INTRODUCTION
The S300PTU Programming and Test Tool is designed for communication with
System Sensor 300 Series sensors (and variants) permitting access to various
functions and logs within the sensors.
Communication is achieved through the sensor’s indicator LED at close range
- approximately 30mm.
The S300PTU is a menu driven device. With reference to
Figure 1
, the controls
for navigating through the menus are as follows:
(1)
On/O
ff
Switch
(2)
Up/Down Arrows - to scroll through menus
(3)
OK
button - Select required function
(4)
Esc
- Returns to the previous menu
Numbers 5-8 refer to battery replacement (see later
Section 7
)
POWER ON
S300PTU
PROGRAMMING & TEST TOOL: USER GUIDE
E N G L I S H
I 56- 1720- 011
1: S300PTU SET UP
Prior to any communications with detectors, it is necessary to con
fi
gure the
S300PTU. This procedure should only need to be carried out once, the settings
then being retained until changed via this screen.
During the set-up procedure, ensure that only one S300PTU is switched on
within a 10m area.
Switch on the S300 PTU. Scroll down through the main menu screens to select
PTU Settings
. This gives access to set-up screens as follows:
2: ACQUIRE DETECTOR SETTINGS and LAST DETECTOR READ
Except where indicated, the same operating screens apply to both acquisition of
the detector settings and the display of information from the last detector read:
Figure 1:
S300PTU Front Panel
Figure 2: Batteries
3 x 1.5V LR03 (AAA)
Batteries Required
When the S300PTU is turned on, the screen shown left will
be displayed for approximately 5 seconds, and then will be
replaced by the
fi
rst of the main menu screens.
MAIN MENU
There are six main menu items, Use the arrow keys to move between them as
follows:
Reads the settings previously programmed into the detector
being accessed including sensitivity, address, device type,
LED operation and service date. Refer to
Section 2
.
Displays the information acquired from the last detector
read. Refer to
Section 2
.
Programs new settings such as address, sensitivity and
mode of LED operation into the detector. Refer to
Section 3
.
Checks that maintenance has been satisfactory, and if OK
programs the current date into the detector as the new
service date. Refer to
Section 4
Performs a detector Alarm Test. Refer to
Section 5
.
Allows the user to set the S300PTU tool to suit
requirements, including the tool operating language and
LCD Intensity. Refer to
Section 1
.
ACQUIRE
1
Detector
Settings
Last
2
Detector
Read
Write
3
Detector
Settings
Write
4
NEW
Service Date
Alarm
5
Test
Press OK x 2
PTU
6
Settings
Series 300
PTU - v.1.7
*** READY ***
PTU
6
Settings
LCD
6.1
Intensity
PTU
6.2
Set LINK
mode
Read
6.3
Current
Date
Set
Link
6.5
--------------
Set
6.4
PTU
Language
Current Date
dd/mm/yy
----------
OK
Language
Set
:
to
English
*** Ready ***
1234567
OK
OK
OK
OK
OK
NOT USED ON THIS VERSION
NOT USED ON THIS VERSION
OK
Esc
Use the up/down arrow
buttons to adjust screen
intensity to suit, then
press
OK
to con
fi
rm
setting
Date is displayed as:
Day/Month/Year
(Based on GMT)
Press
OK
to con
fi
rm
Use the up/down
arrows to display the
required language for
the S300PTU, and then
press
OK
to con
fi
rm
setting
Detector Data
Corrupted
Return detector
to supplier for
reprogramming
(in warranty
only)
Information
Missing
Detector
incompatible
with S300PTU
Displays Detector Type Code:
A
= Conventional EN54 Standard
B
= Conventional NF (AFNOR)
C
= Special
Displays Detector Type:
Therma
l,
Optical
or
Opto-Thermal
Displays Detector Address
(00 to 99)
Note:
1.
Last Detector Read
info is only displayed if a
successful
Aquire Detector Settings
has previously been run.
2. When the S300PTU is
switched o
ff
, the
Last
Detector Read
data
is lost.
displayed for Optical
Service Information
screens only
and Opto-Thermal
detectors
The S300PTU will automatically display the relevant screen. In normal
conditions with no smoke present, the
% Dirty screen
will be displayed,
giving an indication of the level of contamination in the detector
chamber. If the detector has reached it’s drift compensation limit and
needs cleaning the
Sensor Contaminated
screen will be shown, and if
faulty the
Chamber Faulty
screen will be shown.
Displays the current Chamber / Sensor values. For an optical
or thermal detector, the optical or thermal sensor reading only
will be displayed as applicable. For opto-thermal detectors both
readings will be shown.
Continued
overleaf