B501B Plug-in Detector Base

For use with UL Listed detectors:
1551, 2551, 2551T, and 5551

INSTALLATION AND MAINTENANCE INSTRUCTIONS

A Division of Pittway

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

Before Installing

Please thoroughly read the system wiring and installation
manual, and manual I56-407, 

Guide for Proper Use of Sys-

tem Smoke Detectors

, which provides detailed information

on detector spacing, placement, zoning,  and special appli-
cations. Copies of these manuals are available from System
Sensor or through a System Sensor distributor. (For installa-
tion in Canada, refer to CAN/ULC-S22524-M86, Standard
for the Installation of Fire Alarm Systems and CEC part 1,
Section 32.)

General Description

This plug-in detector base is used with System Sensor
model 1551 ionization, 2551 and 2551T photoelectronic,
and 5551 thermal detectors.

The B501B base is intended for use in a 2-wire intelligent
system, with screw terminals provided for power (+) and
(-), and remote annunciator connections. Communication
takes place over the power (+) and (-) lines. (See note on
page 4).

Specifications

Diameter:

6.1 inches (15.5 cm)

Mounting:

4 inch square box with or without plaster ring; Min. Depth: 1.5 inches.
4 inch Octagon Box; Min. Depth: 1.5 inches.
3-1/2 inch Octagon Box; Min. Depth: 1.5 inches.
Single Gang Box; Min. Depth: 1.5 inches.

Electrical Ratings

Voltage Range:

14.5 to 28 VDC peak

Standby Current (nominal):

150 

µ

A at 24 VDC

Power-up Surge at Maximum
Rated Voltage:

1.5 mA-second

LED Current (nominal):

6 mA at 24 VDC

Base Terminals

NO.

FUNCTION

1

POWER (-), REMOTE ANNUNCIATOR (-)

2

POWER (+)

3

REMOTE ANNUNCIATOR (+)

Figure 1. Terminal Layout

A78-1318-00

3

2

1

BASE
TERMINALS

TAMPER PROOF

TAB

Содержание SYSTEM SENSOR B501B

Страница 1: ...cription This plug in detector base is used with System Sensor model 1551 ionization 2551 and 2551T photoelectronic and 5551 thermal detectors The B501B base is intended for use in a 2 wire intelligent system with screw terminals provided for power and and remote annunciator connections Communication takes place over the power and lines See note on page 4 Specifications Diameter 6 1 inches 15 5 cm...

Страница 2: ...onnected de tectors or modules it is recommended that the wire be no smaller than 18 gauge 1 0 square mm Wire sizes up to 12 gauge wire 2 5 square mm may be used with the base For best system performance the power and power loop wires should be twisted pair installed in sepa rate grounded conduit to protect the loop from extrane ous electrical interference Wire connections are made by stripping ab...

Страница 3: ...NCIATOR CAUTION Do not loop wire under terminal 1 or 2 Break wire run to provide supervision of connections Figure 3 Typical wiring diagram for 2 wire loop A78 1253 00 PLASTIC LEVER BREAK TAB AT DOTTED LINE BY TWISTING TOWARD CENTER OF BASE USE SMALL BLADED SCREWDRIVER TO PUSH PLASTIC LEVER IN DIRECTION OF ARROW Figure 4A Activating tamper proof feature Figure 4B Removing detector head from base A...

Страница 4: ...n chimneys in walls on roofs or on the other side of a closed door s may not reach the smoke detector and alarm it A detector cannot detect a fire developing on another level of a building quickly or at all For these reasons detectors shall be located on every level and in every bedroom within a building Smoke detectors have sensing limitations too Ionization detectors and photoelectric detectors ...

Отзывы: