PSSu E S 2AI TC(-T)

Operating Manual 22029-EN-06

}

Decentralised system PSSuniversal I/O

Содержание PSSu E S 2AI TC-T

Страница 1: ...PSSu E S 2AI TC T Operating Manual 22029 EN 06 Decentralised system PSSuniversal I O ...

Страница 2: ...cumentation will be gratefully received Source code from third party manufacturers or open source software has been used for some components The relevant licence information is available on the Internet on the Pilz homepage Pilz PIT PMI PNOZ Primo PSEN PSS PVIS SafetyBUS p SafetyEYE SafetyNET p the spirit of safety are registered and protected trademarks of Pilz GmbH Co KG in some countries SD mea...

Страница 3: ... protection mechanisms 13 4 3 Configuration 13 4 3 1 Measuring ranges 13 4 3 2 Open circuit detection 14 4 3 3 Range monitoring 14 4 3 4 Reference temperature 14 4 3 5 Digital filter 15 4 3 6 Scaling 16 4 3 6 1 Manufacturer scaling 17 4 3 6 2 User scaling 17 4 3 6 3 Values that fall outside the range limits 17 4 3 7 Data formats 17 4 3 8 Summary and overview 18 4 3 9 PSSu assignment in system envi...

Страница 4: ...s 27 6 1 1 Mechanical connection of the base modules 27 6 2 Terminal configuration 29 6 3 Connecting the module 30 Section 7 Operation 31 7 1 Messages 31 7 2 Display elements 31 7 2 1 Display elements for module diagnostics 31 7 2 2 Display elements for input status 32 Section 8 Technical Details 33 Section 9 Order reference 37 9 1 Product 37 9 2 Accessories 37 ...

Страница 5: ...his documentation is intended for instruction and should be retained for future reference 1 1 2 Terminology System environment A and B The PSSu system can be used in two different system environments The module s applic ation area is described in the chapter Intended Use of the manual The distinction is made between PSSu in system environment A PSSu in system environment B The distinction is based...

Страница 6: ...ituation that could lead to serious injury and death and indicates preventive measures that can be taken CAUTION This refers to a hazard that can lead to a less serious or minor injury plus material damage and also provides information on preventive measures that can be taken NOTICE This describes a situation in which the product or devices could be dam aged and also provides information on preven...

Страница 7: ...are available in the chapter entitled Intended Use 2 2 Module features The product has the following features Analogue ST inputs 2 Type of inputs Thermocouples in accordance with EN 60584 1 Corresponding sensors are thermocouples configurable with the letter codes R S B J T E K N Voltage measurement configurable 30 30 mV 60 60 mV 120 120 mV Max resolution 0 0625 C 1 μV 30 30 mV 2 μV 60 60 mV 4 μV ...

Страница 8: ... 312500 100000 001 1 3 8 7 4 5 6 10 2 11 9 A B Legend A Electronic module B Base module 1 LEDs for Module diagnostics Status indicator 2 Labelling strip with Name of electronic module Order number Serial number Hardware version number 2D code 3 Labelling strip for the terminal configuration on the base module 4 Name of electronic module 5 Connection level 1 6 Connection level 2 ...

Страница 9: ...4 With screw to loosen tighten the screw terminal on base modules with screw termin als With mechanism to operate the cage clamp on base modules with cage clamp ter minals 10 Round connection holes connection levels 1 2 3 and 4 for connecting the signal lines 11 Mounting slot for colour marker to label the connection level connection levels 1 2 3 and 4 ...

Страница 10: ...l installation EMC compliant Please refer to the guidelines stated in the PSSuniversal Installation Manual The module is designed for use in an industrial environment It is not suitable for use in a domestic environment as this can lead to interference The following is deemed improper use in particular Any component technical or electrical modification to the module Use of the module outside the a...

Страница 11: ...ety accident preven tion Have read and understood the information provided in this description under Safety And have a good knowledge of the generic and specialist standards applicable to the specific application 3 2 2 Warranty and liability All claims to warranty and liability will be rendered invalid if The product was used contrary to the purpose for which it is intended Damage can be attribute...

Страница 12: ...g range Additional signal processing can be defined using the sys tem software see schematic representation of signal processing The individual steps are described in the Configuration section The input signals are transmitted to the head module via the ST module bus As an option the input module can send status information for each input All the configuration data is stored in the head module and...

Страница 13: ...h a modular device description file it is possible to configure all the values Via the USB port of the head module using the PSSuniversal Configurator All the values can be configured using the PSSuniversal Assistant Any configuration via the USB port will overwrite the configuration made via the fieldbus If a module has been configured via the head module s USB port it is locked and cannot be ove...

Страница 14: ...gured for the input This option is activated in the default configuration The module writes the result of range monitoring as follows System environment A in the Status Byte 20 System environment B in the I O data element Overrange or Underrange see PSSu assignment in system environment B 21 The module behaves as follows irrespective of the range monitoring configuration If the value falls below t...

