PNOZ X1
Operating Manual PNOZ X1
19045-EN-10
| 7
Unit features
}
Positive-guided relay outputs:
– 3 safety contacts (N/O), instantaneous
– 1 auxiliary contact (N/C), instantaneous
}
Connection options for:
– E-STOP pushbutton
– Safety gate limit switch
– Start button
}
LED display for:
– Supply voltage
– Switch status of the safety contacts
Safety features
The safety relay meets the following safety requirements:
}
The circuit is internally redundant with built-in self-monitoring.
}
The safety device remains effective in the case of a component failure.
}
The correct opening and closing of the safety device relays is tested automatically in
each on-off cycle.
Block diagram/terminal configuration
A1
A2
Y1
Y2
23 33
13
24 34
14
Input
K1
K2
42
41
Start
*Safe separation from non-marked area in accordance with EN 60947-1,
6 kV, basic insulation between all safety contacts.