14
- PLE500 -
User manual
Value of digital outputs in error Q 0 block
Value of digital outputs in error Q 1 block
These two variables let you set the status of each individual digital output in case of
communication error. Each bit corresponds to one of the digital outputs. By setting the bit to 1, in
case of communication error, the output will be activated if the corresponding bit in the variable
“Mask of status for digital outputs in error Q 0..1 block” is set to 1. By setting the bit to 0, in case
of communication error, the output will be deactivated if the corresponding bit in the variable
“Mask of status for digital outputs in error Q 0..1 block” is set to 1. If the bit in the variable “Mask
of status for digital outputs in error Q 0..1 block” is set to 0, the bit value of this variable will have
no impact.
Default
: 0x00.
AQ.0 analog output in error mode
AQ.1 analog output in error mode
These two variables let you set the operating mode of each individual analog output in case of
communication error.
0
The output maintains its current value (
Default
)
1
The output assumes the value indicated by the variable “Analog output in error value“
(
Default
).
AQ.0 analog output in error value
AQ.1 analog output in error value
These two variables let you set the value of each individual analog output in case of communication
error.
Default
: 0x00.