 Installation Guide                                                                                                                                                                   55

In Atia External, the numbers continue as following:

In Atia External, zones/users higher than 97 are represented as space character (32 in Ascii as decimal).

*  Alarm/Reset wildcard number means, that there is no difference in converting the values 1 or 3.

**  1 = E, 3 = R (CID, depending on the RS-232 protocol)

SIA

(Currently, event conversion is not available)

Zone\User

Order

62-69

48, 49, 50, 51, 52, 53, 54, 55, 56, 57

70-79

97, 98, 99, 100, 101, 102, 103, 104, 105, 106

80-89

107, 108, 109, 110, 111, 112, 113, 114, 115, 116

90-96

117, 118, 119, 120, 121, 122, 65, 66, 67, 68

Data Code Short Description 

Long Description 

Address Field 

AA

Alarm – Panel 
Substitution 

An attempt to substitute an alternate alarm panel for a secure 
panel has been made 

Condition number 

AB

Abort 

An event message was not sent due to User action 

Zone or point 

AN

Analog Restoral 

An analog fire sensor has been restored to normal operation 

Zone or point 

AR

AC Restoral 

AC power has been restored 

Unused 

AS

Analog Service 

An analog fire sensor needs to be cleaned or calibrated 

Zone or point 

AT

AC Trouble 

AC power has been failed 

Unused 

BA

Burglary Alarm 

Burglary zone has been violated while armed 

Zone or point 

BB

Burglary Bypass 

Burglary zone has been bypassed 

Zone or point 

BC

Burglary Cancel 

Alarm has been cancelled by authorized user 

User number 

BD

Swinger Trouble 

A non-fire zone has been violated after a Swinger Shutdown on 
the zone 

Zone or point 

BE

Swinger Trouble 
Restore 

A non-fire zone restores to normal from a Swinger Trouble state 

Zone or point 

BG

Unverified Event - 
Burglary 

A point assigned to a Cross Point group has gone into alarm but 
the Cross Point remained normal 

Zone or point 

BH

Burglary Alarm 
Restore 

Alarm condition eliminated 

Zone or point 

BJ

Burglary Trouble 
Restore 

Trouble condition eliminated 

Zone or point 

BM

Burglary Alarm - 
Cross Point 

Burglary alarm w/cross point also in alarm - alarm verified 

Zone or point 

BR

Burglary Restoral 

Alarm/trouble condition has been eliminated 

Zone or point 

BS

Burglary Supervisory  Unsafe intrusion detection system condition 

Zone or point 

BT

Burglary Trouble 

Burglary zone disabled by fault 

Zone or point 

BU

Burglary Unbypass 

Zone bypass has been removed 

Zone or point 

BV

Burglary Verified 

A burglary alarm has occurred and been verified within 
programmed conditions. (zone or point not sent) 

