(recommended setting 60-120 sec.) 

Circulation pump 
operation time 

Heat exchanger 

Parameter  is  available  after  setting 

Show  advanced 

parameter  to 

YES. 

Applies  only  to  hydraulic 

installations with heat exchanger between open and closed circuit. 
Available options: 

 

YES 

– boiler pump operates continuously in short circuit boiler – exchanger, it is not turned off, 

e.g. from SUMMER mode or HUW priority 

 

NO 

– boiler pump operates normally. 

Содержание ecoMAX920P1-S TOUCH

Страница 1: ...TALLATION AND OPERATING MANUAL ISSUE 1 0_EN Functions available in additional module B ecoSTER TOUCH ecoNET300 ecoNET apk ecoNET app www econet24 com Devices are not standard equipment of the controll...

Страница 2: ...eam condensation conditions and cannot be exposed to water MAIN PRINCIPLES OF PROPER BOILER OPERATION WITH INDIVIDUAL FUZZY LOGIC The controller must be programmed individually for a given boiler and...

Страница 3: ...ROTECTION LEVEL 24 12 5 ELECTRIC CONNECTION 24 12 6 ELECTRIC SCHEME 26 12 7 CONNECTION OF TEMPERATURE SENSORS 28 12 8 CONNECTING THE WEATHER TEMP SENSOR 28 12 9 CONNECTING THE EXHAUST TEMPERATURE SENS...

Страница 4: ...is intended for boiler manufacturers Before applying the controller a boiler manufacturer should check if the controller s matching with the given boiler type is proper and whether it can cause dange...

Страница 5: ...bserve these instructions 4 Storage of documentation This assembly and operation manual as well as any other applicable documentation should be stored diligently so that it was available at any time I...

Страница 6: ...6...

Страница 7: ...USER SETTINGS ecoMAX920P1 S TOUCH...

Страница 8: ...n Decrease value Schedule Night time circ pump decrease Summer Winter SUMMER mode Summer Winter Auto SUMMER mode activation temp SUMMER mode deactivation temp Mixer 1 5 settings 5 Preset mixer tempera...

Страница 9: ...10 Functions affecting preset boiler temperature Following symbols signal respectively room thermostat contacts open preset room temperature reached preset boiler temperature decrease due to activated...

Страница 10: ...er e g boiler inactivity period in STOP mode Fan is switched on with the power set by Firing up airflow parameter Small fuel dosage is given 20 of basic dosage If during period set by Ignition test ti...

Страница 11: ...teresis H2 and 30 H1 hysteresis Hysteresis H1 and H2 of power modulation Operation in Fuzzy Logic mode In Fuzzy Logic mode the controller automatically regulates burner power to allow boiler operation...

Страница 12: ...ng the fuel and performs cyclic blowing according to Blowing time and Blowing pause settings in order to burn the remaining fuel After flame brightness dropping below Burning out end threshold value i...

Страница 13: ...the menu Summer Winter SUMMER mode for Summer Attention when boiler operates without heating buffer and the controller is switched into SUMMER mode than Standard mode operation is recommended It is no...

Страница 14: ...m temperature 18 C the controller will move heating curve by 2 C In some cases described in point 8 18 it can be necessary to adjust heating curve shift In this configuration room thermostat is able t...

Страница 15: ...oiler Time periods allow setting temperature reduction in given time period i e at night or when user leaves the heated room Thanks to it preset temperature can be reduced automatically without loss o...

Страница 16: ...Fuel level 0 There is a possibility to skip the calibration process if the parameters are set correctly Feeder efficiency and Capacity of tank which are in Service settings Burner settings Operation 8...

Страница 17: ...er operation status alarms allows to set controller parameters and its operation modes it also serves as an additional panel controlling the boiler 8 26 Cooperation with internet module The controller...

Страница 18: ...18...

Страница 19: ...19 INSTALLATION AND SERVICE SETTINGS ecoMAX920P1 S TOUCH...

Страница 20: ...c If the return sensor is clip on insulate it thermally from the surroundings and improve thermal contact with the pipe by using thermal grease Boiler s preset temperature must be set high enough to p...

Страница 21: ...te 80 C Boiler settings Minimum boiler temperature 75 C Service settings Boiler settings CH pump activation temperature 55 C Service settings CH and HUW settings Buffer support Yes Service settings Bu...

Страница 22: ...gs Buffer settings Buffer loading start temperature 50 C Service settings Buffer settings Buffer loading end temperature 75 C Service settings Buffer settings Mixer 1 2 3 4 support CH on Service setti...

