Diagnostics and Troubleshooting
Operating Manual PSENvip RL D P Set
1001641-EN-09
| 92
9.2
Error messages
Error messages appear on the display as soon as an error occurs.
ERROR
OSSD OFF
NORMAL OPERATION
Error in the
optical system
Fig.: Error messages on the display
Error message on the
display
Error message
Remedy
Not relevant to
the user
Press ESC to proceed
Not relevant to the user
Press ESC to continue
1.) Acknowledge the error by
pressing ESC
Internal error
STOP
Internal error
STOP
1.) Restart the PSENvip: Switch
supply voltage off and then on
again
2.) Change the receiver
Wiring error
Wiring error
1.) Restart the PSENvip: Switch
supply voltage off and then on
again
2.) Ensure that the wiring is cor-
rect
3.) Rectify short circuit between
the inputs and/or outputs and 0
V / 24 V
4) Change the receiver
Initial
commissioning
Initial commissioning
1.) Please contact Pilz
No valid data
detected (tool and/
or overrun)
No valid data detected (tool
and/or overrun)
1.) Enter overrun and/or make
adjustment during tool change
No adjustment
performed after
tool change
No adjustment performed
after tool change
1.) Make adjustment during tool
change