Area number 

BX

Burglary Test 

Burglary zone activated during testing 

Zone or point 

BZ

Missing Supervision 

A non-fire Supervisory point has gone missing 

Zone or point 

CA

Automatic Closing 

System armed automatically 

Area number 

CD

Closing Delinquent 

The system has not been armed for a programmed amount of 
time 

Area number 

CE

Closing Extend 

Extend closing time 

User number 

CF

Forced Closing 

System armed, some zones not ready 

User number 

CG

Close Area 

System has been partially armed 

Area number 

CI

Fail to Close 

An area has not been armed at the end of the closing window 

Area number 

CJ

Late Close 

An area was armed after the closing window 

User number 

CK

Early Close 

An area was armed before the closing window 

User number 

CL

Closing Report 

System armed, normal 

User number 

CM

Missing Alarm- 
Recent Closing 

A point has gone missing within 2 minutes of closing 

Zone or point 

CO

Command Sent 

A command has been sent to an expansion/peripheral device 

Condition number 

CP

Automatic Closing 

System armed automatically 

User number 

CQ

Remote Closing 

The system was armed from a remote location 

User number 

CR

Recent Closing 

An alarm occurred within five minutes after the system was 
closed 

User number 

CS

Closing Keyswitch 

Account has been armed by keyswitch 

Zone or point 

CT

Late to Open 

System was not disarmed on time 

Area number 

CW

Was Force Armed 

Header for a force armed session, forced point msgs may follow 

Area number 

CX

Custom Function 
Executed 

The panel has executed a preprogrammed set of instructions 

Custom Function 
number 

CZ

Point Closing 

A point, as opposed to a whole area or account, has closed 

Zone or point 

DA

Card Assigned 

An access ID has been added to the controller 

User number 

DB

Card Deleted 

An access ID has been deleted from the controller 

User number 

DC

Access Closed 

Access to all users prohibited 

Door number 

DD

Access Denied 

Access denied, unknown code 

Door number 

DE

Request to Enter 

An access point was opened via a Request to Enter device 

Door number 

DF

Door Forced 

Door opened without access request 

Door number 

DG

Access Granted 

Door access granted 

Door number 

DH

Door Left Open - 
Restoral 

An access point in a Door Left Open state has restored 

Door number 

Содержание PIMAGUARD

Страница 1: ...SENTINEL Receiver Decoder PCI Card PIMAGUARD Configuration Application Installation and Operating Guide PIMA Electronic Systems Ltd www pima alarms com P N 4410051 F1 XX en Feb 2011...

Страница 2: ...2 Sentinel PimaGuard Installation Guide...

Страница 3: ...unication formats 14 Creating a new format 14 Programming 16 Sentinel 1 16 Sentinel configuration 16 Line 1 configuration 16 Radio 1 18 Communication 18 Type 19 Mode 19 On error switch to 19 Examples...

Страница 4: ...29 Legend 29 Source options examples 30 Structured Formats 30 Appendix E Events Conversion Table 36 NPAF EPAF 40 ELL6 49 CID PID 50 SIA 55 Appendix F Programming Line Radio Formats 60 Line Formats 60...

Страница 5: ...for each channel PAF CID SIA KP DESK ELL and more Automatic testing of the card and the input channel Failures and status are reported to the Central Monitoring Station management application Up to 4...

Страница 6: ...inel package contains the following The Sentinel Card The PimaGuard driver installation CD A radio connection cable P N 3411055 4 RJ 11 standard telephone cords P N 3411046 Cross link 9 pin D type ser...

Страница 7: ...ntinel insert the others too max 4 cards 4 Close the PC case plug it and turn it on Installing several Sentinels When you install several Sentinels up to 4 the procedure is as folllows 1 Insert the ca...

Страница 8: ...reception signal is not interrupted by the squelch filter PIMAGUARD INSTALLATION Under Windows XP After installing the Sentinel when Windows boots up the Add New Hardware Wizard should start running a...

Страница 9: ...stall from a list or specific location and click Next 4 Select Don t search I will choose the driver to install and click Next 5 Press Have Disk If the PimaGuard was previously intalled on the PC disr...

Страница 10: ...e desktop right click the My Computer icon and select Manage In the window that pops up click Device Manager on the left pane 2 Right click the first Network Controller and select Update Driver Softwa...

Страница 11: ...k Install this driver software anyway 10 Wait for the installation to end with the message Windows has successfully updated your driver software and click Close When Working under Windows 7 the UAC Us...

Страница 12: ...t levels of the menu and for all parameters and text fields Copy Paste Clear Formats filters ACKs and other parameters can be copied by using the Copy command on the main menu Pasting the copied infor...

Страница 13: ...count 8000 in most cases This PimaGuard self account fault event is sent to the Central Monitoring Station via all the modules each in its own protocol If you don t set any event the PimaGuard will no...

Страница 14: ...30 Burglary can be converted to Hex 2 digits and be sent as 82 The full event conversion table is in Appendix E page 36 A legend of the characters of the Formats page is located on page 29 Creating a...

Страница 15: ...s example CID PID events will be converted to Hex 2 Digit format see the conversion table on page 40 If for example event 130 Burglary is received it will be converted to 82 The first E in the Contact...

Страница 16: ...nterval and only if the 3 fail a report will be generated See Appendix C page 28 6 Click OK The pop up window is shut down and the Line settings are displayed in the PimaGuard window 7 On the right pa...

Страница 17: ...ter P will be displayed with its value Else the structured format will be displayed as followed S System F Flag E Extra Other information will follow Filters Add to Account Structure PLS and DTMF only...

