28 

 

12.7

 

Connection of temperature 

sensors 

The  controller  cooperates  only  with  sensors 
of  type  CT4  and  CT2S.  The  use  of  other 
types of temp. sensors is prohibited. 
Sensor wires may be extended using wires of 
cross-section  area  not  less  than  0,5  mm

2

Total  length  of  wires  of  each  sensor  should 
not exceed 15 m. 
Insert  boiler  temperature  sensor  into 
thermometer  well  fastened  to  boiler  shell. 
Fasten  feeder  temperature  sensor  to  the 
surface  of  feeder  screw  tube.  Insert 
temperature  sensor  of  HUW  container  into 
thermometer  well  welded  to  the  container. 
The  best  way  to  mount  mixer  temperature 
sensor is to insert it into a sleeve located in 
the  stream  of  flowing  water,  however,  it  is 
also allowed to fasten the sensor in a contact 
manner  provided  that  the  sensor  and  the 
pipe are properly heat-insulated. 

 

Mounting temperature sensor: 1 - pipe, 2 – clamps, 3 - 
thermal insulation, 4 -  temperature sensor

 

 

Sensors shall be protected against 
loosening  from  surfaces  they  are 
mounted to. 

Make  sure  thermal  contact  between  the 
sensors and the surface which temperature is 
measured  is  good.  Apply  thermal  paste  to 
improve the contact. Pouring sensors with oil 
or water is not allowed. Sensor wires should 
be  separated  from  power  supply  wires. 
Otherwise,  temperature  indications  may  be 
erroneous.  Min.  distance  between  these 
wires should be 100 mm.  
Do  not  allow  sensor  wires  to  contact  hot 
parts of the boiler and heating system. Wires 
of temperature sensors are heat resistant to 
the temperature not exceeding 100°C. 

12.8

 

Connecting the weather temp. 

sensor 

The regulator cooperates only with a weather 
temp.  sensor  of  the  CT6-P  type.  The  sensor 
should be installed on the coolest wall of the 
building.  Usually  it  is  the  northern  wall, 
under  the  roof.  The  sensor  should  not  be 
exposed  to  direct  sunrays  and  rain.  The 
sensor should be installed at least 2 m above 
the ground far away from windows, chimneys 
and other sources of heat which could disturb 
the  temperature  measurement.  To  connect 
use  wire  with  diameter  at  least  0,5  mm

2

  up 

to  25  m  long.  Polarization  of  wires  is  not 
essential.  Second  end  should  be  connected 
to terminals of controller or properly to used 
kind  of  controller.  The  sensor  should  be 
screw  to  the  wall.  Access  to  assembly  holes 
is possible after unscrewing the cover of the 
sensor. 

 

Weather sensor connection.

 

12.9

 

Connecting the exhaust 

temperature sensor 

The exhaust temp. sensor should be fitted in 
the  boiler  flue.  The  gap  between  the  sensor 
and  the  flue  should  be  sealed.  The  sensor 
should be installed by a qualified fitter, while 
observing  regulations  applicable  for  chimney 
systems.  The  emission  sensor  should  be 
connected  to  the  sensor  terminals  acc.  to 
The  emission  sensor  lead  cannot  touch  hot 
elements  of  the  boiler  and  the  flue,  the 
temperature of which exceeds 220°C. 

Содержание ecoMAX920P1-S TOUCH

Страница 1: ...TALLATION AND OPERATING MANUAL ISSUE 1 0_EN Functions available in additional module B ecoSTER TOUCH ecoNET300 ecoNET apk ecoNET app www econet24 com Devices are not standard equipment of the controll...

Страница 2: ...eam condensation conditions and cannot be exposed to water MAIN PRINCIPLES OF PROPER BOILER OPERATION WITH INDIVIDUAL FUZZY LOGIC The controller must be programmed individually for a given boiler and...