Страница 23: ...ontroller 5 IP20 from the front side of the executive module IP00 from the side of the executive module cover against damage to the STB capillary placed in the terminal box 12 Controller installation...

Страница 24: ...ction device RCD with inrush current I n 30 mA protecting against the effects of the regulator including protection against fire After deactivating the controller there still can be a dangerous voltag...

Страница 25: ...from the casing of the controller as shown below Cables secured from splitting should be connected to screw terminals of the 6 connector Cables should be put through cable outlets in the casing 1 and...

Страница 26: ...otor AS ash removal servomotor RT room panel or ISM radio module Lambda probe module B module to support additional heating circuits BT boiler temp sensor type CT4 FS feeder temp sensor type CT4 RS bo...

Страница 27: ...rcuit temp sensor type CT4 T3 buffer upper temp sensor type CT4 T4 buffer lower temp sensor type CT4 LS fuel level sensor cooperating with bunker feeder T standard mixer room thermostat H voltage outp...

Страница 28: ...between these wires should be 100 mm Do not allow sensor wires to contact hot parts of the boiler and heating system Wires of temperature sensors are heat resistant to the temperature not exceeding 1...

Страница 29: ...2 1385 0 1385 8 125 1478 5 1479 4 1480 3 150 1572 0 1573 1 1574 2 CT2S Pt1000 exhaust Temp C Min Nom Max 0 999 7 1000 0 1000 3 25 1096 9 1097 3 1097 7 50 1193 4 1194 0 1194 6 100 1384 2 1385 0 1385 8...

Страница 30: ...al module B Exemplary wiring diagram for connecting auxiliary boiler to the controller 1 additional module B 2 auxiliary boiler gas or oil 3 relay RM 84 2012 35 1006 and base GZT80 RELPOL By standard...

Страница 31: ...enu Service settings Boiler settings Auxiliary boiler and set zero value for its switching on temperature Exemplary external alarm device connection 1 additional module B 2 external alarm device 3 rel...

Страница 32: ...s power indicator of valve opening has been calibrated Attention in mixers 2 3 4 5 the calibration is automatic after switching on the mains power In case of these mixers wait until indicator of valve...

Страница 33: ...hich is not the controller s equipment Connect D D wires to G3 socket in the controller Maximum cables length to room panel depends on wires cross section and for 0 25 mm2 wire it should not exceed 30...

Страница 34: ...wer increasing Stoker emptying time Cycle Poker operation time Poker pause Stoker emptying time Roto Poker operation time Poker pause Stoker emptying time Cycle x K Poker operation time Poker pause Po...

Страница 35: ...ing start temperature Buffer loading end temperature Mixer 1 5 settings Thermostat selection Mixer support OFF CH ON Floor ON Only pump Minimum mixer temperature Maximum mixer temperature Proportional...

Страница 36: ...ng the fuel Feeder 2 minimum time Minimum operation time for feeder placed in burner Feeder 2 operation time Determines operation time of additional feeder bunker feeder The feeder is connected to add...

Страница 37: ...ted after finishing of which it will start operation again increasing the device s power to preset operation conditions Mechanism 2 when the burner finishes its operation in Burning out Burning off mo...

Страница 38: ...lt in excessive CH installation cooling since with such settings CH pump is off CH pump standstill parameter during HUW loading prevents it by enabling periodical CH pump activation during loading of...

Страница 39: ...eset temperature the supply of mixer pump will be off After decreasing circuit temperature by 2 C pump is switched on again This option is usually used to control floor heating pump when it cooperates...

Страница 40: ...ue to 0 switches alarm off Outputs test time After this time all devices that were switched ON in Manual control menu will be switched off automatically Show advanced Available options YES displays hi...

Страница 41: ...lame striking back will be off in this case Protective function against flame strike back does not work when feeder sensor is disconnected or when it s damaged or when the controller is not supplied T...

Страница 42: ...the form of two files file with panel program and a file with program for module A of the controller Place new firmware directly on the memory card do not place data in a folder Then connected electri...

Страница 43: ...necessary information read from nameplates In case of the controller it is essential to know its serial number If the serial number is unknown provide its model design and year of production Controlle...

Страница 44: ...and the fuel is not provided check the feeder according to its manual Fuel feeder not operating does not provide fuel Check if feeder wires are correctly connected to terminals If STB temperature lim...

Страница 45: ...45...