Страница 18: ...in milliseconds to enable the full charging of the transmitter after pushing PTT before transmitting a report Empty 180 ms min 80 max 640 5 Press OK Radio format The Radio format window is the same a...

Страница 19: ...DOS Compatible mode it supports all format types See the repeaters on page page 25 On error switch to Select the communication channel to which the output transmissions will be switched when an error...

Страница 20: ...nt is not within the filter s range except for time filters This is to enable the external decoder to keep running in anyway Idle timeout 7 Set the Idle timeout in seconds To view ACK Idle patterns se...

Страница 21: ...ral debug To switch between the two double click the Mode line in the right pane The Debug mode can be operated only with a Sentinel card installed Figure 17 The monitor window General In this mode th...

Страница 22: ...s Yellow Warning some features will not work properly Potential loss of data Red Error some features will not work at all or not work properly Potential loss of data Oscillograph This mode enables you...

Страница 23: ...is displayed in this window 5 Press browse and locate the upgrade file Press Open 6 Press Program than Start If the upgrade version is the same as the PimaGuard s one a warning message will be display...

Страница 24: ...ht pane 9 Select the incoming transmission s format from the drop down list From the list PAF NPAF EPAF DESK are Radio and PSTN formats PID SIA CID are supported if a non dos compatible PID repeater t...

Страница 25: ...be received by the PimaGuard and what will not The filters are Account Event Date Days Time Format and Channel The Filters window appears the same in every channel and module but is set separately fo...

Страница 26: ...tells the PimaGuard to receive transmissions only from Comm 2 After that the PimaGuard reads the content of the file under the list limit no and compares it to the transmission s content only matching...

Страница 27: ...ainst wetness 4 The antenna cable should not run in parallel to any electric wires to avoid RF interferences If this is unavoidable the cable should run at least 1 meter away from the electric wires 5...

Страница 28: ...e 26 Comm 6 Fail A6 Comm 6 Restore 27 Comm 7 Fail A7 Comm 7 Restore 28 Comm 8 Fail A8 Comm 8 Restore 29 Log 1 Fail A9 Log 1 Restore 2A Log 2 Fail AA Log 2 Restore 2B Log 3 Fail AB Log 3 Restore 2C Log...

Страница 29: ...peater Channel Line Radio COMM Decoder ID is taken from the user definitions of the input format decimal 0 default Source options every 2 characters represent a condition and its value to be placed in...

Страница 30: ...ut from Radio A 4 digit account decimal E 2 digit event Atia 13 Expanded Frame Structure R1L3 AAAA EE 0A 0D 3 Input from Line or other 1 Input from Radio A 4 digit account decimal E 2 digit event In C...

Страница 31: ...the output is External the 4x2 protocol is the default one If required use FBI External FBI PAF CID Frame Structure AAAAEE 0D applicable to SIA 4x2 Frame Structure 0A AAAA 18 QEEE PP ZZZ 0D Applicabl...

Страница 32: ...Configuration See Configuration on page 13 FBI DESK Frame Structure AAAAEE 0D Applicable to PAF NPAF EPAF SIA 4x2 Incoming Sentinel Communication Repeater channel number A 4 digit account decimal E 2...

Страница 33: ...SURGARD PAF HEX Frame Structure 10 AAAA EE 14 Applicable to PAF NPAF EPAF 4x2 Frame Structure 50 18AAAAQEEE ZZZ 14 Applicable to CID PID Frame Structure 30 AAAAEE ZZZ 14 Applicable to SIA The structu...

Страница 34: ...ecimal E 2 digit event CC CRC Frame Structure 0A SSSSSSSSSSSSSSSSSSS AAAAAAEEK______CC 0D Applicable to NPAF EPAF PAF SSSSSSSSSSSSSSSSSSS A 6 digit account decimal E 2 digit event K Multiple Condition...

Страница 35: ...count decimal Note that it is 0A AAAA and not 5 digit account number E 2 digit event Hexadecimal 4x2 only COMPUCHER Frame Structure 0A SSSSSSSSSSSSSSSSSSS AAAAAAEE_______CC 0D Applicable to 4x2 SSSSSS...