Страница 3: ...ROTECTION LEVEL 24 12 5 ELECTRIC CONNECTION 24 12 6 ELECTRIC SCHEME 26 12 7 CONNECTION OF TEMPERATURE SENSORS 28 12 8 CONNECTING THE WEATHER TEMP SENSOR 28 12 9 CONNECTING THE EXHAUST TEMPERATURE SENS...

Страница 4: ...is intended for boiler manufacturers Before applying the controller a boiler manufacturer should check if the controller s matching with the given boiler type is proper and whether it can cause dange...

Страница 5: ...bserve these instructions 4 Storage of documentation This assembly and operation manual as well as any other applicable documentation should be stored diligently so that it was available at any time I...

Страница 6: ...6...

Страница 7: ...USER SETTINGS ecoMAX920P1 S TOUCH...

Страница 8: ...n Decrease value Schedule Night time circ pump decrease Summer Winter SUMMER mode Summer Winter Auto SUMMER mode activation temp SUMMER mode deactivation temp Mixer 1 5 settings 5 Preset mixer tempera...

Страница 9: ...10 Functions affecting preset boiler temperature Following symbols signal respectively room thermostat contacts open preset room temperature reached preset boiler temperature decrease due to activated...

Страница 10: ...er e g boiler inactivity period in STOP mode Fan is switched on with the power set by Firing up airflow parameter Small fuel dosage is given 20 of basic dosage If during period set by Ignition test ti...

Страница 11: ...teresis H2 and 30 H1 hysteresis Hysteresis H1 and H2 of power modulation Operation in Fuzzy Logic mode In Fuzzy Logic mode the controller automatically regulates burner power to allow boiler operation...

Страница 12: ...ng the fuel and performs cyclic blowing according to Blowing time and Blowing pause settings in order to burn the remaining fuel After flame brightness dropping below Burning out end threshold value i...

Страница 13: ...the menu Summer Winter SUMMER mode for Summer Attention when boiler operates without heating buffer and the controller is switched into SUMMER mode than Standard mode operation is recommended It is no...

Страница 14: ...m temperature 18 C the controller will move heating curve by 2 C In some cases described in point 8 18 it can be necessary to adjust heating curve shift In this configuration room thermostat is able t...

Страница 15: ...oiler Time periods allow setting temperature reduction in given time period i e at night or when user leaves the heated room Thanks to it preset temperature can be reduced automatically without loss o...

Страница 16: ...Fuel level 0 There is a possibility to skip the calibration process if the parameters are set correctly Feeder efficiency and Capacity of tank which are in Service settings Burner settings Operation 8...

Страница 17: ...er operation status alarms allows to set controller parameters and its operation modes it also serves as an additional panel controlling the boiler 8 26 Cooperation with internet module The controller...

Страница 18: ...18...

Страница 19: ...19 INSTALLATION AND SERVICE SETTINGS ecoMAX920P1 S TOUCH...

Страница 20: ...c If the return sensor is clip on insulate it thermally from the surroundings and improve thermal contact with the pipe by using thermal grease Boiler s preset temperature must be set high enough to p...

Страница 21: ...te 80 C Boiler settings Minimum boiler temperature 75 C Service settings Boiler settings CH pump activation temperature 55 C Service settings CH and HUW settings Buffer support Yes Service settings Bu...

Страница 22: ...gs Buffer settings Buffer loading start temperature 50 C Service settings Buffer settings Buffer loading end temperature 75 C Service settings Buffer settings Mixer 1 2 3 4 support CH on Service setti...

Страница 23: ...ontroller 5 IP20 from the front side of the executive module IP00 from the side of the executive module cover against damage to the STB capillary placed in the terminal box 12 Controller installation...

Страница 24: ...ction device RCD with inrush current I n 30 mA protecting against the effects of the regulator including protection against fire After deactivating the controller there still can be a dangerous voltag...

Страница 25: ...from the casing of the controller as shown below Cables secured from splitting should be connected to screw terminals of the 6 connector Cables should be put through cable outlets in the casing 1 and...