Страница 15: ...g time corresponds approximately to the sum of the filter times of both inputs You can select one of the following filters per input Filtered frequencies Attenuation Filter time per input without reference temperature measure ment Filter time per input with reference tem perature measure ment 60 Hz 90 dB 103 ms 206 ms 50 Hz 80 dB 122 ms 244 ms 50 Hz and 60 Hz 65 dB 122 ms 244 ms 50 Hz and 60 Hz 69...

Страница 16: ...ing Scaling is a multi stage process to adapt the values from the AD converter The straight path in the diagram indicates the default configuration Manuf scaling active Hardware calibration Manufacturer scaling User scaling active User scaling Output formats N Y Y N N ADC raw value ...

Страница 17: ... the resolution will be 1 16 K 1 µV 2 µV or 4 µV 4 3 6 2 User scaling User scaling is an additional scaling level applied after manufacturer scaling You can use this scaling to correct local influences The function is the same as that of manufacturer scaling y a2 256D x b2 or y a2 100H x b2 a2 Amplification factor 256D User scaling is deactivated in the default setting The default value for offset...

Страница 18: ...0 03E8H Analogue value and typical digital value with a measuring range of 100 C 100 C sign and magnitude representation Temperature Decimal digital value Binary digital value Hexadecimal digital value 100 C 1000 1000 0011 1110 1000 83E8H 0 C 0 0000 0000 0000 0000 0000H 100 C 1000 0000 0011 1110 1000 03E8H Range limits Measurement type Lower range limit Upper range limit Two s complement Sign and ...

Страница 19: ... Manufacturer scaling Activated TRUE Manufacturer scaling offset 32768 32767D 0 Manufacturer scaling gain 32768 32767D 160D Amplification factor 10 16 User scaling Deactivated FALSE User scaling offset 32768 32767D 0 User scaling gain 32768 32767D 256D Amplification factor 1 Sign and magnitude representation Deactivated FALSE Two s comple ment is activated 4 3 9 PSSu assignment in system environme...

Страница 20: ...LSB input data 32 MSB input data Input I1 33 LSB input data 48 MSB input data 4 3 9 2 Status byte ST modules for measuring temperature can transfer a variety of status information to the ST PII see table below for the conveyed status The information is transmitted using the input s status byte Structure and contents of the status byte Bit number Content Meaning 0 0 Input value above or equal to th...

Страница 21: ...efined I O data types I O data name I O data type I O data element Meaning I0 11 21 I1 14 24 ST_I_THERMO Data WORD Input data I0 I1 Underrange BOOL 0 Input value above or equal to the lower limit value 1 Value below the lower limit value Overrange BOOL 0 Input value below or equal to the upper limit value 1 Value exceeds the upper limit value ...

Страница 22: ...tatic discharge Electrostatic discharge can damage components Ensure against discharge before touching the product e g by touching an earthed conductive sur face or by wearing an earthed armband 5 1 1 Dimensions Base modules with four connection levels 12 6 mm 76 mm 52 1 mm 8 1 mm 67 7 mm 12 6 mm 56 1 mm 71 8 mm 0 8 mm 128 9 mm 72 6 mm 2 051 0 319 0 496 2 858 0 496 2 99 2 209 2 827 0 031 5 075 2 6...

Страница 23: ... base modules with cage clamp terminals All contacts should be protected from contamination The mechanics of the base modules are designed for 50 plug in out cycles Procedure We recommend that you wire up the base modules before inserting the electronic mod ules Slot the groove on the base module on to the mounting rail from below 1 Push the base module back 2 until you hear it lock into position ...

Страница 24: ... may only be inserted and removed when the load is switched off Unforeseeable error reactions may be triggered if modules are inserted and removed under load When an electronic module is plugged into a base module for the first time one part of the coding element remains on the electronic module while its counterpart is fixed on to the base module This is how the base module is coded The mechanics...

Страница 25: ...nual PSSu E S 2AI TC T 22029 EN 06 25 5 3 1 Inserting an electronic module Procedure The electronic module must audibly lock into position 1 Mark the electronic module using the labelling strips 2 Schematic representation 2 1 1 ...

Страница 26: ...ing operation The configuration data is re tained when a module is changed Effects System environment A In the event of a potential FS communication error the FS section of the PSSu sys tem and all relevant I O Groups SafetyBUS p switch to a STOP condition System environment B All FS hardware outputs on the PSSu system switch to a safe condition The substitute values are used for the modules FS ou...

Страница 27: ...ail Connect the mounting rail to the functional earth via an earthing terminal In environments with strong EMC interference base modules without a C rail provide better protection if the shield is connected If reference temperature measurement is activated please note Use insulated thermocouples Do not earth thermocouples With voltage measurement Use copper wiring The terminal configuration as sta...

