40 - DRR245 -
User manual
33
A2.re.
Alarm 2 Reset
Alarm 2 contact reset type
Are.
Automatic reset (
Default
)
mre.
Manual reset (reset / manual reset by keyboard)
|
mre.s.
Manual reset stored. (keeps relay status also after an eventual
power failure)
34
a.2.s.e.
Alarm 2 State Error
State of contact for alarm 2 output in case of error
c.o.
Open contact (
Default
)
c.c.
Closed contact
35
a.2.Ld.
Alarm 2 Led
State of OUT2 led corresponding to relative contact
c.o.
ON with open contact
c.c.
ON with closed contact (
Default
)
36
a.2.HY.
Alarm 2 Hysteresis
-999..+999 [digit
] (degrees.tenths for temperature sensors),
Default
: 0.0.
37
a.2.d.e.
Alarm 2 Delay
-180..+180 seconds.
Negative
: delay in alarm exit phase.
Positive
: delay in alarm entry phase.
Default
: 0.
38
a.2.s.p.
Alarm 2 Setpoint Protection
Alarm 2 set protection. Does not allow operator to change value set
free
Modification allowed (
Default
)
Lock
Protected
Hide
Protected and not visualized
47
t.a.
Current Transformer
Activation and scale range of current transformer
0 Disabled.
1-200 Ampere.
Default
: 0