Страница 26: ...otor AS ash removal servomotor RT room panel or ISM radio module Lambda probe module B module to support additional heating circuits BT boiler temp sensor type CT4 FS feeder temp sensor type CT4 RS bo...

Страница 27: ...rcuit temp sensor type CT4 T3 buffer upper temp sensor type CT4 T4 buffer lower temp sensor type CT4 LS fuel level sensor cooperating with bunker feeder T standard mixer room thermostat H voltage outp...

Страница 28: ...between these wires should be 100 mm Do not allow sensor wires to contact hot parts of the boiler and heating system Wires of temperature sensors are heat resistant to the temperature not exceeding 1...

Страница 29: ...2 1385 0 1385 8 125 1478 5 1479 4 1480 3 150 1572 0 1573 1 1574 2 CT2S Pt1000 exhaust Temp C Min Nom Max 0 999 7 1000 0 1000 3 25 1096 9 1097 3 1097 7 50 1193 4 1194 0 1194 6 100 1384 2 1385 0 1385 8...

Страница 30: ...al module B Exemplary wiring diagram for connecting auxiliary boiler to the controller 1 additional module B 2 auxiliary boiler gas or oil 3 relay RM 84 2012 35 1006 and base GZT80 RELPOL By standard...

Страница 31: ...enu Service settings Boiler settings Auxiliary boiler and set zero value for its switching on temperature Exemplary external alarm device connection 1 additional module B 2 external alarm device 3 rel...

Страница 32: ...s power indicator of valve opening has been calibrated Attention in mixers 2 3 4 5 the calibration is automatic after switching on the mains power In case of these mixers wait until indicator of valve...

Страница 33: ...hich is not the controller s equipment Connect D D wires to G3 socket in the controller Maximum cables length to room panel depends on wires cross section and for 0 25 mm2 wire it should not exceed 30...

Страница 34: ...wer increasing Stoker emptying time Cycle Poker operation time Poker pause Stoker emptying time Roto Poker operation time Poker pause Stoker emptying time Cycle x K Poker operation time Poker pause Po...

Страница 35: ...ing start temperature Buffer loading end temperature Mixer 1 5 settings Thermostat selection Mixer support OFF CH ON Floor ON Only pump Minimum mixer temperature Maximum mixer temperature Proportional...

Страница 36: ...ng the fuel Feeder 2 minimum time Minimum operation time for feeder placed in burner Feeder 2 operation time Determines operation time of additional feeder bunker feeder The feeder is connected to add...

Страница 37: ...ted after finishing of which it will start operation again increasing the device s power to preset operation conditions Mechanism 2 when the burner finishes its operation in Burning out Burning off mo...

Страница 38: ...lt in excessive CH installation cooling since with such settings CH pump is off CH pump standstill parameter during HUW loading prevents it by enabling periodical CH pump activation during loading of...

Страница 39: ...eset temperature the supply of mixer pump will be off After decreasing circuit temperature by 2 C pump is switched on again This option is usually used to control floor heating pump when it cooperates...

Страница 40: ...ue to 0 switches alarm off Outputs test time After this time all devices that were switched ON in Manual control menu will be switched off automatically Show advanced Available options YES displays hi...

Страница 41: ...lame striking back will be off in this case Protective function against flame strike back does not work when feeder sensor is disconnected or when it s damaged or when the controller is not supplied T...

Страница 42: ...the form of two files file with panel program and a file with program for module A of the controller Place new firmware directly on the memory card do not place data in a folder Then connected electri...

Страница 43: ...necessary information read from nameplates In case of the controller it is essential to know its serial number If the serial number is unknown provide its model design and year of production Controlle...

Страница 44: ...and the fuel is not provided check the feeder according to its manual Fuel feeder not operating does not provide fuel Check if feeder wires are correctly connected to terminals If STB temperature lim...

Страница 45: ...45...

Страница 46: ...46...

Страница 47: ...47...

Страница 48: ...48 ul Wsp lna 19 Ignatki 16 001 Kleosin Poland plum plum pl www plum pl National Waste Disposal No 000009381...

Отзывы: