2.1.4 Wiring the Fault Alarm Contact
The fault alarm contacts are in the middle of the terminal block connector as the picture shows below.
Inserting the wires, the Industrial 802.11ax Wireless AP will detect the fault status of the power failure or
port failure, and then will form an open circuit. The following illustration shows an application example
for wiring the fault alarm contacts.
1
2
3
4
5
6
1.
The wire gauge for the terminal block should be in the range between 12 and
24 AWG.
2.
Alarm relay circuit accepts up to 24V, max. 1A currents.
Insert the wires into the fault alarm contacts