58
Sentinel & PimaGuard
Installation Guide
OH
Early to Open from
Alarm
An area in alarm was disarmed before the opening window
User number
OI
Fail to Open
An area has not been armed at the end of the opening window
Area number
OJ
Late Open
An area was disarmed after the opening window
User number
OK
Early Open
An area was disarmed before the opening window
User number
OL
Late to Open from
Alarm
An area in alarm was disarmed after the opening window
User number
OP
Opening Report
Account was disarmed
User number
OQ
Remote Opening
The system was disarmed from a remote location
User number
OR
Disarm From Alarm
Account in alarm was reset/disarmed
User number
OS
Opening Keyswitch
Account has been disarmed by keyswitch
Zone or point
OT
Late To Close
System was not armed on time
User number
OU
Output State –
Trouble
An output on a peripheral device or NAC is not functioning
Output number
OV
Output State –
Restore
An output on a peripheral device or NAC is back to normal
operation
Output number
OZ
Point Opening
A point, rather than a full area or account, disarmed
Zone or point
PA
Panic Alarm
Emergency assistance request, manually activated
Zone or point
PB
Panic Bypass
Panic zone has been bypassed
Zone or point
PH
Panic Alarm Restore Alarm condition eliminated
Zone or point
PJ
Panic Trouble
Restore
Trouble condition eliminated
Zone or point
PR
Panic Restoral
Alarm/trouble condition has been eliminated
Zone or point
PS
Panic Supervisory
Unsafe system condition exists
Zone or point
PT
Panic Trouble
Zone disabled by fault
Zone or point
PU
Panic Unbypass
Panic zone bypass has been removed
Zone or point
QA
Emergency Alarm
Emergency assistance request
Zone or point
QB
Emergency Bypass
Zone has been bypassed
Zone or point
QH
Emergency Alarm
Restore
Alarm condition has been eliminated
Zone or point
QJ
Emergency Trouble
Restore
Trouble condition has been eliminated
Zone or point
QR
Emergency Restoral Alarm/trouble condition has been eliminated
Zone or point
QS
Emergency
Supervisory
Unsafe system condition exists
Zone or point
QT
Emergency Trouble
Zone disabled by fault
Zone or point
QU
Emergency
Unbypass
Bypass has been removed
Zone or point
RA
Remote Programmer
Call Failed
Transmitter failed to communicate with the remote programmer
Unused
RB
Remote Program
Begin
Remote programming session initiated
Unused
RC
Relay Close
A relay has energized
Relay number
RD
Remote Program
Denied
Access passcode incorrect
Unused
RN
Remote Reset
A TRANSMITTER was reset via a remote programmer
Unused
RO
Relay Open
A relay has de-energized
Relay number
RP
Automatic Test
Automatic communication test report
Unused
RR
Power Up
System lost power, is now restored
Unused
RS
Remote Program
Success
Remote programming successful
Unused
RT
Data Lost
Dialer data lost, transmission error
Line number
RU
Remote Program Fail Remote programming unsuccessful
Unused
RX
Manual Test
Manual communication test report
User number
RY
Test Off Normal
Test signal(s) indicates abnormal condition(s) exist
Zone or point
SA
Sprinkler Alarm
Sprinkler flow condition exists
Zone or point
SB
Sprinkler Bypass
Sprinkler zone has been bypassed
Zone or point
SC
Change of State
An expansion/peripheral device is reporting a new condition or
state change
Condition number
SH
Sprinkler Alarm
Restore
Alarm condition eliminated
Zone or point
SJ
Sprinkler Trouble
Restore
Trouble condition eliminated
Zone or point
SR
Sprinkler Restoral
Alarm/trouble condition has been eliminated
Zone or point
SS
Sprinkler
Supervisory
Unsafe sprinkler system condition
Zone or point
ST
Sprinkler Trouble
Zone disabled by fault
Zone or point
SU
Sprinkler Unbypass
Sprinkler zone bypass has been removed
Zone or point
TA
Tamper Alarm
Alarm equipment enclosure opened
Zone or point
TB
Tamper Bypass
Tamper detection has been bypassed
Zone or point
TC
All Points Tested
All point tested
Unused
TE
Test End
Communicator restored to operation
Unused
TH
Tamper Alarm
Restore
An Expansion Device’s tamper switch restores to normal from an
Alarm state
Unused
TJ
Tamper Trouble
Restore
An Expansion Device’s tamper switch restores to normal from a
Trouble state
Unused
TP
Walk Test Point
This point was tested during a Walk Test
Point number
TR
Tamper Restoral
Alarm equipment enclosure has been closed
Zone or point
TS
Test Start
Communicator taken out of operation
Unused
Data Code Short Description
Long Description
Address Field
Содержание PIMAGUARD
Страница 2: ...2 Sentinel PimaGuard Installation Guide...