6.2.7.5
Advanced settings
Level
Menu designation
Description
Settings
1
Positions Para-
meter
Settings for position monitoring
functions
2
Position (1 ... 4)
Window width
Default
1 pulse
Enter width of position window for
position monitoring functions 1 ...
4
1 ... 24,900,000 pulses
or the corresponding value in the selec-
ted unit
1
Direction Parameter
Settings for direction monitoring
2
(Direct. Left max.
right, Direct. Right
max. left)
Default
0 pulse
Enter max. tolerated number of
pulses (or Edg, m, rot) in the
wrong direction.
1 ... 24,900,000 pulses
or the corresponding value in the selec-
ted unit
1
Mode
Select Input
Default
None
Setting for using the select inputs
-All 16
-1 from 4
-None
1
Delay
Select Input
Default
tdl : 0 ms
Enter delay time of the select in-
puts Y10 – Y13
Info: The states of the select in-
puts are only adopted if they were
unchanged during the set time.
0 ... 30.0 s
1
Function Hysteresis
2
(F1 ... F9) Function
Hysteresis
Default
1 %
Enter hysteresis for the switching
functions F1 ... F9
(not effective with position and dir-
ection monitoring)
0 ... 50 %
1
Output Delay
Setting for the delay effect and
delay time for the outputs
2
Delay Output
(Rel.1 ... Out 4)
Default
On 0 ms (display
only)
Setting for the delay time effect
and delay time for the respective
output
3
Delay Effect
(Rel.1 ... Out 4)
Default
On delay
Enter whether the delay time is to
be activated when switching on,
switching off, or switching on and
off.
- On
- Off
-OnOff
3
Delay Time
(Rel.1 ... Out 4)
Default
tdO: 0 ms
Select delay time for the respect-
ive output
0 ... 30.0 s