Commissioning
Operating Manual PNOZ s30
1001715-EN-15
53
6.2.7.4
Settings
Level
Designation
on the display
Description
Settings
1
Permanent Display
Default
H : Min : Sec (system
time)
v (current speed of
track AB)
Position
Permanent display
Current values and information re-
garding configuration are dis-
played.
You can change the permanent
display on the display
Display combinations:
-vz (current speed of track Z)
-v (current speed of track AB)
- Position
- Switch functions F1...F9
- v (current speed of track AB)
- Position
- Line 1/2: F1/F2, F3/F2, F5/F4, F7/F6
or F9/F8
(parameters selected via select inputs).
v (current speed of track AB)
- H : Min : Sec (system time)
- v (current speed of track AB)
- Position
1
Displ. Units
Speed: Dist:
Default
Hz Imp
Select unit of speed and distance
(position).
Speed:
(speed)
- Pos.
(distance/posi-
tion)
Hz Imp (pulse)
Hz Edg (edge)
m/s m
m/min m
m/h m
rps rot
rpm rot
1
Conversion
Default
1 Hz= 1 Imp/s
Unit conversion.
Enter ratio of unit to pulses.
Display
1 Hz= 1 Imp/s
1 Hz = 4 Edg/s
1 m = x Imp (x = 1 ... 10,000,000
pulses)
1 rot = x Imp (x = 1 ... 10,000,000
pulses)
1
Encoder Settings
Create encoder configuration for
the tracks A,
/A, B, /B, Z, /Z, S