Страница 28: ...nto the round fixing hole 2 as far as it will go 5 Pull out the screwdriver 6 Check that the cable is firmly seated 21 11 1 3 2 4 5 6 Please note The minimum cable cross section for field connection terminals on the base modules is 0 14 mm2 AWG26 The maximum cable cross section for field connection terminals is Digital inputs 1 5 mm2 AWG16 Digital outputs 2 0 mm2 AWG14 Inputs outputs on the counte...

Страница 29: ...ot essential To crimp the ferrules you can use crimp pliers crimp form A or C conforming to EN 60947 1 such as the PZ 1 5 or PZ 6 5 from Weidmüller for example Maximum torque setting 0 8 Nm Use copper wiring 6 2 Terminal configuration Base module Terminal configuration Screw terminals PSSu BP 1 8 S J PSSu BP 1 8 S TJ Cage clamp terminals PSSu BP 1 8 C J PSSu BP 1 8 C TJ Without C rail 11 Input I0 ...

Страница 30: ...als PSSu BP C 1 8 C J PSSu BP C 1 8 C TJ With C rail 11 Input I0 21 Input I0 12 22 n n 13 23 C rail supply shield connection 13 23 linked within the base module 14 Input I1 24 Input I1 21 11 22 12 23 13 24 14 6 3 Connecting the module Input circuit Without C rail With C rail Thermocouple 21 11 22 12 23 13 24 14 I0 I0 I1 I1 21 11 22 12 23 13 24 14 I0 I0 I1 I1 C C ...

Страница 31: ...error Incorrect module type configured The configured hardware registry does not match the actual hard ware registry ST communication error Error during ST communication Change faulty module Bus termination error There is no terminating plate or there is a bad contact with the module bus Install a terminating plate with in tegrated end bracket or insert the base modules together correctly 7 2 Disp...

Страница 32: ...tatus Each input is assigned an LED for displaying the input status LEDs I0 and I1 11 21 I0 I1 Err I0 I1 Err LED Meaning Designa tion Colour Status Signal Input Ter minal I0 No sig nal de tected I0 Input 1 11 21 Green Signal detected I1 No sig nal de tected I1 Input 2 14 24 Green Signal detected ...

Страница 33: ...are version head modules 1 8 0 1 8 0 Electrical data 312500 314500 Internal supply voltage module supply Module s power consumption 0 63 W 0 63 W Periphery s supply voltage peri phery supply Voltage range 16 8 30 0 V 16 8 30 0 V Module s current consumption with no load 15 mA 15 mA Module s power consumption with no load 0 36 W 0 36 W Max power dissipation of module 1 00 W 1 00 W Analogue inputs 3...

Страница 34: ... Voltage Measuring range 60 mV 60 mV Type Voltage Voltage Measuring range 120 mV 120 mV Input filter Digital filter Digital filter Filter time per input 2 wire meas urement with attenuation Attenuation 90 dB 60 Hz 90 dB 60 Hz Filter time 103 ms 103 ms Attenuation 80 dB 50 Hz 80 dB 50 Hz Filter time 122 ms 122 ms Attenuation 65 dB 50 60 Hz 65 dB 50 60 Hz Filter time 122 ms 122 ms Attenuation 69 dB ...

Страница 35: ...yes Environmental data 312500 314500 Climatic suitability EN 60068 2 1 EN 60068 2 14 EN 60068 2 2 EN 60068 2 30 EN 60068 2 78 EN 60068 2 1 EN 60068 2 14 EN 60068 2 2 EN 60068 2 30 EN 60068 2 78 Ambient temperature In accordance with the standard EN 60068 2 14 EN 60068 2 14 Temperature range 0 60 C 40 70 C Storage temperature In accordance with the standard EN 60068 2 1 2 EN 60068 2 1 2 Temperature...

Страница 36: ...ove sea level 2000 m 5000 m Airgap creepage In accordance with the standard EN 60664 1 EN 61131 2 EN 60664 1 EN 61131 2 Overvoltage category II II Pollution degree 2 2 Protection type In accordance with the standard EN 60529 EN 60529 Mounting area e g control cab inet IP54 IP54 Housing IP20 IP20 Mechanical data 312500 314500 Material Bottom PC PC Front PC PC Coding PA PA Dimensions Height 76 0 mm ...

Страница 37: ... PSSu BP 1 8 C J Base module without C rail with cage clamp terminals with in tegrated cold junction compensation 312 603 PSSu BP 1 8 C TJ Base module without C rail with cage clamp terminals with in tegrated cold junction compensation T type 314 603 PSSu BP C 1 8 S J Base module with C rail and screw terminals with integrated cold junction compensation 312 612 PSSu BP C 1 8 S TJ Base module with ...

Страница 38: ...ET p ThE SPIrIT Of SAfETY are registered and protected trademarks of Pilz Gmbh Co KG in some countries We would point out that product features may vary from the details stated in this document depending on the status at the time of publication and the scope of the equipment We accept no responsibility for the validity accuracy and entirety of the text and graphics presented in this information Pl...