Operation
NOTICE
The safety function should be checked after initial commissioning and each
time the plant/machine is changed. The safety functions may only be
checked by qualified personnel.
Status indicators
LEDs indicate the status and errors during operation:
LED on
CH.1
Safety contacts of channel 1 are closed.
CH.2
Safety contacts of channel 2 are closed.
Faults – Interference
By closing or interrupting the input circuit you can check whether the unit switches on or off
correctly.
For safety reasons, the unit cannot be started if the following faults are present:
}
Contact malfunction: As the contact block is connected to a base unit,
reactivation will not be possible if the contacts have welded after the input circuit has
opened.
}
Open circuit, short circuit or earth fault ( e.g. in the input circuit)
}
In the case of an error, the delay-on de-energisation safety contacts may open before
the delay time has elapsed.