PNOZ V
Operating Manual PNOZ V
21115-EN-07
| 14
Technical details
General
774789
774790
774791
Certifications
CCC, CE, EAC, TÜV,
UKCA, cULus Listed
CCC, CE, EAC, TÜV,
UKCA, cULus Listed
CCC, CE, EAC, TÜV,
UKCA, cULus Listed
Electrical data
774789
774790
774791
Supply voltage
Voltage
24 V
24 V
24 V
Kind
DC
DC
DC
Voltage tolerance
-15 %/+10 %
-15 %/+10 %
-15 %/+10 %
Output of external
power supply (DC)
5 W
5 W
5 W
Residual ripple DC
160 %
160 %
160 %
Duty cycle
100 %
100 %
100 %
Max. inrush current im-
pulse
Current pulse, A1
10 A
10 A
10 A
Pulse duration, A1
0,5 ms
0,5 ms
0,5 ms
Inputs
774789
774790
774791
Number
2
2
2
Voltage at
Input circuit DC
24 V
24 V
24 V
Start circuit DC
24 V
24 V
24 V
Feedback loop DC
24 V
24 V
24 V
Current at
Input circuit DC
50 mA
50 mA
50 mA
Start circuit DC
40 mA
40 mA
40 mA
Feedback loop DC
40 mA
40 mA
40 mA
Max. overall cable resist-
ance Rlmax
Single-channel at UB
DC
100 Ohm
100 Ohm
100 Ohm
Dual-channel without
detection of shorts
across contacts at UB
DC
200 Ohm
200 Ohm
200 Ohm
Relay outputs
774789
774790
774791
Number of output con-
tacts
Safety contacts (N/O),
instantaneous
3
3
3
Safety contacts (N/O),
delayed
1
1
1
Auxiliary contacts (N/C)
1
1
1
Max. short circuit current
IK
1 kA
1 kA
1 kA