background image

D900-03-00

3

I56-380-05

C. Semiflush Mount

1. Speaker Only (Figure 4)

(a) System Sensor semiflush mounting plates are

shipped with #8 nuts already installed from the
back.

(b) Route wiring through the opening in the semiflush

mounting plate opening and attach the plate to a
standard 4-inch square electrical box at diagonally
opposite corners, using the two 8-32 X 

5

/

8

 slotted

screws, provided.

(c) Wire the speaker/strobe as described in Electrical

and mount it on the plate using two 8-32 X 1

7

/

16

"

slotted screws in diagonally opposite corners.
Thread a #8 sheet metal screw into each of the two
remaining holes in the speaker/strobe.

2. Speaker with Strobe (Figure 5)

Attach the mounting plate to the electrical box as de-
scribed in paragraph C.1 before wiring the speaker/
strobe assembly as described in paragraph B.2.

D. Flush Mount

Flush mounting requires the use of a System Sensor BBD
deep box, or equivalent.
1. Speaker Only (Figure 6)

(a) Identify the two diagonally opposite speaker holes

that will be needed for mounting the speaker on the
electrical box.

(b) Use two 8-32 X 1

5

/

16

" phillips head screws and

square nuts through the holes not used for mount-
ing to attach the flush plate to the speaker.

(c) Wire the speaker as described in Electrical and

mount the speaker/plate assembly in the electrical
box using two 8-32 X 2

3

/

4

" screws.

2. Speaker with Strobe (Figure 7)

(a) Use a small bladed screwdriver to remove the plastic

flash from the two strobe blade slots on the speaker
and flush mount plate.

(b) See Figure 3. Identify the two diagonally opposite

speaker holes that will be needed for mounting the
speaker on the electrical box. The other two holes
will be used to attach the strobe to the speaker.

(c) Position the strobe over the speaker and guide its

two power lugs into the slots formed when the flash
was removed in step 2(a). Attach the strobe to the
speaker using the #8 phillips head sheet metal
screws through the pair of strobe mounting holes
that was selected in step 2(b).

(e) Slide the right angle connector on the red wire on to

the strobe power lug nearest the “F” in “FIRE”.
Similarly, connect the right angle connector on the
black wire to the remaining lug on the opposite side
of the speaker.

(f)

Connect the free end of the red wire to the STROBE
+ terminal (1) and black wire to STROBE - (5).
Then, connect a source of uncoded (continuous) 12

V400

#8

NUTS

MP-SF

8-32x5/8

8-32x5/8

#8 S.M.

#8 S.M.

8-32X1-7/16

8-32X1-7/16

Figure 4. SemiFlush Mount:

A78-1795-01

8-32x1-5/16

8-32x2-3/4

8-32x2-3/4

8-32x1-5/16

MP-F

V400

#8

NUT

#8 NUT

BB-D

A78-1797-00

Figure 5. Speaker, Strobe Semiflush Mount:

Figure 6. Speaker Flush Mount:

A78-1796-03

V400

8-32x1-7/16

#8 Sht. Mtl.

Signal Strobe

8-32x1-7/16

#8 Sht. Mtl.

#8

NUTS

MP-SF

8-32x5/8

8-32x5/8