Страница 36: ...event E 3 digit event P 2 digit Partition decimal S Ademco 685 Special U User Event C Contact Event Z 3 digit Zone User decimal APPENDIX E EVENTS CONVERSION TABLE This appendix lists build in formats...

Страница 37: ...1 7 A 16 Alarm zone 42 LD 20 130 1 42 7 A 16 Alarm zone 43 LE 20 130 1 43 B A 16 Alarm zone 44 LF 20 130 1 44 F A 16 Alarm zone 45 LG 20 130 1 45 A A 16 Alarm zone 46 LH 20 130 1 46 8 A 16 Alarm zone...

Страница 38: ...14 8 O Disarming User 15 NY BD 401 1 15 8 O Disarming User 16 NZ BD 401 1 16 8 O Disarming User 17 OA BD 401 1 17 8 O Disarming User 18 OB BD 401 1 18 8 O Disarming User 19 OC BD 401 1 19 8 O Disarmi...

Страница 39: ...1 3 11 A C Home User 12 QX A5 401 3 12 A C Arming Auto QY EF 403 3 0 A C Disarming Auto QZ F0 403 1 0 A C Home Auto RA EF 403 3 0 A C Arming Switch RB 97 409 3 0 A C Disarming Switch RC C1 409 1 0 A C...

Страница 40: ...30 1 1 B A 1 Alarm Zone 2 AB 01 130 1 2 4 A 2 Alarm Zone 3 AC 02 130 1 3 9 A 3 Alarm Zone 4 AD 03 130 1 4 9 A 4 Alarm Zone 5 AE 04 130 1 5 E A 5 Alarm Zone 6 AF 05 130 1 6 6 A 6 Alarm Zone 7 AG 06 130...

Страница 41: ...80 DB 20 130 1 80 0 A 16 Alarm Zone 81 DC 20 130 1 81 0 A 16 Alarm Zone 82 DD 20 130 1 82 0 A 16 Alarm Zone 83 DE 20 130 1 83 0 A 16 Alarm Zone 84 DF 20 130 1 84 0 A 16 Alarm Zone 85 DG 20 130 1 85 0...

Страница 42: ...0 R 16 Zone Reset 71 GK 41 130 3 71 0 R 16 Zone Reset 72 GL 41 130 3 72 0 R 16 Zone Reset 73 GM 41 130 3 73 0 R 16 Zone Reset 74 GN 41 130 3 74 0 R 16 Zone Reset 75 GO 41 130 3 75 0 R 16 Zone Reset 76...

Страница 43: ...JR 62 380 1 60 0 T 16 Zone Failure 61 JS 62 380 1 61 0 T 16 Zone Failure 62 JT 62 380 1 62 0 T 16 Zone Failure 63 JU 62 380 1 63 0 T 16 Zone Failure 64 JV 62 380 1 64 0 T 16 Zone Failure 65 JW 62 380...

Страница 44: ...50 0 X 25 Zone Bypass 51 NA 83 570 1 51 0 X 25 Zone Bypass 52 NB 83 570 1 52 0 X 25 Zone Bypass 53 NC 83 570 1 53 0 X 25 Zone Bypass 54 ND 83 570 1 54 0 X 25 Zone Bypass 55 NE 83 570 1 55 4 X 25 Zone...

Страница 45: ...r 16 QJ A8 401 3 16 A C Home User 17 QK A8 401 3 17 A C Home User 18 QL A8 401 3 18 A C Home User 19 QM A8 401 3 19 A C Home User 20 QN A8 401 3 20 A C Home Short Code QO A9 408 3 0 A X 25 Home Tempor...

Страница 46: ...F5 616 1 0 z X 25 Tamper 2 Alarm TP C5 137 1 0 z X 25 Tamper 2 Restore TQ C6 137 3 0 z X 25 Listen In To Follow TR FF 606 1 0 z X 25 TS TS FF 616 1 0 z X 25 TT TT FF 616 1 0 z X 25 TU TU FF 616 1 0 z...

Страница 47: ...WY FF 616 1 0 z X 25 Spare WZ FF 616 1 0 z X 25 Disarming User 21 YA BD 401 1 21 8 C Disarming User 22 YB BD 401 1 22 8 C Disarming User 23 YC BD 401 1 23 8 C Disarming User 24 YD BD 401 1 24 8 C Dis...

