Function description
Operating Manual PNOZ m ES Profinet
1003386EN02
11
4
Function description
4.1
Operation
The virtual inputs and outputs that are to be transferred via PROFINET are selected and
configured in the PNOZmulti Configurator. The base unit and the expansion module PNOZ
m ES Profinet are connected via a jumper.
After the supply voltage is switched on or the PNOZmulti 2 is reset, the expansion module
PNOZ m ES Profinet is configured and started automatically.
LEDs indicate the status of the fieldbus module PROFINET.
The configuration is described in detail in the PNOZmulti Configurator's online help.
INFORMATION
The GSDML file is available on the Internet at www.pilz.de.
4.2
Data access
The data is structured as follows:
}
Virtual data
–
Input area PNOZ m ES Profinet
The values for the inputs are set as an output in the Master and transferred to the
PNOZmulti 2.
–
Output range PNOZ m ES Profinet
The outputs are configured in the PNOZmulti Configurator and transferred to the
Master.
}
Status of LEDs:
Bit 0 … 4: Status of LEDs on the PNOZmulti 2
–
Bit 0: OFAULT
–
Bit 1: IFAULT
–
Bit 2: FAULT
–
Bit 3: DIAG
–
Bit 4: RUN
}
Data exchange is displayed in Bit 5.
}
Polling the usable data: 2 Bytes with the table number and segment number are sent by
the Master for access to the usable data table (15 Bytes are returned to the Master).
Detailed information on data exchange (tables, segments) is available in the document
"Communication Interfaces" in the section entitled "Fieldbus modules".