PSEN ma1.3-22 M12/8 VA
Operating Manual PSEN ma1.3-22 M12/8 VA
1004511-EN-02
18
NOTICE
The safety function should be checked after initial commissioning and each
time the plant/machine is changed. The safety functions may only be
checked by qualified personnel.
Application in series connections
}
Always test the function with the PSEN ix1 interface and connected evaluation device.
Application in single connections
}
Always test the function with the control cabinet terminal PSEN ix0 F1 mag and con-
nected evaluation device.
Dimensions in mm
Safety switch
60
36
1
M12x1
Actuator PSEN ma1.3-08/VA
25
19
M12x1
Technical details
General
Certifications
CE, EAC (Eurasian), ECOLAB, TÜV, UL/cUL
Sensor's mode of operation
Magnetic
Coding level in accordance with EN ISO 14119
Low
Design in accordance with EN ISO 14119
4
Classification in accordance with EN 60947-5-3
PDDB
Electrical data
Supply voltage
Voltage
24 V
Kind
DC
Voltage tolerance
-20 %/+20 %
Max. switching frequency
1 Hz
Lowest operating current (Im)
1 mA
Max. voltage drop (Ud)
0,5 V