Страница 48: ...1 9 z X 25 Zone Expander Fault 10 33 FE 333 1 10 z X 25 Zone Expander Fault 11 34 FE 333 1 11 z X 25 Zone Expander Fault 12 35 FE 333 1 12 z X 25 Zone Expander Fault 13 36 FE 333 1 13 z X 25 Zone Expa...

Страница 49: ...4 14 AE ALARM ZONE 15 53 53 3 A 15 15 15 AF ALARM ZONE 16 EE EE E A 16 16 16 AG RESTORAL ZONE 1 77 77 7 R 1 17 17 R1 RESTORAL ZONE 2 35 35 5 R 2 18 18 R2 RESTORAL ZONE 3 50 50 0 R 3 19 19 R3 RESTORAL...

Страница 50: ...E F F Pull Station 115 3 73 3 C E G G Duct 116 3 74 4 C E H H Flame 117 3 75 5 C E D D Near Alarm 118 3 76 6 C E I I Panic 120 3 78 8 C E J J Duress 121 3 79 9 C E K K Silent 122 3 7A A C E J J Audibl...

Страница 51: ...ilure 307 1 0 33 3 C E 1b 1b System shutdown 308 1 0 34 4 C E 1c 1c Battery test failure 309 1 0 35 5 C E 1d 1d Ground fault 310 1 0 36 6 C E 1e 1e Battery Missing Dead 311 1 0 37 7 C E 1f 1f Power Su...

Страница 52: ...2 2 C E 2A 2A Protection loop open 371 3 0 73 3 C E 2B 2B Protection loop short 372 3 0 74 4 C E 2C 2C Fire trouble 373 3 0 75 5 C E 2D 2D Exit error alarm zone 374 1 76 6 C E s s Exit error alarm zon...

Страница 53: ...CD D C E 3F 3F Legal Code Entry 462 3 0 CE E C E 3G 3G Re arm after Alarm 463 3 0 CF F C E 3H 3H Auto arm Time Extended 464 3 0 D0 0 C E 3I 3I Panic Alarm Reset 465 3 0 D1 1 C E 3J 3J Service On Off...

Страница 54: ...5 5 C E 00 00 Fire Zone Walk Tested Zone Digital Comm 614 0 66 6 C E 00 00 Panic Zone Walk Tested 615 0 67 7 C E 00 00 Service Request 616 0 68 8 C E 00 00 Event Log reset 621 1 0 6D D C E 4d 4d Event...

Страница 55: ...pass Zone bypass has been removed Zone or point BV Burglary Verified A burglary alarm has occurred and been verified within programmed conditions zone or point not sent Area number BX Burglary Test Bu...

Страница 56: ...trouble eliminated Expander number ES Expansion Device Tamper Expansion device enclosure tamper Expansion device number ET Expansion Trouble Expansion device trouble Expander number EX External Devic...

Страница 57: ...Zone or point KJ Heat Trouble Restore Trouble condition eliminated Zone or point KR Heat Restoral Alarm trouble condition has been eliminated Zone or point KS Heat Supervisory Unsafe heat detection s...

Страница 58: ...point QU Emergency Unbypass Bypass has been removed Zone or point RA Remote Programmer Call Failed Transmitter failed to communicate with the remote programmer Unused RB Remote Program Begin Remote p...

Страница 59: ...rouble condition has been eliminated Zone or point WS Water Supervisory Water unsafe water detection system condition Zone or point WT Water Trouble Water zone disabled by fault Zone or point WU Water...

Страница 60: ...problem with the power supply Unused YQ Power Supply Restored TRANSMITTER S RECEIVER S power supply has been restored Unused YR System Battery Restoral Low battery has been corrected Unused YS Communi...

Страница 61: ...el PimaGuard Installation Guide 61 bit6 bit25 INTRAC2000 bit11 MILCOLD DESK mask bit7 spare mask Repeater Formats The supported are PAF NPAF EPAF and all 4x2 compatibles Format Source format Flags Ext...

Страница 62: ...to take all necessary precautions for his her safety and the protection of his her property This document may not be duplicated circulated altered modified translated reduced to any form or otherwise...

Отзывы: