- PLE500 -
User manual
5.1.g
Digital outputs
QI.0 QI.7
QI.7
QI.0
17 24 -
..
5 12
..
12..24 VDC ± 15% digital output (based on the power supply of the
outputs)/ 700mA (Max 3A in total)
5.1.h
Example of incremental encoder connection
ENC2
7
ENC3
9
ENC4
11
A
B
Z
+
- SUPPLY
ENC1
5
8 10 12
6
18 19 20
17
ENC
ODER
Use push-pull encoders
Max. frequency 80KHz
5.1.i
Example of mono-directional counter connection
CNT2
7
CNT3
9
CNT4
11
+
- SUPPLY
CNT1
5
PNP type input (VIH = 8.0 V).
Max. frequency 80KHz
5.2
Meaning of status lights (LED)
RUN
• Slow flashing of 40msec every 1.2sec: during the program start
phase.
• Fixed on: normal operation of the module with PLC in run.
• Fast 50 ms flashing: it indicates that an anomaly was found during
the network node numbering procedure.
I/O
• It indicates that the corresponding input or output are active (high
logic level)
6
Configuration parameter table
1
AI.0 type sensor
2
AI.1 type sensor
Sensor selection / analog input configuration
0
0-10 V
1
4-20 mA
2
0-20 mA
3
AI.0 input lower limit
4
AI.1 input lower limit
Analog input lower limit for normalized signals. E.g.: with input 4..20 mA V this parameter assumes
the value associated to 4 mA
-32767..+32767,
Default
: 0.
5
AI.0 input upper limit
6
AI.1 input upper limit
Analog input upper limit for normalized signals. E.g.: with input 4..20 mA V this parameter assumes
the value associated to 20 mA
-32767..+32767.
Default
:1000
7
Linear input beyond limits AI.0
8
Linear input beyond limits AI.1
In case of linear input it allows the process to exceed the minimum and maximum numeric limits
set in parameters 3, 4, 5 and 6.
0
Disabled (
Default
)
1 Enabled